Professional Documents
Culture Documents
DIR-67
AUTOMATIC PROGRAM FOR THE TEST OF
DIRECTIONAL RELAYS ANSI-IEC 67
USER MANUAL
Ver. 6.5.3
Doc. MSE20030 Rev. 6.5.3 Page 2/33
5.2.0 6, 29-30 17/11/2008 Added “Save in TDMS” menu item and the link Rossoni
with the same print report as TDMS
5.2.1 All 16/02/2009 Updated images. Described nominal Morandi
characteristic settings and Verify Vo-Io
characteristic test type
6.5.3 ALL 9/1/2015 Updated to the new revision Lodi
Doc. MSE20030 Rev. 6.5.3 Page 3/33
PREFACE .......................................................................................................................................................... 4
2 PRINTING RESULTS............................................................................................................................... 29
Preface
The program DIR-67 has been designed as an interactive test software for all ISA Automatic test
sets, to test directional relays ANSI-IEC 67.
Theoretically, from the beginning the user is driven throughout all steps in simple way, so that he
has the feeling that everything is under control.
It is like playing with a fully manual test equipment with very powerful tools. The following are the
features available in the program:
Capability to load/save the results created as a Microsoft Access file (*MDB;*.67)
Manual and automatic test of any type of directional relays
Capability to load a result and repeat all the tests included
The Revision 6.5.3 has, as an additional feature, the capability of importing the nominal over-
current curve.
Doc. MSE20030 Rev. 6.5.3 Page 5/33
1.1.1.1 Open
This menu item allows loading a result file that contains all the tests performed and the relative
relay settings (graphics included). Results are stored into a database file (Microsoft Access file).
1.1.1.6 Exit
Closes the application.
1.1.2.1 Header
By choosing this menu item, the user is asked to fill data that identifies the conditions of the test.
They will be printed on the results, allowing the traceability of the test performed. In detail, please
insert the Substation name (Plant name), the Line name (Feeder), data regarding the relay such as
Relay Manufacturer, Relay Model and Serial Number. Also fill the Operator and Instrument
Serial Number fields. The other fields are to be considered optional.
Doc. MSE20030 Rev. 6.5.3 Page 8/33
Click on Load logo to change the logo to be printed on the test report, or if the program is not able
to find the predefined logo. Reasons could be that the file no longer exists or the .INI file is
corrupted.
1.1.2.2 Preferences
This menu item loads a window where the operator can specify general parameters that will
influence the way test are carried out or results are displayed
Doc. MSE20030 Rev. 6.5.3 Page 9/33
The frame CT Ratio allows using appropriately a CT on the current outputs (specifically designed
for the option IN1-CDG). It allows therefore to select which is the CT ratio by selecting the primary
side and secondary side currents, and to define on which outputs it will be used. The selection can
be made by choosing the appropriate Primary/Secondary side values from the menus or by typing
directly the ratio in the provided box. CT ratio can be selectively applied to the current outputs.
The frame Time delay allows the user to define how to display trip times and delays: in seconds or
in cycles. In the latter case it must be indicated the reference frequency to be used for the cycle
calculation.
The frame Zero Power allows defining specific working parameters of this instrument and will be
enabled only if the instrument is connected.
The frame Output Colors allows to choose the color appearance of the voltage and current outputs
in: the Manual mode screens, both Pre-fault and Fault values.
The frame Measure Conversion constants allows to choose whether to take into account the value
and type of a conversion parameter. This will be reflected on the values shown by the Measuring
board, and is particularly useful when measuring signals via a transducer, such as clip-on
transformers. In this case the transducer can convert from Current to Current (and therefore the ratio
I/I Conversion is taken into account) or from Current to Voltage (and therefore the ratio I/V
Conversion is considered).
The frame Power Line Synchronization is disabled: if enabled, the generation will be
synchronized to the mains.
The frame GPS & IRIG Injection Delay applies when these options are available (models DRTS6
or DRTSXX). It is possible to delay the test generation with respect to the synchronization pulse:
this serves to synchronize different devices.
By pressing OK the parameters will be saved, whether with Cancel any change is discarded.
A picture of the connected instrument appears. It also shows ISA contact details.
1.1.4 Languages
This menu gives the capability to change the language of the software without closing the program.
The active language will be saved by quitting the program.
