Motor Protection Relay: Technical Data TD02600004E

You might also like

You are on page 1of 24

Effective May 2016

Technical Data TD02600004E Supersedes March 2011

EMR-4000
Motor Protection Relay
Contents
Description Page
Key Features, Functions and Benefits. . . . . . . . . . 2
General Description. . . . . . . . . . . . . . . . . . . . . . . . 2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Protection and Control Functions . . . . . . . . . . . . . 4
Diagnostic Features. . . . . . . . . . . . . . . . . . . . . . . . 5
Monitoring and Metering. . . . . . . . . . . . . . . . . . . . 5
Communication Software . . . . . . . . . . . . . . . . . . 10
Standards, Certifications and Ratings. . . . . . . . . . 11
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ordering Information. . . . . . . . . . . . . . . . . . . . . . 20
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Key Features, Functions and Benefits General Description


• Microprocessor-based protection with monitoring and control for Eaton’s EMR-4000 motor protection relay is a multifunctional micro-
medium voltage motors. processor-based protective relay for the protection of any size motor
at all voltage levels. It is most commonly applied on medium voltage
• Integral test function reduces maintenance time and expense. or larger motors. The EMR-4000 relay is a current and voltage device
with built in differential protection that provides complete and reli-
• Zone selective interlocking improves coordination and tripping able motor protection, monitoring, diagnostics, metering, and start-
time, and saves money compared to a traditional bus differential ing control functions.
scheme.
The EMR-4000 motor protection relay provides complete current,
• Programmable logic control functions to accommodate different voltage, and frequency protection in a single compact case. The
control schemes, simplify the wiring of the starter. relay has eight current inputs rated for either 5 amperes or 1 ampere
and four voltage inputs. Three of the voltage inputs are to be con-
• Automatically detects direction of the motor and eliminates the nected to the 3-phase power voltage for voltage protection and for
need of switching current inputs into the relay. metering. They can be connected in wye-ground or open delta con-
figuration. The fourth voltage is for independent single-phase under-
• Reduce trouble shooting time and maintenance costs- Trip and voltage/overvoltage protection. The unit is user programmable for 60
event recording in non-volatile memory provides detailed informa- Hz or 50 Hz operation.
tion for analysis and system restoration. 6000 cycles of waveform
capture aids in post fault analysis (viewable using Powerport-E The maintenance mode password protected soft key, can be used
software). for arc flash mitigation to change to an alternate settings group, set
to have instantaneous elements only. The multiple setting groups
• Minimum replacement time- Removable terminal blocks ideal in can also be changed, via communications or a digital input. Flash
industrial environments. memory is used for the programming and all settings are stored in
nonvolatile memory.
• Front USB port and Powerport-E software provides local com- An integral keypad and display is provided for direct user program-
puter access and user-friendly windows based interface for relay ming and retrieval of data without the need of a computer. 14 pro-
settings, configuration, and data retrieval. grammable LEDs provide quick indication of relay status.
• Breaker open/close from relay faceplate or remotely via commu- A front USB port is provided for direct computer connection.
nications. Multiple ports and communications protocols are available.
The EMR-4000 motor protection relay includes programmable logic
• Fast an easy troubleshooting, improved maintenance procedures,
functions. Logic gates and timers may be defined and arranged for
and increased device security. Provides detailed traceability for
customized applications. With the programmable logic control func-
system configuration changes.
tions you can simplify the complexity of your starting schemes by
• Relays self-diagnostics and reporting improves uptime and trou- eliminating timers and auxiliary relays. Flash memory is used for the
bleshooting. programming and all settings are stored in nonvolatile memory. The
relay allows for four preprogrammed setting groups which can be
• Breaker trip circuit monitoring improves the reliability of the activated through software, manually, or contact input.
breaker operation. The EMR-4000 motor protection relay has mass memory for data
storage and a real-time clock with 1 ms time resolution. The relay
will log 300 sequence of event records, 20 detailed trip logs, mini-
. mum/maximum values, load profiles, the 5 latest start profiles,
motor trending, breaker/contactor wear information and waveform
data.
The EMR-4000 has eight discrete inputs, 1 fiber optic input, 2 Form
C, and 2 NO output programmable contacts, and 1 Form C healthy
contact.It also has four 4-20 mA analog outputs and one zone inter-
locking card. The relay provides maximum user flexibility to config-
ure the I/O. All inputs and outputs (except the healthy output) are
user-programmable. The unit also counts with a test mode to force
outputs and simulate currents, to facilitate the commissioning of the
unit. It can be powered from 19 Vdc to 300 Vdc or 40 Vac to 250 Vac
auxiliary power.

2 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Features • kWh (forward, reverse, net)

Protection Features • Vars and kvar demand


• Thermal protection (49/51) • kvarh (lead, leg and net)
• Locked rotor protection ( 49S/51)
• Power factor
• Phase overcurrent elements:
• Frequency
• Two instantaneous elements with timers ( 50P[1], 50P[2], and
50P[3]) • % THD V and I
• Three inverse time overcurrent elements (51P[1], 51P[2], and
51P[3])
• Magnitude THD V and I

