POWER QUALITY
ANALYZER & METER
Models 8230 & 8220
@ ceo
Measures up to 660Vrms or Voc
Measures current up to 6500Axc or 1400A0¢
Measures inrush current
Energy metering (kAh, VARh, kWh)
Displays Min, Max and Average Volts and Amps,
Crest Factor, Peak value and K-Factor
Calculates and displays Watts, Wh, VARs and VA,
Power Factor and Displacement Power Factor
{or single-phase and balanced three-phase
> Individual Volt and Amp harmonics are
displayed in value and % to the 50”
> Stores up to eight screen captures (Model 8230)
> Displays temperature in both °F and °C
(Model 8220)
> Includes Dataview” software FREE for data
storage, real-time waveform display, analysis and
report generation
> Displays and records up to 17 different
power quality paramotere (Model 8220)
> Captures and displays in RUSH Waveforms
and statistics
> Displays and verifies phase rotation sequence
> Captures and displays rotational speed (RPM) ~
model 8220 only
GJ AEMc’
INSTRUMENTS,
(CHAUVIN ARNOUX GROUP =
vrvvy
YSingle-Phase
Power Quality Analyzer
PowerPad’ Jr. Model 8230
de 2250 c€o
The PowerPad’” Jr. Model 8230 is a single-phase
power quality analyzer that is easy-to-use, compact and
shook-resistant. It is intended for technicians and engineers
to measure and carry out diagnostic work and power quality,
work on single-phase systems and three-phase balanced
load networks, Users are able to obtain instant waveforms of
an electrical network's characteristics, and also monitor their
variation over a petiod of time.
‘The multitasking measurement system simultaneously
handles all the measurement functions and waveform
display of the various parameters, detection, continuous
recordings and their display without any constraints.
» Verification of power distribution circuits
> Measures and records power systems (kW, VA, KVAR)
> Energy metering (kAh, VARh, kWh)
> Determine harmonic content and its origins
> Motor analysis,
> Measures up to 660Vims or Voc
> Measures up to 6500Aac or 1400A00
(probe dependent)
> Displays Min, Max and Average Volts
and Amps, Crest Factor, Peak value
and K-Factor
» Calculates and displays Watts, VARS,
kWh, and VA, Power Factor and
Displacement Power Factor for single-
phase and balanced three-phase
» Displays total harmonic distortion (THD-F
and THD-R) for voltage and current
> Individual Volt and Amp harmonics are
displayed in value and % to the 50”
> Captures, displays and stores inrush
current waveforms and statistics
Displays and records up to 17 different
power quality parameters
Determines phase rotation
Stores up to eight screen captures
Stores up to 1MB of trend recorded data
Captures up to 4096 alarm events using
up to 10 different thresholds
Configurable from DataView* software or
front pane!
> Download stored data to DataView*
software via optical with isolated USB port
>» Includes FREE DataView? software for
data storage, real-time waveform display,
analysis and report generation
yryvyv oy
Y
Oe
Al models include current probe wit 10 ft lead
(M89 example shown), black and red 10 ft wage
leads and aligatorclps, optical USB cable, NIMH etter,
120V US wall chargor, DalaViow sofware,
‘camying bag and user manual
2 wiwaemocom
Mc”
Tara iomma moses Ra AEMEmaeme
INSTRUMENTS Technical Assistance (800) 343-1397
Recording Setup
GERLECTRCAL HORI)
<¢Single-Prase
‘4 tocontim your choice)
Easily select and configure all system
set up functions.
Quickly select which parameters are to
be recorded.
Waveform Mode
Displays inrush current waveforms and
statistics all on one screen.
Displays voltage and current waveforms
and statistics, minimax data, power and
phase rotation.
Harmonies Mode
VnO1 1000: 2281v soe"
ene TH 18x 4
Displays real-time trend recording.
Displays harmonic content to the 50° for
volts, amp and power including direction.
‘wawaemecom 3PowerPad’ Jr. Model 8230
> One button direct access to all
major functions with immediate
display of realtime data
> Simple to use navigation and
selection buttons
> Clean, easy-to-read color display
VGA Color LoD.
