Professional Documents
Culture Documents
of
Project Report
Submitted by
Mr Ganesh Kudva
Assistant Professor - Senior Scale,E&E Engg. Dept.
In partial fulllment of the requirements for the award of the degree of
BACHELOR OF TECHNOLOGY
IN
ELECTRICAL AND ELECTRONICS ENGINEERING
CERTIFICATE
This is to certify that the project titled Microcontroller based Protection of
Three Phase Induction Motor is a record of the bonade work done by Rohan
partial fullment of the requirements for the award of the Degree of Bachelor of Tech-
nology (B.Tech.) in Electrical and Electronics Engineering (E & E Engg) by Manipal
Institute of Technology, Manipal, Karnataka (A Constituent College of Manipal Uni-
versity), during the academic year 2016-17.
At the very beginning we would like to express our deepest gratitude to the
almighty for giving us the strength and the composure to complete our B-Tech
courses and prepare this report within the scheduled time.
During the period of our project work, we have received generous help from many
quarters, which we would like to put on record here with deep gratitude and great
pleasure. Words actually will never be enough to express our gratefulness.
We would like to express our gratitude respect to Dr. GK Prabhu, Director MIT
and Dr. Savitha G Kini, Head of Department of E& E Engineering and all the
Professors of Manipal Institute of Technology, Manipal for their constant guidance,
advice, encouragement every possible help in the overall preparation of this report.
We would also like to thank our project guide Mr. Ganesh Kudva, Assistant Pro-
fessor, Department of E& E Engineering for all his support and insight which has
helped us to complete our project successfully. His deep knowledge about electrical
motors made us understand the core concepts that are related to our project topic.
A special thanks also goes to all other sta members and laboratory technicians
for their support valuable suggestions during the course of project and to make
this endeavor of ours, a successful one.
The plan to achieve the above aim will be done in conjecture with appropriate
testing done at each individual level, that is with and without connecting the
motor.The relay circuit was rst tested without connecting the motor and only
when it proved eective the motor was connected and all of the above conditions
were induced in the motor and the protection system was introduced to protect
the motor from these faults. We used a hall current sensor in addition with an
instrumentation amplier to detect changes in current and step down transformers
for each phase for detecting changes related to voltage.
In conclusion, we obtained a protection system which could detect all of the above
faults and disconnect the motor with the help of the microcontroller-relay circuitry
as and when these faults occur.
Contents
1 INTRODUCTION 1
1.1 Background and Motivation . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Literature Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 BACKGROUND THEORY 5
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.1 Single phasing . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 Over voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.3 Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.4 Undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 METHODOLOGY 8
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Motor testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Ratings of Motor under test . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Proposed Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 Implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5.1 Hardware Implementation . . . . . . . . . . . . . . . . . . . 11
3.5.2 Software Implementation . . . . . . . . . . . . . . . . . . . . 17
3.6 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4 RESULT ANALYSIS 21
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Result Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5 CONCLUSION AND FUTURE WORK 26
6 BIBLIOGRAPHY 27
List of Figures
i
List of Tables
ii
Chapter 1
INTRODUCTION
Induction motors are the most widely used motors in industries because they are
rugged, reliable and economical. They require lesser maintenance when compared
with other type of motors. Its speed control is simple and
exible because of
advance development made in the eld of power electronics and electrical drives.
The protection of induction motor plays an essential part in its long life and
this will in turn be benecial for the productivity of the industry where they are
being used. The small scale industries are not well equipped to include expensive
protection systems which make use of PLCs hence it is imperative that a cheap
and aordable solution is designed for protection of these motors employed in their
industries as and when these type of faults occur. Subsequently a microcontroller
based relay actuating system has been designed for protection of 3-phase induction
motors against over voltage, under voltage, single-phasing and overload.
1
3 phase induction motors worldwide are plagued by various faults which dras-
tically aects their performance and they being the work-horses of industries, this
scenario in turn aects the industrial performance and productivity. Hence to
dissolve the motor from these most occurring (refer - bar graph) faults namely
overvoltage,overload,single-phasing and undervoltage, we decided to make a sys-
tem which is able to do just that. Looking at the wide use of induction motors in
almost every sector of the industrial arena, it is imperative that such a protection
system is built with impeccable accuracy and precision so that these induction
motors run up to their desired life without any hassles.
