You are on page 1of 13

Safe Metal Clad Switchgears up to 36KV

ISO 9001-2015 Certified

Factory Address:
Plot No: A-24, Sipcot Industrial Growth Centre, Mathur Village
Oragadam, Sriperumbudur Taluk, Kancheepuram District
Tamilnadu - 602105, India
Ph: 044-27172035

Office Address:
C-22, 12th Cross Street, Hindu Colony, Nanganallur
Tamilnadu, Chennai - 600061, India
Ph: 044-42187837
Email: info@howellenergysystems.com

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


ABOUT US:
Design, Manufacture and Supply of Medium voltage & Low voltage Switch Gear up to 36Kv and
Control & Relay Panels up to 400Kv

Howell Energy Systems Pvt. Ltd is a leading company in Medium Voltage Components
Integration and is highly skilled in all aspects of switchgear manufacturing with technical
expertise that ensures safety, reliability and convenience for customers. The production unit
is fully equipped with hi-tech machines for electrical assembly, testing and inspection.
We are the manufacturer of safe metal clad switchgear panels ranging from 12KV-36KV as
per IEC Standards. In this arrangement M/s Schneider Electric (I) Pvt. Ltd. supplies VCB
Circuit Breakers trucks and Howell manufacturers tailor made panels suitable to customer
requirements.

Howell Energy Systems Pvt. Ltd is ISO 9001-2015 certified and focuses on Zero defects.
The company’s head office is at C-33, 12th Cross, Hindu Colony, Nanganallur, Chennai and
the production division is at SIPCOT, Oragadam, Chennai - India.

PRODUCT RANGE:

Description 11kV Panel 22kV Panel 33kV Panel

Breaker Type Vacuum Vacuum Vacuum

Breaker Model HVX/Evolis HVX/Evolis HVX

Rated Voltage (kV) 12 24 36

Rated Current (A) Upto 1250 A Upto 1250 A Upto 1250 A

Short time current Upto 26.3kA/sec Upto 26.3kA/sec Upto 26.3kA/sec

Impulse withstand Voltage (kVp) Upto 95kVp Upto 125kVp Upto 170kVp

Panel type Indoor/Outdoor/RMG Indoor/Outdoor/RMG Indoor/Outdoor/RMG

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


SALIENT FEATURES:

 Modular design for Indoor/Outdoor enclosures.

 Availability of emergency tripping arrangement without having to open the front


door of the breaker chamber

 Horizontal Draw out type

 Self-aligning cluster contact owing to robust design

 Fully Interlocked to ensure operational safety

 Explosion Vents provided for all HT- Compartmentalized in Indoor design.

 Contracted with CRCA Sheets with easily portable bolt & Nuts.

 Tailor-made for individual requirement.

 Maintenance free

 Modifications for switchgear equipment easily accommodated.

 Copper and Aluminium Bus bars as suitable.

 Inspection Windows provided for VCB Chamber.

 Bus Bar PT and feeder line PT facility available and provided as required.

 Protection, measuring, monitoring, controlling features customized as per


requirement.

 Metering compartment consisting of Numeric/Static or Electromagnetic relays

 Necessary interlocks as per international standards requirement are provided.


Secondary plugs are provided with interlock through self-aligned contacts.

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


HVX - CIRCUIT BREAKERS - DESIGNED FOR FLEXIBILITY:

Technical Characteristics

Rated Voltage (kV) 12 17.5 24 36

Rated lightning impulse withstand Voltage


75 95 125 170
(kV)

Rated short time power frequency Voltage


28 38 50 70
(kV)

Rated short circuit breaking current (kA) Upto 26.3kA Upto 31.5kA Upto 26.3kA Upto 26.3kA

Rated Current (A) 800 - 1250 800 - 1250 800 - 1250 800 - 1250

HVX is available in a range of standard, draw able configurations, with plug-in connections. Breaker
Voltage 12/24/36 kV with modified pole parts for increased withstand voltage is available.

ACB 11KV VCB

11Kv VCB 33Kv VCB

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


AIR INSULATED INDOOR SWITCHGEAR CUBICLE TYPE:
Indoor Application - IP 4X certified.

Design various Substations & Utility buildings.

Available with current ratings up to 1250A and Short Time Ratings of 26.3kA/3sec Panel is designed
and type tested to meet the requirements of IEC-60298

33KV OUTDOOR PANEL:


Outdoor Kiosk Panels:

The KIOSK is specially designed for unmanned substations in the Outdoor distribution network. It is a
standalone vacuum switchgear system with built in self-driven independent control supply for self-
tripping & closing of CB. The product is well equipped for metering, control, protection & SCADA
compatibility.

The product is available in two basic designs - Roof bushing type with incoming & outgoing
through roof bushings (Rated Voltage: 12 & 36 kV) Line up type with incoming through rear
bottom/side cable entry & outgoing through rear bottom/side cable entry.

11KV RMG PANEL:

Ring main unit is used in Medium voltage switchgear. It is basically used at the load connection points
of a Ring type distribution network for an uninterrupted power supply. Alongside, it also protects
your secondary side transformer from the occasional transient currents. Depending on your
applications and loading conditions you can use a switch fuse combination or a circuit breaker to
protect the transformer. This transformer connected to the switch fuse/ circuit breaker is called your
T off. In a common arrangement you have Load break switches on both the sides of your T off. Ring
main Units come in standard ratings of 11/22/33 kV, 800A/1250 A, 26.3kA/3 sec.