• 11 standard curves • Minimum/maximum recording


• Instantaneous or time delay reset • Trending (load profile over time)
• Ground overcurrent elements: • Minimum/maximum recording
• Two instantaneous measured elements with timers (50X[1],
and 50X[2]) • Temperature with remote URTD module
• Two instantaneous calculated elements with timers (50R[1], Monitoring Features
and 50R[2])
• Trip coil monitor
• Two inverse time overcurrent measured elements (51X[1], and
51X[2]) • Breaker wear primary and secondary (accumulated interrupted
current)
• Two inverse time overcurrent calculated elements (51R[1], and
51R[2]) • Oscillography (6000 cycles total)
• 11 standard curves • Fault data logs (up to 20 events)
• Instantaneous or time delay reset • Sequence of events report (up to 300 events)
• Trending (load profile over time)
• Jam or Stall protection (50J[1], 50J[2])
• Motor History
• Phase unbalance negative sequence overcurrent (46[1], 46[2]))
• Records the last 5 motor start profiles
• Underload protection (37[1], 37[2])
• Motor Start Trending
• Temperature protection with optional URTD (49/38)
• CT supervision
• Stars per hour (66)
• VT supervision
• Switch onto fault protection
• Clock (1 ms time stamping)
• Phase voltage unbalance and sequence protection (47[1], 47[2])
• Main 3-phase under/overvoltage (27M[1], 27M[2], 59M[1], 59M[2]) Diagnostic Features
• Broken rotor bar
• Auxiliary single-phase under/overvoltage (27A[1], 27A[2], 59A[1],
59A[2]) Control Functions
• 6 Frequency elements that can be assigned to: over frequency, • Transition for reduced voltage starts
under frequency, rate of change, or vector surge (81[1], 81[2], • Incomplete sequence delay
81[3], 81[4], 81[5], 81[6])
• Permits numbers of cold starts
• Apparent and displacement power factor (55A[1], 55A[2],
55D[1], 55D[2])
• Limits numbers of starts per hour
• Anti-backspin time delay
• Forward and Reverse Watts (32[1], 32[2], 32[3]) • Mechanical load shedding
• Forward and Reverse Vars (32V[1], 32V[2], 32V[3]) • Zero speed switch for long acceleration motors
• Lockout protection (86) • Motor stop inputs
• Remote trip input
• Breaker failure (50BF)
• Emergency override
• Zone interlocking for bus protection (87B) • Breaker/Contactor open-close/stop-start
Metering Features • Remote open-close (stop-start)
• Amperes: Positive, negative and zero sequence • Programmable I/O
• Programmable LEDs
• Volts: Positive, negative and zero sequence
• Programmable Logic
• Differential Current • Multiple setting groups
• Volt-amperes and VA demand
• Watts and kW demand

EATON www.eaton.com 3
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Communication Features Instantaneous overcurrent


• Local HMI The EMR-4000 motor protection relay provides an instantaneous
• Password protected phase overcurrent function to trip the motor for high fault current
levels and save the fuses. This function can be disabled and has
• Addressable an adjustable time delay on starting to avoid nuisance tripping on
• IRIG-B inrush.
• Local USB communication port Phase Unbalance Protection
• Configuration software Motor supply circuits are often fed through fuses and can be run
• Remote communication port: with a single-phase fuse blown, referred to as single phasing the
motor. The EMR-4000 motor protection relay measures the current
• RS-485 Terminals
and voltage unbalance and either can be used to alarm or trip the
• Ethernet RJ45 motor before damage occurs. The EMR-4000 has 2 voltage and 2
• Fiber Optic ST current unbalance elements. Pickup, start, and run timers are pro-
vided for each element.
• RS-485 D-SUB
• LC Duplex Fiber Optic Ground Fault Protection
A separate measuring circuit is used to measure ground current. A
• Protocols: ground CT is recommended for more sensitive protection against
• Modbus-RTU winding insulation breakdown to ground. The relay ground circuit can
• Modbus-TCP be connected residually from the three-phase CTs. The ground fault
protection has pickup and time delay set points or can be disabled.
• IEC-61850
• DNP3-RTU Jam protection
• DNP3-TCP/UDP The user-selectable Jam function protects motors that are running
against a sudden mechanical jam or stall condition. The common
• Profibus-DP application is on motors used on crushers, chippers, or conveyors.
It detects an increase of motor current to a level above full load.
Protection and Control Functions Pickup, start, and run timers and a second element for alarm pur-
poses are provided.
The Eaton’s EMR-4000 motor protection relay has been designed
for maximum motor operation and protection. It permits running the Underload/Underpower Protection
motor close to its design limits while protecting it against excessive The user selectable underload/underpower function is used to detect
heating and damaging overload conditions. The EMR-4000 field prov- the loss of load on the motor. Coupling failure is a common cause
en protection algorithms were developed based on motor designs for loss of load. Whenever is possible, it is better to use underpow-
and operating parameters for optimum operation and protection er to detect loss of load. Three power elements and two underload
while minimizing nuisance tripping. The EMR-4000 motor protection elements are provided in the relay for tripping and alarm purposes.
relay utilizes a patented protection algorithm and measurement tech- Pickup, start, and run timers are provided for each element.
nique based on proven positive and negative (unbalance) sequence
current sampling and true RMS calculations. Frequency Protection
Intel-I-Trip (I2t) overload protection The frequency elements provide the ability to detect when the
motor is operating at off-nominal frequencies that can do damage
The EMR-4000 motor relay features the exclusive Eaton Intel-I-Trip to the process or, to signal to upstream protections or controls to
intelligent overload protection system. Intel-I-Trip develops custom implement load shedding actions.
overload curves simply from motor nameplate data. Intel-I-Trip pro-
tects motors from potentially damaging overload and abnormal oper- Power Factor Protection
ating conditions. The Intel-I-Trip intelligent overload protection feature
utilizes field proven measurement techniques and a patented motor This protection is used in synchronous motors applications to detect
thermal protection model. The EMR-4000 motor relay’s unique mea- out-of-synchornism conditions.
surement technique samples the current waveforms 36 times per
cycle, providing accurate measurements of the positive and negative Undervoltage/Overvoltage Protection
sequence currents. The negative sequence current causes a greater Use the voltage protective functions to detect abnormal system volt-
heating effect on the rotor and has a greater impact on the thermal age conditions potentially hazardous to the motor.
model in the relay. Intel-I-Trip utilizes these measurements in its
motor model to safely protect the motor against the heating effects Reduced voltage starting
of these currents
The EMR-4000 motor protection relay provides a transition and
The motor thermal model is analogous to a bucket that is being filled incomplete sequence function for reduced voltage starting. The user
and drained at the same time. The fill rate is dependent on the motor can select to transition based on the current level and/or on time.
currents and the drain is based on motor design principles. The size
of the bucket is equivalent to the thermal capacity associated with Antibackspin
the mass of the motor. Intel-I-Trip integrates these rates and will The stop function is programmable from 2–20%. For certain applica-
issue a trip when the thermal capacity is filled. tions, such as pumping a fluid up a pipe, the motor may be driven
backward for a period of time after it stops. The EMR-4000 relay pro-
Intel-I-Trip features adaptive trip characteristics that adjust the trip vides an antibackspin timer to prevent starting the motor while it is
times based on measured motor temperature when RTDs are used. spinning in the reverse direction. The timer begins counting from the
moment a stop is declared by the relay.