Recording button Alarm button
ON/OFF button ‘Setup button
‘Waveform button ‘Snapshot button
PowerfEnergy button Harmonics button
Infrared optical
Isolated interface
{or USB cable
‘Navigation
buttons
Charging light
ere
MODEL 8230
Power supply
Input
Mc”
nara Tara iomma moses Ra AEMEMODEL 8230
Voltage (TRMS) MN-2 Probes: Phase-t-Phase: 660
240 Phase-to-Neutral: 600
61204,
(Current (TRMS) [MN Probe: 5mA to 6A/T20A or 2 to 240 ‘SR Probe: 3 to 12008
[MR Probe: 10 to 1000Asc, 10 to 1400Ao¢ /AmpFlex*: 10 to 65008”
Frequency (Hz) 40 to 70H
Other Measurements
KW, KVAR, PF, OP, Ki, KVARH, KU, K-Facto,
‘licker, Harmonic Phase Shi Phase Rotation n RUSH
Harmonies THO-R,THO-F, V8, VA
1*to 0"; Direction, Sequence
nfush Displays and records duration, 1/2 cycle max, peak and displays waveforms
| Sampling Frequency 256 samples/oycle
Data Storage 1.5MB partitioned for waveforms,
alarms and trend recording
‘arms ‘Stores up to 2096 events showing time, duration and value
Power Source NiMH rechargeable battery pack
[AC Supply: 120/230Vac (50/60H2)
Battery Life > Eight hrs with display on
TEATS
2 40 hrs with display off (recording mode)
Communication Port Optically slated USB
Display 11 VGA 20x 240) olor LOD
Dimensions 8.3 x 4.3 x 2.4" (211 x 108 x 60mm)
| woignt 1.9 hs (08849)
Saety Rating EN 61010, 600V CAT, Poltion Deore 2
DISPLAY
Disnay Type oor LoD
ENVIRONMENTAL
Operating Temperature 32°10 122 ("to 0)
Storage Temperature (<30 days) -4° to 122°F (-20° to 50°C) with batteries
pn
Safety Rating EN 61010-31: 2002, EN 61010-1: 2001, EN 61010-2: 1995, 600V CAT Ill, Pollution Degree 2
Double nsuation Yes
Ce Mark ves
‘rest factor at 6500 = 1
Choose from a variety of current probe options:
ceo ceo
|SR193 (12004) current probe
AmpFlex° 199 (65004) flexbie current probe
ceo
[M93 (2404) current probe or
M193 (64/1204) curent probe
wawaemecom 5Power Quality Meter
Model 8220 > Measures up to 660Vims or Voo
> Measures up to 6500Asc or 1400Anc
(probe dependent)
> Displays Min, Max and Average Volts
land Amps, Crest Factor, and Peak value
> Calculates and displays Watts, Wh, VARS
land VA, Power Factor and Displacement
Power Factor for single-phase and
balanced three-phase
> Displays total harmonic distortion (THD-F
‘and THD-R) for voltage and current
> Displays individual harmonic values and
% for Volts and Amps to the 50° harmonic
> Captures and displays inrush current
Calculates and displays phase rotation
and RPM
Y
» Displays temperature in either °F or °C
> Displays restance up to 20000
> Conducts continuity and diode tests
> Stores up to nine complete sets of
Tecan ral Vt arp, power
eed ceo harmonics end oor messremets
> Conigurai rom Daa st
The Model 8220s single-phase AC + DC power meter wih Contra tom DataViw” sofware or
an electroluminescent backlit digital display and is rated to GOOV bar
CAT Ill, It is a measurement tool for electrical parameters and > Download stored data to DataView”
Gitibuion nomork dtubances, enasng ie usoro obi stant” sofware via opal coupled USB port
mmeasuromonts ef tho main charecosicool a srejerphasenelverk—_y. Opeeaer at rates nb adantn
(voltage. current. power. voltage and current harmonics. etc.) and
to monitor machinery in operation (temperature, inrush current and (optional)
duration of operation, resistance of windings and rotational speed) > Includes FREE DataView’ software for
Compact and shock resistant, its ergonomic design and data storage, real-ime waveform display
straightforward interface make it user friendly and intuitive, Within analysis and report generation
seconds you will be gathering the measurements you want.
‘The Mode! 8220's accuracy is better than 1% (excluding current
sensors). It has a great flexibility due to AEMC"s range of current
sensors, measuring from a few hundred miliamps to several
thousand amps,
‘The Model 8220 is designed for technicians, control and
maintenance engineers, as well as, electrical contractors and
educators.
> Monitor all power quantity variables (V, A, W, VAR, VA)
> Monitor motor performance (inrush, RPM, temperature)
> Energy metering (kAh, VARI, kWh)
> Troubleshoot connections with resistance/continuity Al models include curent probe with 10 ft iead (MNS example
measurements Shown), black and red 10 ft voltage leads and aligator cps,
‘optical USB cable, sk 1.5V batteries, two safety test probes,
> Determine proper system wiring with phase rotation function DataView” sofware, carying bag and user manta
> And much more ‘An optional AC Power adapter is available,
Mc”
eee rrr ores BG AEMEaeme
[sreuwents Technical Assistance (800) 343-191
Voltage
= 2B ty
~ 968 .
4AS9*
401/04 J
Displays volts, amps and frequency on
‘one screen.
—
- 483.
- 2088 .
1367 *
Displays inrush current and duration
including max and peak values.
Power
rig
12.26 war
C {BS wm
<0 1/02>
Displays all power measurements on
one screen.
~ Q!
~ ecb ty
sel te fis
40 1/5o>
Displays THD, % and value for each
harmonic to the 50° with one screen for
each harmonic.
RPM Temperature
=z
Ye
24 {5 RPM
Sie
Display of rotational speed. Displays temperature in both °F and °C.