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


Detailed Specifications of Indoor/Outdoor HVX BREAKER Panels:

INDOOR/OUTDOOR INDOOR/OUTDOOR
S.NO DESCRIPTION
HES-11 -HVX HES-33-HVX

1 Frequency 50Hz 50Hz

2 Rated Voltage 11KV 33KV

3 System voltage 12KV 36KV

4 Rated current Upto 1250A Upto 1250A

5 Short Circuit current rating with duration Upto 26.3kA Upto 26.3kA

6 Certificate/Report of short circuit type test CPRI CPRI

7 Rated operating duty cycle O-0.35-CO-3min-CO O-0.35-CO-3min-CO

8 Opening time 35ms +/- 5ms 35ms +/- 5ms

Total break time in milli sec.


9 a) At 10% rated interrupting capacity 55ms +/- 5ms 55ms +/- 5ms
b) At rated interrupting capacity

Breaking current
a) Rated out of phase current
10 b) Rated cable charging current As per IEC 62271-100 As per IEC 62271-100
c) Rated kilometric fault level
d) Rated capacitor breaking current

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


11 Make time in ms. 35ms +/- 5ms 47ms +/- 5ms

Rated restriking voltage at 100% and 50% rated


Capacity
a) Amplitude factor
12 As per IEC 62271-100 As per IEC 62271-100
b) Phase factor
c) Natural frequency
d) R.R.R.V (Volts/Micro sec)

Dry 1 minute power frequency withstand test voltage

13 a) Between line terminal and Earth KV rms 28Kv 28Kv

b) Between terminals with breaker contacts


open 1.2/50 full wave impulse withstand test
75Kvp 170Kvp
voltage
c) Between line terminal and Earth KVp
Between terminals with breaker
14 75Kvp 170Kvp
contacts open KVp
Spacing between Bus bars
130 mm 310 mm
a) Live part to live part
15
b) Live part to Earth 90 mm 275 mm

16 Vacuum Interrupter Make Schneider Schneider

17 Contact separation Distance As per IEC 62271-100 As per IEC 62271-100


Copper Chromium Copper Chromium
18 Type of main contacts
Alloy Contact Alloy Contact

19 Contact pressure As per IEC 62271-100 As per IEC 62271-100

20 Contact Resistance As per IEC 62271-100 As per IEC 62271-100

Life of the Interrupter (In no of operations)

a) Tripping at Rated current 10,000 10,000


21
b) Tripping at maximum fault current
100 100
(Allowable maximum erosion 3mm)

c) Mechanical operations 30,000 30,000

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


Primary contact Primary contact
Details of main contacts making contact with the Jaw type - Copper Jaw type - Copper
22
Breaker truck with the panel Secondary contact Secondary contact
Plug & Socket - Copper Plug & Socket - Copper

23 Whether Trip free or not Trip Free Trip Free

24 Whether all the interlocks provided Yes Yes

Indoor - Indoor -
750x2325x2000 1100x2350x2600
25 Overall dimensions
Outdoor - Outdoor-
800x2375x2000 1200x2685x2800

Indoor 2mm CRCA sheet Indoor 2mm CRCA sheet


Gauge of the MS sheet used for the
26 Outdoor 2.5mm CRCA Outdoor 2.5mm CRCA
fabrication of the cubicle
sheet sheet

27 Total weight of one complete Panel 1 Ton Approx. 1.8 Ton Approx.

Whether Breaker Truck lifting / lowering mechanism Draw out type and Trolley Draw out type and
28 provided if the Breaker positioned in the panel at a will be provided to draw Trolley will be provided
height out to draw out

CONTROL & RELAY PANEL:

The Control & Relay Panel contains electronic components such as meters and protection relays.
Our manufacturing range is from 33KV to 400KV. HT Switchgear communicates with the CRP for
monitoring and protecting the Electrical equipment. Our panel is made of fine quality and fabricated
with good powder coating. The major components of CRP are

 Metering Instruments
 Protection Relays
 Mimic Diagram
 Alarm System
 Switches

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


LT PANELS:

LT Panel is an electrical distribution board that receives Power from generator or transformer and
distributes the same to various electronic devices and distribution boards. Such panels are used in
industries both for internal and external use and, therefore, they are quite rugged to withstand
different climatic conditions. Our LT panels are designed to be energy efficient which makes them
cost effective.

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


INHOUSE TESTING DETAILS:

S.NO EQUIPMENT MAKE RANGE/MODEL QTY

AC High Voltage transformer with (0-100)kV/


1 Automatic Electric Ltd 1
Control kit (100mA)

2 Primary Injection Kit Automatic Electric Ltd (0-3000)A 1

3 Secondary Injection Kit Anandajothi (0-100)A 1

5000V
4 Insulation Tester (Megger) CIE 1000V 3
500V

5 AC High Voltage test kit Anandajothi (0-3kV)/100mA 1

6 DC Power pack Anandajothi 0-240V DC/10A

7 Three Phase Variac Automatic Electric Ltd (0-440V) AC 1

8 CT Polarity Tester Anandajothi - 1

9 Digital clamp meter Kyoritsu 2002PA 2

10 Leakage tester LT Lutron (200mA-200A)/DL-6054 2

11 Multimeter Rishab - 4

Contact Resistance Measurement kit


12 Scope 100C 1
(CRM)

13 Breaker Timing test kit Scope - 1

14 Three phase relay test kit Omickron C356 1

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


PANELS GALLERY:

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....


WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....
KEY CUSTOMERS:

WHEN IT COMES TO “POWER”…..WE MAKE THE RIGHT “CONNECTIONS”.....

You might also like