4 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Start control timers Diagnostic Features


Motors typically have limits to the number of cold starts, starts per Broken Rotor Bar
hour period, or time between starts that are permitted without dam-
age. The EMR-4000 motor protection relay incorporates these timers The EMR-4000 provides advanced motor diagnostics including a
to prevent starting the motor beyond its capabilities. broken rotor bar detection function. The broken rotor bar detection
is a condition maintenance function that continuously monitors
Load shedding the motor’s health while in operation. The advanced Motor Current
Signature Analysis (MCSA) continuously analyzes the motor current
The EMR-4000 motor protection relay provides a mechanical load signature and based on preset algorithms will determine when a
shedding feature that can be used to control an upstream process. broken rotor bar is present in the motor.
The load-shedding function closes a contact on an overload condi-
tion to control an upstream process from adding more load until the The broken rotor bar function will provide early detection of any
overload condition is gone. rotor problems and advise maintenance personnel of the impending
issue allowing for predictive maintenance of the motor and preven-
Emergency override tion of catastrophic motor failures.
The EMR-4000 motor protection relay has a user-programmable fea- By providing early indication of potential rotor problems, serious
ture that will let the operator reset the start inhibitor timers and ther- system issues such as: reduced starting torque, overloads, torque
mal overload bucket. This function is intended for use in emergency and speed oscillation and bearing wear can be avoided. With the
conditions only, and it may result in motor damage or failure. advanced broken rotor bar detection system, advanced warning
of impending problems reduces catastrophic failures, maximizing
Long acceleration motors motor life and system uptime.
Large motors with a high inertia may experience starting currents
that exceed the locked rotor current and time. The EMR-4000 motor Monitoring and Metering
protection relay has logic and provisions for a zero speed switch Sequence of Events Records
input to differentiate between a stall and start condition. If the motor
is spinning, then the relay will not trip on the normal locked rotor The EMR-4000 protection relay records a maximum of 300 events
time allowing the motor to start. associated with the relay. An event is classified as a change of state
as detected by the relay. These include relay pickups, dropouts, trips,
Remote/differential trip contact closure, alarms, setting changes and self-diagnostic failures.
Each event is date and time stamped to a 1 ms resolution. The
The digital inputs can be programmed to accept a contact input
events are stored in a FIFO in chronological order.
from a separate differential relay or other device to trip the motor.
This provides local and remote target information and utilizes the trip Trip Log
contacts of the EMR-4000 motor protection relay. It will also record
and log the motor information at the time of the trip. The EMR-4000 protection relay will store a maximum of 20 trip
records in a FIFO trip log. Each trip record will be date and time
Breaker Failure or Stuck Contactor stamped to a 1 ms resolution. The trip log record will include infor-
mation on the type of fault, protection elements that operated, fault
The EMR-4000 motor protection relay includes a breaker failure
location and currents and voltages at the time of the fault.
(50BF, 62BF) function that can be initiated from either an internal or
external trip signal. This is an independent element that can be used Waveform Capture
to operate a lockout relay or trip an upstream breaker. The timer
must be longer than the breaker operating time and the protective The EMR-4000 motor protection relay provides oscillography-record-
function reset times. ing capabilities. The relay will record all measured signals along with
the binary signals of pickup, trip, logic and contact closures. The
Flexible Phase Rotation EMR-4000 relay can record up to 6000 cycles of data. The number
of records is proportional to the size of each record; the maximum
The EMR-4000 motor protection relay can be applied on either an
size per record is 600 cycles. The waveform capture is initiated by
A-B-C or A-C-B phase rotation. A user setting permits correct opera-
up to 8 different triggers; it can also be generated manually through
tion and indication of the actual system configuration.
the display or via communications.
Maintenance Mode
Integral User Interface
The Maintenance Mode can improve safety by providing a simple
The front panel user interface has a 128 x 64 pixel LCD display with
and reliable method to reduce fault clearing time and lower incident
background illumination for wide angle viewing in all light condi-
energy levels at energized panels. The Maintenance Mode allows
tions. 7 programmable LEDs provide quick and easy visual display of
the user to switch to more sensitive settings via a password protect-
power on, mode of operation, alarm and trip indication. Soft keys are
ed soft key, communication or via a digital Input while maintenance
provided for operation mode selection, scrolling through data and
work is being performed at an energized panel or device. The more
settings. In addition, the relay settings and test functions are pass-
sensitive settings provide greater security for maintenance person-
word protected.
nel and helps reduce the possibility of injury.
Starting Profiles
The EMR-4000 records the average current versus time for the last
five starting cycles. This information is available via the communica-
tions port through Powerport-E.

EATON www.eaton.com 5
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Motor Statistics Programmable I/O


For each motor start, the EMR-4000 stores a motor start report and The EMR-4000 motor protection relay provides heavy-duty, trip-
add this data to the motor statistics buffer. With the motor statistics rated, 2 normally open and 1 Form C contacts. One isolated inputs
you can track motor start data for the past eighteen 30-day periods. can be used for monitoring the trip circuit. One Form C contact is
For each 30-day interval, the relay records the following information: dedicated to the relay failure alarm function and is operated in a nor-
mally energized (failsafe) mode. There are 4 eight user-configurable
• The date the interval began
discrete inputs that accept a wet contact and can operate through
• The total number of starts in the interval a wide range of power. Each input and output is user-programmable
• The averages of the following quantities: for maximum application flexibility.
• Motor Start Time Programmable Logic
• Start % Rotor Thermal Capacity Used The EMR-4000 motor protection relay provides logic gates and tim-
• Maximum Start Current ers that the user can customize for special or unique applications.
Each gate can be assigned a logic function of either AND, OR,
Load Profiling/Trending NAND or NOR. Each gate can have a maximum of four input signals
and each input signal can be required to be a NOT. Input signals can
The EMR-4000 relay automatically records selected quantities into be external inputs received via the binary inputs or internal values
non-volatile memory every 5, 10, 15, 30, or 60 minutes, depending associated with the protection, alarm or metering set points. Each
on the trending report setting. gate has a unique output assignment and designation that can be
used as the input to another gate.

Figure 1. Programmable Logic.


8.16
[207,2]
7.76
[197,2]
7.17 "B" HOLES FOR
[182,0] PROJECTION
6.00 PANEL MOUNT
[152,4]
"A" HOLES FOR
C
L STANDARD
B PANEL MOUNT
B A

A A

CUTOUT 4.88
[124,0]
7.12 B C 6.30
[180,8] L [160,0]
B
6.64
[168.6]

A
A
B A
B
6x 0.19
6x 0.19 [04,8]
[04,8]

Figure 2. Drilling Plan.


