240 ‘STRUCTURAL CONCRETE BUILDING CODE (ACI 318-11) AND COMMENTARY
CODE
13.2 — General
13.2.1 — Column strip Is a design strip with a width on
each side of a column centerline equal to 0.25¢, or
0.25¢, whichever Is less. Column strip includes
beams, if any.
13.2.2 — Middle strip is a design strip bounded by two
column strips.
13.23
center
A panel is bounded by column, beam, or wall
es on all sides.
13.2.4 — For monolithic or fuly composite construction,
a beam includes that portion of slab on each side of
the beam extending a distance equal to the projection
of the beam above or below the slab, whichever Is
greater, but not greater than four times the slab
thickness.
13.2.5 — When used to reduce the amount of negative
moment reinforcement over a column or minimum
required slab thickness, a drop panel shall
(a) project below the slab at least one-quarter of the
adjacent slab thickness; and
(b) extend in each direction from the centerline of
Support a distance not less than one-sixth the span
length measured {rom center-to-center of supports
In that direction,
13.2.6 — When used to increase the critical condition
section for shear at a slab-column joint, a shear cap
shall project below the slab and extend a minimum
horizontal distance from the face of the column that is
equal to the thickness of the projection below the slab
soffit
COMMENTARY
R13.2 — General
13.2.3 — A panel includes all flexural elements between
column centerline, Thus, the column strip includes the
beam, if any.
R13.2.4— For monolithic or fully composite construction,
the beams include portions of the slab as flanges. Two
examples of the rule are provided in Fig. R13.2.4.
13.2.5 and R13.2.6— Drop panel dimensions specified in
18.2.5 are necessary when reducing the amount of negative
moment reinforcement following 13.3.7 or to satisfy some
minimum slab thicknesses permitted in 9.5.3. If the
dimensions are less than specified in 13.2.5, the projection
may be used as a shear cap to increase the shear strength of
the slab. For slabs with changes in thickness itis necessary
to check the shear strength at several sections. See 11.11.1.2.
(be, be
Fig. R13.2.4—Examples of the portion of slab o be included
with the beam under 13.2.4
‘American Conctete insttule Copyrighted Material—www-conecrete.org