[1] expressed that three phase induction motor can proceed to run when one phase
of the supply left open. This might be because of any combine blowing or opening
of defensive gadget of the motor, at venture down transformer or at feeder end. At
this condition the three-phase induction motor keep on running however the motor
will warm up rapidly and it ought to be shielded by expelling it from the benet
at the moment of single staging. At the point when phase opens at venture down
transformer then again at feeder end, the stator and rotor losses increments to ten
times and the shaft output power declines to zero. However, in the event that the
single staging happens at motor terminals the losses builds twice as contrast with
steady state losses. To ensure the motor all the terminal ought to be open.
[2] have proposed the assurance of three phase induction motor in view of volt-
age estimation and is insucient to secure the motor if the blame happens at
conveyance transformer or at substation feeder. On the o chance that blame
happens at motor terminals then the voltage estimation can ensure the motor
extremely well. The current estimation gadget ought to be executed inside the
defensive gadget. They have likewise proposed a phase estimation gadget which
can quantify the phase dierence of the voltages since when the blame happens
at whatever other area as opposed to the motor terminals, then the blamed phase
will draw negative succession current and work as a voltage generator. The voltage
created is near line voltage however the estimation plan is not ready to distinguish
the blame, however the phasor dierence of the blamed phase changes.
2
1.3 Ob jectives
The main objective of the work is to make a cheap and reliable protection system
for three-phase induction motor to protect it from:
Single-phasing
Overvoltage
Overload
Undervoltage
Our project deals with protection of induction motor from 1)Single-phasing 2)Over-
load 3)Undervoltage 4)Overcurrent. From reference[1], it can be clearly understood
that single phasing can be a major problem an induction motor could face. When
phase opens at step down transformer or at feeder end, the stator and rotor losses
increases to ten times and the shaft output power decreases to negligible. But if
the single phasing occurs at motor terminals the losses become twice as compared
to steady state losses. From reference[2], we get to know that when the fault
occurs at the distribution transformer or at the feeder site, it could still be fatal
and disrupt the functioning of the induction motor. If fault occurs at the motor
terminals, then the voltage measurement can protect the motor very well. The
current measurement device should be implemented within the protective device.
Industries tried to accomplish this task of protection using PLC techniques, but
we are doing the same using microcontrollers simply because electrical parameter-
s cannot be visualized by Programmable Logic Controller (PLC) based method
whereas the microcontroller negates the above issue.
3
Here is an excerpt of the technique proposed earlier by us. here the priority en-
coder provides the digital codes needed to implement a set of protection techniques
for various problems faced by the motor. These codes are read by the microcon-
troller and it is programmed in such a way which lets it to control the functions
of the motor relay driver, which disables the motor from the supply whenever any
one of the above fault occurs in any one of its terminals.
1.4 Summary
To summarise, these protection techniques are vital for better functioning of induc-
tion motor. As induction motors are the backbone for any industry, hence these
techniques may prove paramount for glib running of most of today's industries.
4
Chapter 2
BACKGROUND THEORY
2.1 Introduction
Induction motors are the workhorses of almost every industry due to their
exi-
bility, rigidity and low assembling cost. Induction motors are the solid machines.
however their damage rate is roughly 3 percent and it can be as high as 12 percent
in paper industry. repair work of the machine in the industry might be costly
hence the protection framework may upgrade the unwavering quality, individual
well being and shield the motor from over heating. The major faults which could
damage the induction motor are :
Single phasing
Overvoltage
Overload
Undervoltage
On the o chance that the state of single staging emerges amid the running of
motor, the winding of motor gets warmed because of the negative sequence current
in the faulty phase. Two phases of three phase induction motor will get control
supply in single staging condition and they deliver negative sequence current in
the faulty phase on the grounds that the inward association of three phase motor
are associated with each other. Single staging problem may emerge at three areas:
Opening one phase of the primary side of substation transformer.
Opening one phase of the primary side of distribution transformer.
Opening one phase at the motor terminals.
5
2.1.2 Over voltage
The over voltage occurs when any one of the phase voltage increases above the
rated voltage and it leads to harmful eect on machine insulation. In order to
overcome this problem, over voltage sensing unit is designed. The designed unit
consists of three step down transformers to step down the phase voltage to 8V.
This step down voltage is rectied and ltered to get dc voltage proportional to the
phase voltage. This dc voltage is compared with reference voltage which has been
set by the pre-set value given to the comparator. This comparator is formed using
quad op-amp IC LM 324 and the output of the comparator is fed directly to the
micro controller .Under voltage occurs, when reduced supply voltage with the rated
mechanical load on the machine produces and inturn increases the stator and rotor
losses. In order to overcome this problem, similar design is implemented as done in
the case of over voltage condition mentioned above.Due to this increased current,
excess heating voltage sensing circuit is designed .The under voltage sensing circuit
uses the dc output from the over voltage sensing circuit and compared with the
reference voltage in the comparator wired using op-amp LM324. The only change
is the reference voltage given to the negative terminal of the comparator is lowered
to a certain value below which the problem of undervoltage occurs.The output here
is again fed back to the microcontroller which then trips the relay circuit as and
when needed.