Doc. MSE20030 Rev. 6.5.3 Page 11/33
Ramp Vdc: if the auxiliary DC voltage is applied with a step, an overload may occur on
the Vdc amplifier. This is normally caused by a high filter capacitor put in parallel of the power
supply. In this case it is recommended to generate the Vdc with a ramp otherwise the capacitor
is sensed as a short circuit, at least during the first few milliseconds.
o Vo = (V1+V2+V3)/3: select this if the relay needs the complete three phase voltages to
determine the zero sequence voltage Vo (or Vr): the three voltages
V1, V2, V3 will be used during the test.
o Vo = V1 (Open delta): select this if the relay needs only one voltage coming from open-delta
connected VT’s
only V1 will be used during the test
Then, it is possible to define the directional characteristic or the overcurrent characteristic: two tabs
are available.
Doc. MSE20030 Rev. 6.5.3 Page 13/33
Time settings
o Err Max Maximum allowed time error to consider a test Pass. The maximum
error is calculated as the maximum between the relative error given in
% and the minimum error
o Characteristic Angle this is the MTA, and represent the angle of maximum sensitivity
o Err Max [°] Maximum allowed angle error to consider a test Pass.
o Sector extension: represent the extension of the directional sensitivity
Vo-Io Characteristic
This is not enough: Vo and Io must be higher than their relative pick-up’s.
With this selection, it is possible to define the overcurrent relay characteristic curve.
The relay characteristic is made of a number of parts, superimposing on each other, and each
one corresponding to a threshold. Each line of the above table represents the characteristic of the
corresponding element. There is no limitation on the number and type of thresholds.
The element is defined with:
o Type (definite time, normal inverse, very inverse, standard…)
o Pick up, this given in units of In.
When the relay is sensing the fault current, it will check all the phases for which the measured
current is more than the pick-up current. As a result, for a specific test current, the tripping time is
the one of the fastest tripping phase. This is why the test of three phase relays must be done with
three single-phase tests: else, one or two faulty phase measurements would not be detected.
The table displays a default characteristic. The curve programming is performed as follows:
Go to the first element, and correct, if necessary, the threshold setting, by double clicking on
it;
Press the Curve description: a down arrow is displayed. Click on the arrow: you access a
very long list of pre-defined shapes, according to many different Standards.
Double click TD or T(10I>), according to the relay setting, and program it.
Once you have finished, the first element of the curve is drawn on the diagram.
Now you can move to next element(s), until the characteristic is programmed.
If you prefer, instead of modifying parameters you can delete one line.
If some element is missing, press add and then program it.
“Clear all” removes all the programming, and makes you to start from scratch.
At the end, the complete characteristic is displayed.
In this page there are also the settings related to the input contact to monitor or the auxiliary contact
to be enabled and if so with the delay relative to the test start.
By clicking on the square box in the Timer and Input contact frame, it is possible to define the
hardware status of the contacts. This section applies to DRTS ,DRTS3, DRTS6 and ART100. The
following window appears:
Debounce.
The debounce is the time during which the instrument waits for the input to become stable: this
serves to avoid stopping the test because of noise, and also to ignore contact bounces. When a
transition is sensed the debounce counter starts: any opposite transition before the debounce expires
resets the counter. Only if the input does not change for the programmed duration the input is
accepted, and the timer stopped. Default value: 500 us. With electronic inputs the value can be
programmed to 0; with heavy contacts the debounce is better programmed to 2000 us (maximum).
The time measurement is not affected by this selection.
Type
There are three selections about the type of contact: Dry; Polarized by a d.c. voltage; Polarized by
an a.c. voltage. With selection dry, next selection is not applicable. With selection a.c. voltage, the
debounce is forced to 2000 us to overcome the zero crossings of the input.
Threshold
Doc. MSE20030 Rev. 6.5.3 Page 17/33
When the contact is selected Polarized, it is also possible to select the threshold voltage: all inputs
less than 80% of the selected value are made equal to zero. This serves to avoid noise on the line, or
in case there is a protective resistor in parallel to the contact driving the coil, so that the Open
contact does not correspond to zero volts. Available thresholds: 5 V (logic input); 24 V; 48 V; 100
V. This selection should match the wetting voltage.
If dry input is selected and a voltage is applied the instrument does not suffer, provided that the
input is no more than 220 V. If a voltage is selected and the input is not polarized, the trip is not
sensed.