°
wiwaemecom 7Model 8220
> Rotary selection of variables to be
measured with easy-to-read icons
> Large easy-to-read mult-ine
electroluminescent display
> Direct access buttons for saving,
printing, viewing and discarding data
Electroluminescent
backlit digital display
Print button Left arrow button
(select previous screen)
Snapshot button Right arrow button
(Golect next screen)
View button 7 Yetow faction
Delete button White funetion
‘elect button
Infrared optical
Wolated neracs
for USB cae
Rotary selection,
switch
ON/OFF indiestor
Berra)
Current probe
Input
Power supply
input
@ wnwaemocom
Mc”
Tara iomma moses Ra AEMEMODEL 8220
Voltage (RMS) WWN-2 Probes: Phase-to-Phase 60
240 Phase-o-Neuta: 600
ewizon
Current (RMS) [MH Probe: SmA To GA/1208 or 2 to 240 ‘Probe: 30 12008
[MR Probe: 10 to 10008, 10 to 140006 Ampex: 10 to 65008
Frequency (2) 4010 702
‘ther Measurements Kv KVAR, PDP. VA, Phase Rotation Temperature,
RPM, sistance, Conny, Diode Test
armonies 11050"
Sampling Frequency 256 samples /oycle
tres Displays ma, pak and dation
PM 610 120,000 RPM
Temperature 326° to 1532°F (200° to 850
Data Storage Store nine oes of readings for vols, amps,
ower and harmonics
Power Source Sik 1.5V AA Alkaline batteries
‘Ae Supply: 120230Vac (50/602) — optional
Bator Life > Eight hrs with cisplay on
Communication Port Optical isolated USB
Display Three-tine backit digital display with custom icons
Dimensions 8349424" 211 x 108 60mm)
Weight 191s (0.8)
Safety Rating EN 61010, 00V CAT I, P54, Pollution Degree 2
|e SC |
Dieplay Type octrolimineecont back gal deplay
Operating Temperature 32°12 OH)
Storage Temperature {80 days) 4°10 122°F 20" to 50°C wit bares
50° 108°F (10° to 40°) wit rare alisies
Safety Rating EN 61010-32002, EN 61010-1: 2001, EN 61010-2: 1985, 600V CAT Il, Pollution Degree 2
Double insulation 3] Yes
CE Mark Yes
"Crest factor at 6500 = 1
Choose from a variety of current probe options:
ce
'SR193 (12004) curent probe
ceo ceo
Ampex 193 (65004) lexbie current probe ‘N83 (2404) curent probe or
MN193 (64/1204) curent probe
F
QAM aaa
‘wawaemecom 9DataView"
Data Analysis and Reporting Software for Power Quality Meters
Configure all functions of the
PowerPad"
* Display and analyze real-time
data on your PC.
+ Configure all PowerPau f
parameters from your PC
+ Customize views, templates and
reports to your exact needs
= Create and store a complete library of
configurations that can be uploaded to
the PowerPad® as needed
+ Zoom in and out and pan through
sections of the graph to analyze the
data
* Download, display and analyze
recorded data
* Display wavetorms, trend graphs,
harmonic spectrums,
text summaries, transients,
event logs and
stored alarms
reports using standard
Or custom templates you
design
+ Free updates are available
on our website
www.aeme.com
welions and
Minimum System Requirements
> Windows 2000/XP/Vista® operating system
> 128MB of RAM for Windows 2000
(256MB recommended)
256MB of RAM for Windows XP_
512MB of RAM for Windows Vista®
> 80MB of hard disk space
(200MB recommended)
» CD-ROM drive
Windows a registered vademark of Mcrosot
Corporation inthe United States andr other
counties.
70 wawaemecom
Clear and easy setup of all functions from one tabbed
dialog box.
DataView® software provides a convenient way to
configure and control power quality from your computer.
Through the use of clear and easy-to-use tabbed dialog
boxes, all PowerPad® functions can be configured and
tests can be initiated. Results can he displayed in real
time and stored in your PC. Reports may be printed
along with the operator's comments and analysis.
GAeMe’
“Technical Assistance (800) 943-139DataView" Sample Reports
Sn | rane Diy A Cains Ras ra | ENEDED|
= _eeFenmey
Yim amones
et
at Oe
2A rosa Pete
te
ows) 1 fF
a ne
ra eel ercacace > Semasevcaeeg
nao ane och)
, a
Setup ofall functions on the Model 6230 | Sw jo vs —
‘s easily aocomplished using DataView® Fam ane SES eS
software. Bw vn eva a
Bor tea fee Shem =
—————$—<—————— drone Peinsfts =]
fins] te (5) 7 Names Orb | fac xO
[im SIP ve ( ostameesOoy | factory
Se A
# cece | AAA
| Menon es 305
BeFeadton wisnet
Reports can be displayed on your PC and printed. Each report includes
all test results in a tabular and graphic format, as well as operator and test
site information. Comments typed by the operator will also be included.
F
AEM Seem rrr