6 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Figure 3. Projection Mount Front and Side Views.

Figure 4. Standard Mount Front and Side Views.

EATON www.eaton.com 7
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Figure 5. Typical AC Connections. Wye VTs, 5A Cts, and Ground Current Measured by Residual Connection.

8 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

EMR-4000
1
Metering,
27A Statistics and
Demand
Current and Volt.:
59A
unbalance
%THD and THD
74 Fund. and RMS
46 51J 50P 51 51P 51R 66 LOP
TC min./max./avg.
phasors and
angles
3 50
37 49S 50R CTS
BF
Power:
1 Fund. and RMS
55 MVA, Mwatt, Mvar,
47 32 32V
A/D PF
3 Waveform recorder
81
27M 59M 81 R 78V 51V 50X 51X
U/O Fault recorder
*
Event recorder
Trend recorder
IRIG-B00X Programmable Zone Analog Start recorder
Breaker Wear
SNTP Logic Interlocking Outputs
Statistics recorder

URTD Assembly History function

14

Option standard
Load

Motor

URTD Assembly

26

Figure 6. Typical One-Line Diagram.

Figure 7. Typical Control Diagram.

EATON www.eaton.com 9
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Communication Software
Eaton provides two types of communication software. The first is The second package is Power Xpert Software. Power Xpert Software
PowerPort-E. It runs on a PC or laptop for easy access to a single is a power management software package that is designed for con-
relay to change set points or configuration and to view metered tinuous, remote monitoring of many devices. It provides additional
values and stored data. PowerPort-E is free and can be downloaded functions such as billing, trending and graphics. Contact your local
from the Eaton Web site at the following URL: Eaton representative for more information on Power Xpert software.
http://www.EatonElectrical.com/pr

Powerport-E- EMR-4000 Device Planning

Figure 8. Powerport-E - EMR-4000 Device Planning.

10 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Standards, Certifications and Ratings Current and Ground Current Measurement


Plug-in Connector with Integrated Short-Circuiter
(Conventional Current Inputs)
NOTICE
USE COPPER CONDUCTORS ONLY, 75°C (167°F). Phase and Ground Current Inputs:
CONDUCTOR SIZE AWG 14 [2.5 MM].
Nominal Currents: 1A/5A

Climatic Environmental Conditions Max. Measuring Range: Up to 40 x In (phase currents)


Up to 25 x In (ground current standard)
Storage Temperature: -30°C to +70°C (-22°F to 158°F) Capacity: 4 x In/continuously
Operating Temperature: -20°C to +60°C (-4°F to 140°F) Overcurrent Proof: 30 x In / 10 s
100 x In / 1 s
Permissible Humidity at Ann. Average: <75% rel. (on 56d up to 95% rel.) 250 x In / 10 ms (1 half-wave)
Permissible Installation Altitude: <2,000 m (6,561.67 ft) above sea level Power Consumption: Phase current inputs
At In= 1 A S=0.15 mVA
If 4,000 m (13,123.35 ft) altitude applies, a At In= 5 A S=0.15 mVA
changed classification of the operating and
test voltages may be necessary. Ground Current Input
At In= 1 A S=0.35 mVA
At In= 5 A S=0.35 mVA
Degree of Protection EN 60529

HMI Front Panel with Seal: IP54 Sensitive Ground Current Inputs:
Rear Side Terminals: IP20 Nominal Currents: 1 A / 5 A with 50:0:025 core balance CT
Max. Measuring Range: Up to 2.5 x In
Capacity: 2 x In/continuously
Routine Test
Overcurrent Proof: 10 x In / 10 s
Insulation Test Acc. to IEC60255-5: All tests to be carried out against ground 25 x In / 1 s
and other input and output circuits. 100 x In / 10 ms (1 half-wave)
Aux. Voltage Supply, Digital Inputs, Current 2.5 kV (eff.) / 50 Hz Power Consumption: At In= 1 A S=0.35 mVA
Measuring Inputs, Signal Relay Outputs: At In= 5 A S=0.35 mVA
Voltage Measuring Inputs: 3.0 kV (eff.) / 50 Hz Frequency Range: 50 Hz / 60 Hz ± 10%
All Wire-Bound Communication Interfaces: 1.5 kV DC Terminals: Screw-type terminals with integrated short-
circuiters (contacts)
Screws: M4, captive type acc. to VDEW
Housing Connection Cross Sections: 1 x or 2 x 2.5 mm2 (2 x AWG 14) with wire
end ferrule
Housing B2: Height / Width 183 mm (7.205 in.)/ 212.7 mm (8.374 in.) 1 x or 2 x 4.0 mm2 (2 x AWG 12) with ring
cable sleeve or cable sleeve
Housing Depth (Incl. Terminals): 208 mm (8.189 in.) 1 x or 2 x 6 mm2 (2 x AWG 10) with ring
Material, Housing: Aluminum extruded section cable sleeve or cable sleeve

Material, Front Panel: Aluminum/Foil front The current measuring board’s terminal
Mounting Position: Horizontal (±45° around the X-axis must be blocks may be used as with 2 (double) con-
permitted) ductors AWG 10,12,14 otherwise with single
conductors only.
Weight: Approx. 4.2 kg (9.259 lb)

Voltage and Residual Voltage Measurement

Nominal Voltages: 60 - 520 V (can be configured)


Max. Measuring Range: 2 x nominal voltage or 800 V
Continuous Loading Capacity: 800 Vac
Power Consumption: at Vn= 100 V S=0.1 mVA
at Vn= 110 V S=0.1 mVA
at Vn= 230 V S=0.4 mVA
at Vn= 400 V S=1.0 mVA
Nominal Voltages: 60 - 520 V (can be configured)
Frequency Range: 50 Hz or 60 Hz ± 10%
Terminals: Screw-type terminals

EATON www.eaton.com 11
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Frequency Measurement Real Time Clock

Nominal Frequencies: 50 Hz / 60 Hz Running Reserve of the Real Time Clock: 1 year min.