2.1.3 Overcurrent
6
2.1.4 Undervoltage
2.2 Summary
In this chapter,the various potential faults and problems which could arise in the
induction motor were discussed, and the additional issues these faults bring to
the motor and other systems were also highlighted. The methods employed to
protect the motor when any of these faults arise was also discussed in a concise
manner. The additional faults like in the case of overcurrent(overload) create
local temperature and heat hot spots which bring about a new set of diculties
regarding temperature management in the motor core and in its windings. Hence
these methods are of utmost importance.
7
Chapter 3
METHODOLOGY
3.1 Introduction
This chapter deals with the proposed block diagram of the project, hardware
requirements for over/under voltage and algorithm of the proposed code for the
project implementation.
8
Figure 3.1: Motor Testing for no load and full load conditions
9
3.4 Proposed Solution
Figure 1.1 block diagram was an alternative approach of designing the pro-
tection system because we need a more ecient protection system, which means
lesser number of equipments to get the desired output. Hence, as seen from gure
3.1 we can accomplish the same task by omitting the priority encoder altogether,
hence a more ecient and cost eective system can be designed to cater the needs
of small scale industries.
This LM324 IC has four dierent comparators, hence four dierent comparisons
can be performed simultaneously and if we look at the numbers of faults from which
we are protecting the induction motor, LM324 fullls all the desired objectives.
10
3.5 Implementation
Overvoltage/Undervoltage
When the line voltages applied to a polyphase induction motor are not equal, un-
balanced currents in the stator windings will result. A small percentage voltage
unbalance will result in a much larger percentage current unbalance. Consequent-
ly, the temperature rise of the motor operating at a particular load.The imbalance
also leads to a much larger proportion of the current imbalance. Therefore the high
temperature of the engine operates in a certain load and the voltage imbalance
ratio will be greater than to operate the engine under the same conditions with
the balanced voltages.
The term single-phasing is the term used when one phase of a three-phase sys-
tem opens. This can occur on either the primary side or secondary side of a
distribution transformer. Three-phase induction motors, when not individually
protected by three time-delay, dual-element fuses, or three overload devices, are
subject to damaging overcurrents caused by primary single-phasing or secondary
single-phasing.
The worst case of single phasing occurs when system is star/delta or delta/star, in
this case the unbalance of voltages is quite more than when they are in delta/delta
or star/star.In the former case the motor current in one secondary phase increases
to 230 percent of normal current and this latter case the increase is also damaging
but is limited to 170 percent rather than the 230 percent value.
And as discussed before, when single phasing occurs the rate of increase of tem-
perature is more than the rate of increase of current in the lines. Hence due to
this reason the deterioration of the motor is more rapid than when overload or
overcurrent faults occur. Hence it is vital that the protection system is able to
isolate the power connections (in this case the relay drive module does the job) to
the motor from the supply in the nick of time and save the motor from going out
of business and maintain its stability and sustenance.
12
Overload
13
Figure 3.6: Testing of current sensor ACS712
This graph was obtained without using the AC coupling feature of the digital
oscilloscope hence the oset of 2.5 V is clearly visible as we look at the graph. This
graph helped us to see the AC current wave as it went through the hall current
sensor. If we applied this current converted to voltage value to the rectier, the
rectier would not be able to decipher what is the AC component to be change to
DC because of the presence of the DC oset component and eventually due to this
problem the comparator would not sense the signal as it needs a proper DC input
to recognize its inherent comparing logic (as we making it compare with a xed
14
DC reference voltage given by the DC regulated power supply component (RPS)).
15
This graph was obtained after using the AC coupling feature of the digital
oscilloscope hence the oset of 2.5 V is not visible as we look at the graph. The
coupling feature of the digital oscilloscope works on the principle of isolation of DC
components with the help of the coupling capacitor which only passes the AC part
and keeps out the DC part from casting its in
uence on the circuit parameters.
In reality the logic of the coupling capacitor can only be obtained and works well
when the digital oscilloscope is put to use and it is very tough to make it work
without the digital oscilloscope and an alternative approach is needed. Hence we
are making the same thing(elimination of the DC oset part) happen by using the
instrumentation amplier.
16
AD620 is an 8 pin IC. AD620 is well suited for multiplexed applications with
its settling time of 15 s to 0.01 percent, and its cost is low enough to enable designs
with one in-amp per channel.