If a wrong voltage threshold is selected:
. Threshold higher than the voltage: the trip is not sensed;
. Threshold lower than the voltage: the contact could be found closed when it is open.
Test Tab
Doc. MSE20030 Rev. 6.5.3 Page 18/33
Select an angle
Set the extensions of the graph by clicking on the arrows beside the graph. We suggest that you
set:
o Vmax = 100 V
o Vmin = 0,1 V
o Imax = 1 A
o Imin = 0,01 A
Move with the mouse over the graph and then click down when you have reached the desired
point
Select the Test tab to see the relative values for voltage and current the measured trip time.
Please note:
o Fixed parameter: Angle Vo-Io
o Variable parameter: Vo and Io
o In our representation we generate the Vo by moving the star-point along V1. The distance 00’
between the two star points (0 before and 0’ after the fault)is equal to Vo .
Please note:
o Fixed parameter: Vo and Io
o Variable parameter: phIo = Angle Vo-Io
The test verifies the directionality and the blinders with an automatic test. After confirming the
selection by pressing the OK button, the following lines are added to the Test Table:
o if the direction test is successful the test will carry on with the following:
Verification of Blinder 1 and 2 with a binary search
Doc. MSE20030 Rev. 6.5.3 Page 21/33
It is possible to verify the Io or the Vo limit of the characteristic by selecting the relative option.
If Verify Io is selected then it is necessary to set the Voltage at which the test will be
performed. The result is a Test Pass or Fail. By changing the voltage it is possible to explore
all the Io side of the characteristic
If Verify Vo is selected then it is necessary to set the Current at which the test will be
performed. The result is a Test Pass or Fail. By changing the Current it is possible to explore
all the Vo side of the characteristic
A test will be a pass or a fail depending on the Nominal characteristic set and the Max error allowed
in the Settings page of the program.
To give an example, with the values displayed above, the program will search the Io threshold for
Vo = 100 –80 – 60 – … – 20 – 10 – 8 – 6 – … – 2
Doc. MSE20030 Rev. 6.5.3 Page 22/33
The red net in the graph is to show you the voltage and current values where the search will be
performed.
Press the OK button to insert the test points to the Test Table. Then press the button to
start the test.
To explain the way the test is performed, we suppose that we have selected both searches for
voltage and current according to the figure above:
Note
It may happen that a Io search at fixed voltage Vo fails. For instance, if we have selected that we
want all Io values for Vo up to 0.1 V, and the pick-up voltage is only 1V, all tests between 1 V and
0.1 V would fail because the relay never trips. In this case, in order to save time, you’ll be notified
Doc. MSE20030 Rev. 6.5.3 Page 23/33
that the test failed for that specific voltage value, and all the remaining test at lower voltage will be
skipped.
Same for the Vo search at fixed current Io.
Look at this figure. Here we are displaying a test result together with the test selections: it is evident
that nearly all searches of Io below 10V cannot lead to a result because the relay never trips
1.4.5 Dragging
This is not a real test. It is used to generate voltage and current Vo, Io in real time at mouse
position. You can click and drag in the following graphs:
With this test, you can automatically verify the overcurrent relay characteristic. You have to enter
the start test current, the stop test current and the step current; that is, the first test current, the last
test current and the current increment between two tests. The values can be entered either in pu, or
in A. The program computes and displays the number of tests it will perform.
In order to help you set these values, the program displays the dots corresponding to the test points.
Once you press OK, a set of lines are added to the test table.
The test execution is simple: for each point, the program generates the fault current and measures
the corresponding trip time. The result table displays:
The measured trip time;
The nominal trip time, and the corresponding tolerance;
The time error, in ms;
The Pass/fail judgement. The result is Pass if the time error is less than the tolerance.
Here you can decide whether to save, print or delete all the results. You can also open previously
executed test results.
By clicking on the result table it is also possible to select multiple rows and delete them by
choosing the menu item that appears after the click.
Doc. MSE20030 Rev. 6.5.3 Page 26/33
1.6 Actions
Different actions are possible when you test a relay.
For instance you may change the colors of the graph: background, nominal characteristic, tested and
not tested points.
You can repeat a test that you feel wasn’t performed correctly because the relay wasn’t energized.