Voltage Supply Digital Inputs

Aux. Voltage: 24 - 270 Vdc / 48 - 230 Vac (-20/+10%) Max. Input Voltage: 300 Vdc / 259 Vac
>= 50 ms at minimal aux. voltage Input Current: <4 mA
Buffer Time in case of Supply Failure: Interrupted communication is permitted.
Reaction Time: <20 ms
18 A peak value for <0.25 ms
Drop-out Time:
Max. Permissable Making Current: 12 A peak value for <1 ms
Shorted Inputs <30 ms
The voltage supply must be protected by a fuse of: Open Inputs <90 ms
2,5 A time-lag miniature fuse approx. 5 x 20 mm (0.2 x 0.8 in.) according to IEC 60127
3,5 A time-lag miniature fuse approx. 6,3 x 32 mm (0.25 x 1.25 in.) according to UL 248-14
Relay Output Contacts

Power Consumption Continuous Current: 5 A ac / dc


Max. Make Current: 25 A ac / 25 A dc for 4 s
Power Supply Range: Power consumption in Idle Max. Power Consumption 30 A / 230 Vac according to ANSI IEEE Std
Mode C37.90-2005
30 A / 250 Vdc according to ANSI IEEE Std
24 - 270 Vdc: Approx. 7 W Approx. 13 W
C37.90-2005
48 - 230 Vac Approx. 7 VA Approx. 13 VA
Max. Breaking Current: 5 A ac up to 240 Vac
(For Frequencies of 50-60
5 A dc up to 30 V (resistive)
Hz):
Continuous Current: 5 A ac/ dc
Contact Type: Form C or normally open contact
Display Terminals: Screw-type terminals

Display Type: LCD with LED background illumination


Resolution - Graphics Display: 128 x 128 pixel
Supervision Contact (SC)

Continuous Current: 5 A ac / dc
LED - Type: Two colored: red / green
Max. Switch-on Current: 15 A ac / 15 A dc for 4 s
Number of LEDs, Housing B2: 15
Max. Breaking Current: 5 A ac up to 250 Vac
5 A dc up to 30 Vdc (resistive)
0,25 A at 250 Vdc (resistive)
Front Interface USB
Max. Switching Voltage: 250 V ac / 250 Vdc
Type: Mini B Switching Capacity: 1,250 VA
Contact Type: Form C
Terminals: Screw-type terminals

12 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Analog Outputs RS485*


The following technical data only apply to devices, which are Master/Slave: Slave
equipped with analog outputs. Please refer to the order code of
your device. Connection: 6 screw-clamping terminals RM 3.5 mm (138
MIL) (terminating resistors internal)
The mode of each output can be individually selected between cur-
rent or voltage output. Shielded cable for the analog outputs is rec-
ommended. The terminals of the HF shield should be used, when
connecting the shield to the ground on both sides of the cable is
not possible. On one side of the cable the shield has to be directly CAUTION
connected to ground. In case of the use of unshielded twisted pair
cables, the length must not exceed 10 m. All analog outputs have a THE RS485 INTERFACE IS REALIZED VIA TERMINALS. THE COMMUNICA-
common potential. Each output has an own common terminal. TION CABLE HAS TO BE SHIELDED. THE SHIELDING HAS TO BE FIXED AT
THE SCREW THAT IS MARKED WITH THE GROUND SYMBOL (REAR SIDE OF
THE DEVICE).
Current Mode
Range: 0-20 mA Fiber Optic*
Max. Load Resistance: 1kΩ
Master/Slave: Slave
Voltage Mode
Range: 0 - 10 V maximum output current 20 mA Connection: ST-Plug

Accuracy 0.5% of the nominal value 20 mA resp. 10 V


Influence of temperature to accuracy <1% (within the range of 0°C to +60°C
(+32°F to +140°F) URTD-Interface*
Test voltage of outputs (one group) against Connection: Versatile Link
other electrical groups 2.5 kV
*availability depends on device
Test voltage of outputs (one group) against
ground 1.0 kV

Boot Phase
After switching on the power supply, the protection will be available
Time Synchronization IRIG-B00X in approximately 19 seconds. After approximately 165 seconds, the
boot phase is completed (HMI and Communication initialized).
Nominal Input Voltage: 5V
Connection: Screw-type terminals (twisted pair)

Zone Interlocking

NOTICE
ONLY FOR ZONE INTERLOCK TRIPPING OUTPUTS (ZONE INTERLOCK, SEMI-
CONDUCTOR OUTPUT): 5 VDC, <2MA FOR CONNECTION TO ELECTRONIC
INPUTS ONLY.

Zone Out:
Output voltage (High) 4.75 to 5.25 Vdc
Output voltage (Low) 0.0 to +0.5 Vdc

Zone In:
Nominal input voltage +5 Vdc
Max. input voltage +5.5 Vdc
Switching threshold ON min. 4.0 Vdc
Switching threshold OFF max. 1.5 Vdc

Galvanic isolation: 2.5 kV ac (to ground and other IO)


Connection: Screw-type terminals (twisted pair)

EATON www.eaton.com 13
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Standards EMC Emission Tests


Approvals Radio Interference Suppression Test
• UL-listed file: E217753 IEC/CISPR11 Limit value class B