AD620 has a incredibly high accuracy of 40 ppm with maximum nonlinearity, low
oset voltage of 50 V max, and oset drift of 0.6 V/C max, is ideal for use in
precision data acquisition systems, such as weigh scales and transducer interfaces
hence has also been used in designing systems where such precision techniques
(like protection systems for motors as done here ) are required to detect changes
and act upon it.
This device was used by us to eliminate the DC voltage oset given by the hall
current sensor. The elimination is based on the input taken by this IC. The input
of the instrumentation amplier is proportional to the dierence between the Vin
and Vref given to the IC and this can amplied to any value by varying the resis-
tance value which is connected between pins 1 and 8.
Overvoltage Algorithm:
Step1: Start
Step8:In case of fault, output port becomes high and it trips the relay thus,
disconnecting the motor from supply.
17
Undervoltage Algorithm:
Step1: Start
Step8:In case of fault, output port becomes high and it trips the relay thus,
disconnecting the motor from supply.
Overcurrent Algorithm:
Step1: Start
Step8:In case of fault, output port becomes high and it trips the relay thus,
disconnecting the motor from supply.
18
Single-Phasing Algorithm:
Step1: Start
Step8:In case of fault, output port becomes high and it trips the relay thus,
disconnecting the motor from supply.
19
3.6 Summary
20
Chapter 4
RESULT ANALYSIS
4.1 Introduction
21
Figure 4.2: Display for Overvoltage testing
Table 4.2: Overvoltage testing details
If the voltage is increased to more than its rated value (here the rated voltage set
by us is 420V) then the overvoltage problem is detected and the microcontroller
LCD starts to display the above message and the relay driver module trips the
supply to the motor causing the motor to stop.
22
Table 4.3: Single-Phasing testing details
The RYB sequence of the supply is connected in star and the autotransformer
is connected in delta and the motor is also connected in delta.
Now as previously mentioned the single phasing more adversely aects those sys-
tems which are either connected in start/delta or delta/star rather than those
connected in star/star or delta/delta as current in the former increases to 230
percent of rated current while in the latter the current increases to 170 percent
which is also damaging but relatively it is lesser than the former. This above is
not the only problem, there is also a lot of voltage unbalance which could occur
if we remove the R-phase of the supply directly rather than opening any phase of
the 3-phase autotransformer to induce single phasing condition in the motor.
23
Table 4.4: Undervoltage testing details
If the voltage is reduced to less than its running condition value ie 400V
(here the threshold value of voltage for this condition set by us is 370V) then the
undervoltage problem is detected and the microcontroller LCD starts to display
the above message and the relay driver module trips the supply to the motor
causing the motor to stop.
24
Table 4.5: Overcurrent testing details
If the load is increased to more than its rated value (here the rated current
of the 3-phase induction motor is 3.3A) then the overcurrent problem is detected
and the microcontroller LCD starts to display the above message and the relay
driver module trips the supply to the motor causing the motor to stop.
25
Chapter 5
Protection of three phase induction motor from undervoltage, single phasing, over
current and overvoltage ensures smooth running of the 3- phase induction motor
and improves its lifetime and its eciency. Generally theses faults come about
when we violate with the limits of the motor (exceed its ratings). We also during
the time we spent working on the project learnt a lot of theoretical concepts re-
garding motors in general and AC motors in particular.
We learnt how adversely these faults aect the functioning of the motor. Learnt
more about single phasing which is a very common type of fault occurring with-
in induction motors and learnt how badly it eects the motor when connected in
dierent type of orientations (namely star/star,delta/delta or star/delta,delt/star).
We also managed to use and test a lot of electrical and electronic components
during the various phases of our project work. For overall functioning we used a
ESA MCB-51 microcontroller, which was the main control unit and operated the
relays. which eventually tripped the connection to the motor whenever any fault
occurred.
For current sensing,we initially used a current transformer to test out conditions
but we eventually went with the hall current sensor(ACS712) as gives a much more
stable and suitable output to the comparator block. We also got to use and learn
about the instrumentation amplier(AD620) and we got to this result after a lot
of testing to nd a solution for removing the DC oset given by the current sensor.
The instrumentation amplier helped us to eliminate the DC oset as its input
is proportional to the dierence of voltages (Vin and Vref) and with a help of a
variable resistance we can vary the gain to get a suitable output.
For future this type of a protection system will be useful to all small scale in-
dustries as it is way cheaper than protection systems designed with the help of
PLCs and also this protection system is able to visualize and analyze the current
and voltage parameters which cannot be done by the latter.
26
Chapter 6
BIBLIOGRAPHY
Project Details: