You are on page 1of 4

Structural T

his article presents an overview of the • For use in load combination 7:


design requirements for shallow reinforced E = Eh - Ev = ρQE - 0.2SDS D
concrete foundations (spread footings and In these equations, ρ is the redundancy factor

Design
mat foundations) supporting buildings assigned to determined in accordance with ASCE/SEI 12.3.4,
Seismic Design Category (SDC) D, E, or F. Also SDS is the design spectral response acceleration at
included is a proposed design method that goes short periods, and QE are the effects due to the
beyond requirements in current codes and stan- horizontal seismic forces.
dards. Although the following discussion focuses The combined factored stresses at the base of the
design issues for
exclusively on spread footings supporting mem- footing must be less than or equal to the design
structural engineers bers of the seismic-force-resisting system (SFRS), soil bearing strength, ϕQns. The resistance factor, ϕ,
it is also applicable to mat foundations. is given in ASCE/SEI Table 12.13-1 and is equal
According to ASCE/SEI 7-16, Minimum Design to 0.45 for bearing strength. ASCE/SEI 12.13.5.2
Loads and Associated Criteria for Buildings and permits ϕ to be taken as 0.80 where the nominal
Other Structures, Section 12.18.9.2, buildings are bearing strength has been determined by in-situ
permitted to be supported on shallow foundations testing of prototype foundations when the test-
provided the foundations are designed and detailed ing program has been ® approved by the authority

E
in accordance with ASCE/SEI 12.13.9.2.1 and the having jurisdiction.
conditions of ASCE/SEI 12.13.9.2 are met. The nominal soil bearing strength, Qns, is per-

R
mitted to be determined by the following
methods:
Shallow Reinforced ConcreteCopFoundations
U
ht •
Presumptive load-bearing values
yrig

T
(organic silts, organic clays, peat, or
non-engineered fill are assumed not to

C
have a presumptive load capacity).
Design for SDC D, E,
e
U
• Geotechnical site investigations by a registered
Determining Base Area
and F Buildings
i n design professional, which include field and

R
Bearing failure is the primary design consideration laboratory testing.
z
T
when footings are subjected to seismic forces. • In-situ testing of prototype foundations.
By David A. Fanella, Ph.D., S.E.,
a
It is common practice to use service load com-
g
S
P.E., F.ACI, F.ASCE, and
binations to size the footing with an allowable
Michael Mota, Ph.D., P.E.,
a
bearing capacity that is equal to the static bearing
SECB, F.ASCE, F.ACI, F.SEI
m
capacity multiplied by a factor to account for the
transient nature of the earthquake forces. The
2018 International Building Code (IBC), Section
1806.1, permits the presumptive vertical and lat-
eral bearing pressures values in Table 1806.2 to be
increased by one-third where the alternative basic
load combinations of IBC 1605.3.2 that include
earthquake forces are used. It is also permitted
David A. Fanella is Senior in such cases to use allowable bearing capacities
Director of Engineering at the that have been determined from a geotechnical
Concrete Reinforcing Steel investigation.
Institute and can be reached ASCE/SEI 12.13 contains requirements for
at dfanella@crsi.org. the design of foundations, including spread
footings. In lieu of performing a linear analysis
Michael Mota is Vice President
that includes foundation flexibility and the load-
of Engineering at the Concrete
deformation characteristics of the foundation soil
Reinforcing Steel Institute and can
system (ASCE/SEI 12.13.3), the base dimensions
be reached at mmota@crsi.org.
of a footing can be determined utilizing either
a strength design method (ASCE/SEI 12.13.5)
or an allowable stress design method (ASCE/
SEI 12.13.6).
Strength Design Method
In the strength design method, load combinations
1 through 7 in ASCE/SEI 2.3.1 and 2.3.6 are
used with the seismic load effects, E, determined
in accordance with ASCE/SEI 12.4.2:
• For use in load combination 6: Figure 1. Soil pressure distributions beneath a footing
E=Eh + Ev = ρQE + 0.2SDS D subjected to axial force and bending moment.

38 March 2018
with ASCE/SEI 12.13.4 for foundations of strength, ϕQns. The area of the footing is
buildings where (1) the structure is designed in determined based on the governing load com-
accordance with the Equivalent Lateral Force bination and the appropriate equation for
Procedure (ELFP) in ASCE/SEI 12.8 and (2) maximum factored bearing stress.
the structure is not an inverted pendulum
Allowable Stress Method
or cantilevered column type structure. Only
the seismic load effects may be reduced by In the allowable stress design method, load
25% when calculating the bearing pressures; combinations 1 through 10 in ASCE/SEI
all other load effects must not be reduced. 2.4.1 and 2.4.5 are used with the seismic
A 10% decrease of the overturning effects is load effects, E, calculated in accordance with
permitted when a modal analysis in accordance ASCE/SEI 12.4.2 to determine the maximum
with ASCE/SEI 12.9 is performed. bearing stresses at the base of a footing, which
Analysis of bearing stresses using the strength must be less than or equal to the allowable
design method depends on whether inelastic bearing capacity. As in the case of the strength
soil response is acceptable or not. If elastic design method, reduction of foundation over-
response is required, the maximum factored turning effects is®permitted in accordance with
bearing stress is calculated using the appropri- ASCE/SEI 12.13.4.

E
ate elastic equations in Figure 1 where factored
Proposed Design Method

R
axial forces, Pu, and bending moments, Mu,
are determined by load combinations 1 The earthquake effects, E, determined in

U
through 7 in ASCE/SEI 2.3.1 and 2.3.6. accordance with ASCE/SEI Chapter 12 are
ht
Where inelastic yrig soil response is accept- less than those that would be expected during

T
Cop
able, the maximum bearing stress, which is a design-level earthquake. Therefore, in the

C
assumed to be constant over the entire contact case of footings, the reactions caused by E that
area, can be calculated assuming full plasticity are transferred from the supported member
e
Figure 2. Soil pressure distribution beneath a

U
of the soil (Figure 2). to the footing will typically be smaller than
footing assuming full inelastic soil response.
qu,max = Pu /BL´
i n those that would be transferred during an

R z
According to ASCE/SEI 12.13.5, overturn- Regardless of elastic or inelastic soil response, actual seismic event. Thus, determining the

T a
ing effects at the soil-foundation interface are the maximum bearing stress, qu,max, must be bearing stresses (and the required flexural and

g
S
permitted to be reduced by 25% in accordance less than or equal to the design soil bearing shear strengths) based on code-prescribed

a
m
ADVERTISEMENT–For Advertiser Information, visit www.STRUCTUREmag.org

STRUCTURE magazine 39 March 2018


earthquake forces inherently implies that report, times the density of the soil. IBC
Design Procedure
some inelastic behavior is allowed in the foot- Table 1806.2 provides presumptive passive
ing regardless if strength-level or service-level The following design procedure can be used pressure values in pounds-per-square-foot-
load combinations are used. Allowing such to size the base area of a footing supporting per-foot-below-grade for various soil types.
inelastic behavior may be tolerable for typical members that are part of the SFRS in build- The lateral resistance provided by friction is
buildings assigned to nonessential risk cat- ings assigned to SDC D, E, or F: equal to the total normal force at the base of
egories (ASCE/SEI Table 1.5-1). However, 1) Determine the factored load effects using the footing times an ultimate coefficient of
foundations that are designed in this way may load combinations 1 through 7 in ASCE/ friction. When determining the total normal
possibly be damaged during a seismic event, SEI 2.3.1 and 2.3.6, where load combina- force, load combination 7 should be used
and may not perform as intended during tions 6 and 7 include seismic load effect because this results in the smallest normal
subsequent seismic events. Furthermore, with overstrength. force at the base. Ultimate coefficients of fric-
inspecting foundations after an earthquake 2) Where elastic soil response is required, tion depend on the soil type and are generally
can be very expensive or might not even be determine the base area of the footing, reported in a geotechnical report.
possible, so there is usually no direct way of Af, using the appropriate elastic equations ASCE/SEI 12.13.5.1.1 permits the total
ascertaining if damage has occurred unless in Figure 1 and the design soil bearing design lateral strength, ϕQns, to be the sum of
the damage is obvious. Repairing founda- strength, ϕQns. the values determined
® for passive pressure and

E
tions is also costly and, in some cases, may 3) Where inelastic soil response is permitted, horizontal sliding (from friction, cohesion, or
not be feasible. determine the base area of the footing, some combination thereof ). The geotechnical

R
For buildings assigned to SDC D, E, and F, it Af, using the uniform bearing pressure report should specifically designate what type
is recommended to design footings using load distribution illustrated in Figure 2 and or types of horizontal sliding resistance are

U
combinations 1 through 7 in ASCE/SEI 2.3.1 the design soil bearing
righ
t strength, ϕQns. applicable at a site.