Design Standards Radio Interference Radiation Test


IEC/CISPR11 Limit value class B
Generic Standard EN 61000-6-2
EN 61000-6-3
Product Standard IEC 60255-6
EN 50178 Environmental Tests
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 14-95 (Industrial Control Classification:
Equipment)
IEC 60068-1 Climatic 20/060/56
ANSI C37.90
Classification
IEC 60721-3-1 Classification of ambient 1K5/1B1/1C1L/1S1/1M2 but min.
conditions (Storage) -30°C (-22°F)
High Voltage Tests (IEC 60255-6)
IEC 60721-3-2 Classification of ambient 2K4/2B1/2C1/2S1/2M2 but min.
High Frequency Interference Test conditions (Transportation) -30°C (-22°F)
IEC 60255-22-1 With one circuit 1 kV/2 s IEC 60721-3-3 Classification of ambient 3K6/3B1/3C1/3S1/3M2
Class 3 Circuit to ground 2.5 kV/2 s conditions (Stationary but min. -20°C (-4°F) / max 60°C
Circuit to circuit 2.5 kV/2 s use at weather protected (140°F)
locations)
Insulation Voltage Test
Test Ad: Cold
IEC 60255-5 All circuits to other circuits 2.5 kV (eff.)/ 50Hz, 1 min.
EN 50178 and exposed conductive IEC 60068-2-1 Temperature -20°C (-4°F)
parts Test duration 16 h
Except interfaces 1.5 kV DC, 1 min.
Test Bd: Dry Heat
Voltage measuring input 3 kV (eff.)/50 Hz, 1 min. IEC 60068-2-2 Temperature 60°C (140°F)
Relative humidity <50%
Impulse Voltage Test
Test duration 72 h
IEC 60255-5 5 kV/0.5J, 1.2/50 µs
Test Cab: Damp Heat (Steady State)
IEC 60068-2-78 Temperature 40°C (104°F)
Relative humidity 95%
EMC Immunity Tests Test duration 2
Test Db: Damp Heat (Cyclic)
Fast Transient Disturbance Immunity Test (Burst)
IEC 60068-2-30 Temperature 60°C (140°F)
IEC 60255-22-4 Power supply, mains inputs ± 4 kV, 2.5 kHz
Realative humidity 95%
IEC 61000-4-4
Cycles (12 + 12-hour) 2
Class 4 Other in- and outputs ± 2 kV, 5 kHz (coupling network)
ANSI C37.90.1 ± 4 kV, 2.5 kHz (coupling clamp)
Surge Immunity Test
IEC 61000-4-5 Within one circuit 2 kV
Class 4 Circuit to ground 4 kV
Communication cables to
Class 3 ground 2 kV
Electrical Discharge Immunity Test
IEC 60255-22-2 Air Discharge 8 kV
IEC 61000-4-2
Class 3 Contact discharge 6 kV
Radiated Radio Frequency Electromagnetic Field Immunity Test
IEC 6100-4-3 26 MHz - 80 MHz 10 V/m
ANSI C37.90.2 80 MHz - 1 GHz 35 V/m
1 GHz - 3 GHz 10 V/m
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
IEC 61000-4-6 10V
Class 3
Power Frequency Magnetic Field Immunity Test
IEC 61000-4-8 Continuous 30 A/m
Class 4 3 sec 300 A/m

14 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Mechanical Tests Specifications of the Measured Value Acquisition

Test Fc: Vibration Response Test


Phase and Ground Current Measuring
IEC 60068-2-6 (10 Hz – 59 Hz) 0.0014 in. (0.035 mm) Nominal current (ln): 1 A or 5 A (separate terminal inputs)
IEC 60255-21-1 Displacement
Class 1 (59 Hz – 150 Hz) 0.5 gn Max. Measuring Range: 40 A (25 A Ground or 2.5 A Ground sensitive)
Acceleration Frequency Range: 50 Hz / 60 Hz ± 10%
Number of cycles in each 1
axis Accuracy: Class 0.5

Test Fc: Vibration Endurance Test Amplitude Error if I < 1 In: ±0.5% of the rated value *

IEC 60068-2-6 (10 Hz – 150 Hz) Amplitude Error if I > In: ±0.5% of the measured value *
IEC 60255-21-1 Acceleration 1.0 gn Amplitude Error if I > 2 In: ±1.0% of the measured value *
Class 1
Number of cycles in each Resolution: 0.01 A (0.001 A for earth current sensitive)
axis 20
*For earth current sensitive the precision
Test Ea: Shock Test does not depend on the nominal value but is
IEC 60068-2-27 Shock response test 5 gn, 11 ms, 3 impulses in referenced to 100 mA (with In =1 A) respec-
IEC 60255-21-2 each direction tively 500 mA (with In = 5 A)
Class 1 Harmonics: Up to 20% 3rd harmonic ±2%
Shock resistance test 15 gn, 11 ms, 3 impulses in Up to 20% 5th harmonic ±2%
each direction Frequency Influence: <±2% / Hz in the range of ±5 Hz of the con-
Test Eb: Shock Endurance Test figured nominal frequency

IEC 60068-2-29 Shock endurance test 10 gn, 16 ms, 1,000 impulses Temperature Influence: <±1% within the range of 0°C to +60°C
IEC 60255-21-2 in each direction (+32°F to +140°F)
Class 1
Test Fe: Earthquake Test
IEC 60068-3-3 Single axis earthquake 3 – 7 Hz: Horizontal 0.394 in. Phase-to-Ground and Residual Voltage Measurement
KTA 3503 vibration test (10 mm), 1 cycle each axis
IEC 60255-21-3 Nominal voltage (Vn): 60 ... 600 V in 1 V steps
Class 2 7 – 35 Hz Horizontal: 2 gn, 1 Max measuring range: 800 V
cycle each axis
Frequency range: 50 Hz or 60 Hz ±10%
Precision: Class 0,5
Amplitude error for V<Vn (measured): ±0.5% of the rated value
Specifications
Amplitude error for V<Vn (calculated): ±1.0% of the rated value
Specifications of the Real Time Clock Amplitude error for V>Vn (measured): ±0.5% of the measured value
Resolution: 1 ms Amplitude error for V>Vn (calculated): ±1.0% of the calculated value
<1 minute / month (+20°C [68°F]) Resolution: 0.1 V
Tolerance: < ±1 ms if synchronized via IRIG-B
Harmonics: up to 20% 3rd harmonic ±1%, up to 20% 5th har-
monic ±1%
Frequency Influence: <±2% / Hz in the range of ±5 Hz of the configured
Time Synchronization Tolerances nominal frequency
The different protocols for time synchronization vary in their accu- Temperature Influence: <±1% within the range of 0°C up to +60°C
racy:

Used Protocol Time drift over one month Deviation to time generator
Without time synchronization <1 min (20°C) Time drifts Frequency Measurement
IRIG-B Dependent on the time drift <±1 ms Nominal frequency: 50 Hz / 60 Hz
of the time generator
Precision: ±0.05% of fn within the range of 40-70 Hz at
SNTP Dependent on the time drift ±1 ms voltages >50 V
of the time generator
Voltage dependency: frequency acquisition of 5 V – 800 V
Modbus TCP Dependent on the time drift Dependent on the network
of the time generator label

Energy Measurement*

Energy counter error for VAh < Sn* 1 h: 3% of Sn


Energy counter error for VAh > Sn* 1 h: 3% of measured energy

EATON www.eaton.com 15
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Power Measurement* Reset Mode Calculated, ±5%


(Instantaneous, IEC NINV
VA, W, VAr: <±3% of the measured value or 0.1% x Sn t-delay) IEC VINV
IEC EINV
IEC LINV
IEC MINV
Power Factor Measurement* IEC VINV
IEC EINV
PF: ±0.01 of measured power factor or 1° Flat
l > 30% x In lt
l2t
l4t