So you can:
By Clicking on the Test Table, a popup menu appears. The enabled items depend on the status of
the test table:
If the table is empty, by clicking on the header of the table, the only available item is “Select
columns to show”
If more than one row is selected, the items “Comment to the test”, “Load fault values with
line values” and “Load line values with Fault values” are not enabled, otherwise all items
are enabled.
Mark as executed: this function puts a mark * beside the test number of the selected rows. In
this way it is possible to treat a not executed test as it has been executed and therefore save it
into a database.
Repeat selected tests: repeats the tests corresponding to the selected rows
Comment to the test: The following window appears:
In the “Message” box, it is possible to define a comment to the test that must be displayed
prior to the test execution. The “Show this message” Checkbox allows the user to decide
whether to display the message when this test is executed. There is also a “Notes” box,
where other notes can be inserted. “Message” and “Notes” are stored together with the test
data and can contain also pictures.
By pressing the OK button, if the “Show this message” checkbox is set, an icon will appear
on the first column of the test table beside the test number. This means the comment is
active and will be shown when the test is executed.
Store all tests: transfers all the test that have been executed (with the mark *) from the test
table to the result table
Delete all tests: deletes all the rows in the test table
Set columns to show: opens up a window, showing the columns available in the test table
and allowing the user to select which columns should be displayed.
Doc. MSE20030 Rev. 6.5.3 Page 28/33
Doc. MSE20030 Rev. 6.5.3 Page 29/33
2 PRINTING RESULTS
By selecting “Print Results” option in the file menu, the following window opens:
By checking the option “Show Graph” the report will include a graphic diagram of the results; by
checking the option “Include Notes Page” the report will include a page containing the notes added
by means of the menu item “Notes to the test”
When the user press OK, the following window appears:
The first four buttons allow the user to browse thorough the pages of the report
(first, previous, next and last page).
The button allows the user to print the report, after selecting the printer.
The button allows the user to export the report in the Adobe Acrobat (*.pdf), Microsoft ® Excel
(*.xls), Microsoft ® Word (*.doc) or Rich Text Document (*.rtf) formats, by selecting the type
from the drop down menu, as shown in the following picture:
The button allows the user to zoom in or out the print preview.
Doc. MSE20030 Rev. 6.5.3 Page 31/33
As mentioned in chapter 2 , a result file is formatted as a data base file, ready to be used by
Microsoft Access. Furthermore, it’s possible to import a result table in Microsoft Excel . In the
following figures is explained which are the selections in Excel:
And, after the inclusion of all the columns without any filter, and ordering the rows by
“DBNumber”, the table will appear:
Doc. MSE20030 Rev. 6.5.3 Page 33/33
These notes quickly explain the basic functionality of two medium voltage relays
This type of relay is normally used to protect MV networks against earth faults.
There are several kind of DEF relays. Usually, they operate by measuring the active and reactive
power flowing into the line. When a phase to earth fault occurs, the total power factor decreases as
consequence of a greater angle between currents and voltages.
The phase angle during the fault depends upon the status of the
neutral of the network. For a network with insulated neutral,
the phase angle will be a little bit less than 90°: this is due to
the capacitance of the line.
For other earthing systems (read: Petersen Coil, etc.), the
MTA
phase angle can be less: 40°, 60°...
As a conclusion, two key settings for a directional relay are the Angle Sector
Characteristic Angle MTA and the width of the Angle
Sector sensitivity. The first one is the nominal angle between
current and voltage, with the voltage taken as the reference.
Another key characteristic of a DEF relay is the capability to detect very high resistance earth
faults. The fault current could be very low depending on the fault resistance and grounding status;
sometimes the fault current is even
comparable with the load current.
V
Also, the earth directional relay
shouldn’t trip for all values of voltage Tripping Zone
and current. It is widely accepted that
a directional relay characteristic can Non tripping
run inside the dotted line area, as Zone
shown in the figure.
DEF relays work by measuring the
zero sequence voltage and current. If I
the zero sequence current is easy to
measure (it is the neutral current), the
zero sequence voltage is more complicated. Depending on the system, the Vo can come from delta
connected VT’s, producing a residual voltage Vr = V1+V2+V3, or with internal compensation, so
the relay requires the three phase voltage.
Please note that normally DEF relays measure the residual voltage and current instead of zero
sequence voltage and current. In other words:
Vr = V1+V2+V3 instead of Vo = (V1+V2+V3)/3
Ir = I1+ I2 + I3 instead of Io = (I1+ I2 + I3)/3