T
y
and 2.3.6, where load combinations 6 and 7 Cop
Allowable Stress Design Method
include seismic load effect with overstrength:

C
• Load combination 6: 1.2D + Ev +
Resistance to Lateral Loads In the allowable stress design method, allow-

e
U
Emh + L + 0.2S = (1.2 + 0.2SDS)D + In general, lateral forces from earthquakes are able passive bearing pressures and coefficients
ΩoQE + L + 0.2S transferred from a footing to the adjoining
i n of friction are used in conjunction with

R
•L  oad combination 7: 0.9D - Ev + Emh soil through friction at the base of the footing maximum seismic load effects calculated by
z
T
= (0.9 - 0.2SDS ) + ΩoQE and passive bearing pressure along the edge of allowable stress load combinations to deter-
In these equations, Ωo is the overstrength a
the footing perpendicular to the direction of
g
mine whether resistance to lateral sliding is

S
factor given in ASCE/SEI Table 12.2-1 for analysis (Figure 3). As in the case of bearing adequate or not. As in the case of bearing
the SFRS. a
pressure at the base of a footing, both strength pressure at the base of a footing, allowable pas-
Like the design of collectors in accordance
with current provisions, footings are antici- m
design and allowable stress design methods
can be used to check if resistance to sliding
sive pressures may be increased when seismic
load combinations are considered to account
pated to respond primarily in the elastic range is adequate or not. for transient load effects.
when designed using this approach, thereby
Strength Design Method Design and Detailing Requirements
reducing the likelihood of damage when sub-
jected to a design-level seismic event. Nonlinear In the strength design method, factored The applicable design and detailing require-
response is limited to the supported mem- lateral forces must be less than or equal to ments given in ACI Chapter 13 and ACI
bers, which are correctly detailed according the design lateral strength, ϕQns. The reduc- 18.13.2 must be satisfied for footings sup-
to the appropriate requirements in ACI 318- tion factor, ϕ, is given in ASCE/SEI Table porting members of the SFRS in buildings
14, Building Code Requirements for Structural 12.13-1, and is equal to 0.50 for lateral assigned to SDC D through F. Similar to the
Concrete, Chapter 18. As an upper limit, the resistance provided by passive bearing pres- cases of determining the base area of a foot-
forces delivered to a footing need not exceed sure and 0.85 for lateral resistance provided ing and checking for sliding resistance, it is
the capacity of the supported structure. by sliding (either friction or cohesion). recommended that reinforcement for flexure
ACI 12.13.5.1.1 contains and force transfer at the interface are deter-
the types of soils that pro- mined using load combinations 1 through
vide lateral sliding resistance 7 in ASCE/SEI 2.3.1 and 2.3.6, where load
from friction and cohesion. combinations 6 and 7 include seismic load
Values of Qns, based on the effect with overstrength. Shear strength
soil profile at the site, are requirements should be satisfied based on
typically provided in the those load combinations as well.
geotechnical report. Additional in-depth information and
Passive bearing pressure worked-out design examples can be found
varies linearly with respect in the CRSI publication Design and Detailing
to the depth below grade. At of Low-Rise Reinforced Concrete Buildings.▪
a depth ds below grade, the
passive pressure is equal to ds
times the passive pressure coef- The online version of this article
ficient, Kp, which is typically contains references. Please visit
Figure 3. Lateral load transfer by friction and passive bearing stress. provided in a geotechnical www.STRUCTUREmag.org.

STRUCTURE magazine 40 March 2018


References
ACI (American Concrete Institute). 2014. Building Code Requirements for Structural
Concrete and Commentary. ACI 318-14, Farmington Hills, Michigan.
ASCE (American Society of Civil Engineers). 2017. Minimum Design Loads and Associated
Criteria for Buildings and Other Structures. ASCE/SEI 7-16, Reston, VA.
CRSI (Concrete Reinforcing Steel Institute). 2017. Design and Detailing of Low-Rise
Reinforced Concrete Buildings. Schaumburg, IL.
ICC (International Code Council). 2017. International Building Code. Washington, D.C.

R E
U
t
righ

T
y
Cop

U C i n e

S T R m
a g a z

STRUCTURE magazine 41 March 2018

You might also like