*Tolerance at 0.8 … 1.2xVn (with Vn=100V) , |PF|>0.5, symmetrically t-reset (Reset Mode = t-delay) 0.00 ... 60.00 s 0.01 s ±1% resp. ±10 ms
fed. Units are selected automatically depending on CT and VT rat-
ings for best fit. Sn=1.73 * VT rating * CT rating
Ground Current Elements: Range Step Accuracy
50X[x], 50R[x]
Protection Elements Accuracy Pickup (measured ground 0.02 ... 4.00 x ln 0.01 x ln ±1.5% of the setting value
current) Resp. 1% x In
Pickup (calculated ground ±2.0% of the setting value
NOTICE current) Resp. 1.5% x In
THE TRIPPING DELAY RELATES TO THE TIME BETWEEN ALARM AND Dropout Ratio 97% or 0.5% x In
TRIP. THE ACCURACY OF THE OPERATING TIME RELATES TO THE TIME
t 0.00 ... 300.00 s 0.01 s DEFT ±1% resp. ±10 ms
BETWEEN WHEN THE MEASURED VALUE HAS EXCEEDED THE THRESHOLD
UNTIL THE PROTECTION ELEMENT IS PICKED-UP. Operating Time <35 ms
Starting from IE higher than
1.1 x IE>
Disengaging Time <45 ms
Overcurrent Protection Range Step Accuracy
Elements 50P[x] t-reset (Reset Mode = t-delay) 0.00 ... 60.00 s 0.01 s ±1% resp. ±10 ms

Pickup 0.02 ... 20.00 x ln 0.01 x ln ±1.5% of the setting value


resp. 1% x in.
Ground Current Elements: Range Step Accuracy
Dropout Ratio 97% or 0.5% x In 51X[x], 51R[x}
t 0.00 ... 300.00 s 0.01 s DEFT Pickup (measured ground 0.02 ... 4.00 x ln 0.01 x In ±1.5% of the setting value
±1% resp. ±10 ms current) Resp. 1% x In
Pickup (calculated ground ±2.0% of the setting value
Operating Time <35 ms current) Resp. 1.5% x In
Starting from l higher than
1.1 x l> Dropout Ratio 97% or 0.5% x In
Disengaging Time <45 ms Operating Time <35 ms
Starting from IE higher than
1.1 x IE>
Overcurrent Protection Range Step Accuracy Disengaging Time <45 ms
Elements 51P[x]
t-Multiplier 0.02 ... 2.00 0.01 ±5%
Pickup 0.02 ... 4.00 x ln 0.01 x ln ±1.5% of the setting value IEC NINV
resp. 1% x in. IEC VINV
Dropout Ratio 97% or 0.5% x In IEC EINV
IEC LINV
Operating Time <35 ms
Starting from l higher than 0.02 ... 20.00 0.01 ±5%
1.1 x l> ANSI MINV
ANSI VINV
Disengaging Time <45 ms ANSI EINV
Flat
t-Multiplier 0.02 ... 2.00 0.01 ±5%
lt
IEC NINV
l2t
IEC VINV
l4t
IEC EINV
IEC LINV Reset Mode Calculated, ±5%
(Instantaneous, IEC NINV
0.02 ... 20.00 0.01 ±5%
t-delay) IEC VINV
IEC MINV
IEC EINV
IEC VINV
IEC LINV
IEC EINV
ANSI MINV
Thermal Flat
ANSI VINV
lt
ANSI EINV
l2t
Flat
l4t
lt
l2t
l4t

16 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

t-reset (Reset Mode = t-delay) 0.00 ... 60.00 s 0.01 s ±1% resp. ±10 ms Disengaging Time <40 ms

Voltage restraint: Range Step Accuracy Over Frequency Protection: Range Step Accuracy
51V[x] 81O[x]
Pickup 0.04 ... 2.00 x Vn 0.01 x Vn ±1.5% of the setting value Threshold 40.00 ... 69.95 0.01 Hz 10 mHz at fn
Resp. 1% x In Hz
Dropout Ratio 97% or 0.5% x ln Dropout Ratio 99.95%
or 0.05% x fn
Operating Time <35 ms
Starting from l higher than t 0.00 ... 3600.00 0.01 s ±1% resp. ±10 ms
1.1 x l> s
Disengaging Time <45 ms Operating Time 40-50Hz <60 ms
Starting from f higher than 50-70Hz <50 ms
f>+0.02 Hz
Overcurrent Protection Range Step Accuracy Disengaging Time 40-50Hz <85 ms
Elements: 49 Thermal 50-70Hz <75 ms
Model
Trip Threshold 0.60 ... 0.99 0.01 ±1.5% of the setting value
Resp. 1% In Under Frequency Range Step Accuracy
Protection 81U[x]
Trip Delay 0.0 ... 3600.0 s 0.1 s DEFT ±1% resp. ±10 ms
Threshold 40.00 ... 69.95 0.01 Hz 10 mHz at fn
Alarm Threshold 0.60 ... 0.99 0.01 ±1.5% of the setting value
Hz
Resp. 1% In
Dropout Ratio ±1% resp. ±10 ms
Alarm Delay 1 ... 360 x min 1 x min DEFT ±1% resp. ±10 ms
t 0.00 ... 3600.00 0.01 s 100.05% or 0.05% x fn
s
Undervoltage and Range Step Accuracy Operating Time 40-50Hz <60ms
Overvoltage (Phase and Starting from f lower than 50-70Hz <50ms
Auxiliary) 27M[x] / 59M[x] f<-0.02 Hz
27A[x] / 59A[x]
Release Time 40-50Hz <85 ms
Pickup 0.01 ... 1.30 x Vn 0.01 x Vn ±1.5% of the setting value 50-70Hz <75 ms
Resp. 1% x Vn
V Block f ±1.5% of the setting value
Dropout Ratio 97% or 0.5% x Vn resp 1% x Vn
t 0 ... 300 s 0.01 s DEFT Dropout Ratio 103%
±1% resp. ±10 ms or 0.5% x Vn
Operating Time <35 ms

Starting from V higher/lower Rate of Change of Range Step Accuracy


than 1.1 x V> or V< Frequency df/dt
Disengaging Time <45 ms Threshold 0.01 .. 10 Hz/s 0.01 Hz/s 100 mHz per Second
t 0.00 ... 300.00 0.01 s ±1% resp. ±10 ms
s
Current unbalance: 46[x] Range Step Accuracy
Operating Time <40 ms
Threshold 0.01 ... 4.00 x ln 0.01 x In ±2% of the setting value
resp. 1% In Disengaging Time <40 ms
l2/l1 ≥ 0.1 ... 4.00 x In 2 ... 40% 1.00% ±1%
t DEFT Rate of Change of Range Step Accuracy
0 ... 300 s 0.01 s ±1% resp. ±10 ms Frequency Df/Dt
Operating Time <60 ms Df 0.0 ... 10.0 Hz 0.1 Hz 100 mHz per Second
Starting from l2/l1 ≥ 1.1 x In
Dt 0.1 ... 10.0 0.1 s ±1% resp. ±10 ms
Disengaging Time <40 ms
Operating Time <40 ms
Disengaging Time <40 ms
Voltage unbalance: 47[x] Range Step Accuracy
Threshold 0.01 ... 1.30 0.01 x Vn ±2% of the setting value Vector surge 78V Range Step Accuracy
x Vn resp. 1% Vn
Threshold 1 ... 30 degrees 1 degree ±0,5 [1-30°] at Vn and fn
V2/V1 ≥ 0.1 x Vn 2 ... 40% 1.00% 97% or 0.5% x Vn
Operating Time <40 ms
t 0 ... 300 s 0.01 s DEFT
±1% resp. ±10 ms
Operating Time <60 ms PQ-protection: 32[x]/32V[x] Range Step Accuracy
Starting from V2/V1 ≥ 1.1
x Vn

EATON www.eaton.com 17
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Threshold 0.02 ... 10.00 0.01 x VAn ±3% or ±1.5% VAn Kd - Correction Factor 0.00 ... 0.99 0.01
x VAn
Dropout Ratio 94%
t 0.00 ... 1100.00 0.01 s ±1% resp. ±10 ms
s
Operating Time 75 ms Jam-Stall Protection: Range Step Accuracy
50J
Disengaging Time 75 ms
Threshold 1.00 ... 12.00 0.01 x FLA ±1.5% of the setting value
Dropout Ratio 97% for P>/Q> and 103% x FLA resp. 1% In
for P</Q<
Resetting Ratio 97% or 0.5%
x ln
Power Factor PF-55D / Range Step Accuracy t 0.00 ... 0.01 s DEFT
PF-55A 1200.00 s ±1% resp. ±10 ms
Trigger-PF 0.50 ... 0.99 0.01 ± 0.01 (absolute) Operating Time < +35 ms
Starting from l higher than
Reset-PF 0.50 ... 0.99 0.01 ± 0.01 (absolute)
1.1 x l>
t-trip 0.00 ... 0.01 s ±1% resp. ±10 ms
Disengaging Time < +45 ms
300.00 s
T-Pickup Comp 0.00 ... 0.01 s ±1% resp. ±10 ms
300.00 s Under Load Protection: Range Step Accuracy
T-Reset Comp 0.00 ... 0.01 s ±1% resp. ±10 ms 37[x]
300.00 s Threshold 0.05 - .90 x 0.01 x FLA ±1.5% of the setting value
Operating Time <120 ms FLA resp. 1% In
t 0.04 - 1200.0 s 0.01 s DEFT
±1% resp. ±10 ms
Switch On To Fault: SOTF Range Step Accuracy
Operating Time < +35 ms
Operating Time <35 ms Starting from l higher than
1.1 x l>
l< 0.01 ... 1.00 0.01 x ln ±1.5% of the setting value
x ln resp. 1% x ln Disengaging Time < +45 ms

t-enable 0.10 ... 10.00 s 0.01 s ±1% resp. ±10 ms

Mechanical Load Range Step Accuracy


Shedding: MLS
Breaker Failure Range Step Accuracy
Protection: 50BF Pickup Threshold 0.05 - 1.50 0.01 x FLA ±1.5% of the setting value
x FLA resp. 1% In
I-BF> 0.02 ... 0.10 0.01 x ln ±1.5% of the setting value
x ln resp. 1% x In Pickup Delay 0.0 -5.0 s 0.1 s DEFT
±1% resp. ±10 ms
t-BF 0.00 ... 10.00 s 0.01 s ±1% resp. ±10 ms
Dropout Threshold 0.05 - 1.50 0.01 x FLA ±1.5% of the setting value
Resetting Ratio 0.5% x ln x FLA resp. 1% In
Operating Time <40 ms Dropout Delay 0.0 -5.0 s 0.1 s DEFT
Starting from I Higher than ±1% resp. ±10 ms
1.3 x 1-BF>
Disengaging Time <40 ms

Trip Circuit Monitoring: Range Step Accuracy


TCM
t-TCM 0.10 ... 10.00 s 0.01 s ±1% resp. ±10 ms

Loss of Potential: LOP Range Step Accuracy


t-Pickup 0.0 ... 9999.0 s 0.1 s ±1% resp. ±10 ms

Current Transformer Range Step Accuracy


Supervision CTS
Dl 0.10 ... 1.00 0.01 xln ±2% of the setting value
xln resp. 1.5% In
Pickup Delay 0.1 ... 9999.0 s 0.1 s ±1% resp. ±10 ms

18 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Motor Protection: 66 [x] Range Step Accuracy


SPH 1 - 10 per hr. 1 ±0
Number of starts per hour.
Reset Starts Per Hour 1 hr. N.A. ±1 min.
Reset starts per hours timer
from oldest start event.
Stop Declaration > 280 ms Fixed + .016ms, - 0 ms
Time period current must
drop below threshold.
Anti Backspin 1 -3600 sec. 1 sec. ±1 sec.
Blocking time to allow for
back spin.
TBS Timer 1 -240 min. 1 min. + 1 sec.
Time between repeated
starts.

Temperature Protection Range Step Accuracy


Elements: 49/38 [x]
RTD Trip w /URTD
Trip WDx, MBx, LBx 0 - 200°C (32 - 1°C (1.8°F) ±1°C (1.8°F)
392°F)
Alarm WDx, MBx, LBx 0 - 200°C (32 - 1°C (1.8°F) ±1°C (1.8°F)
392°F)
T-delay Alarm 0 ... 360 x min 1 x min DEFT
±1% resp. ±10 ms
Reset Hysteresis -2°C (-3.6°F) Fixed ±1°C (1.8°F)
of threshold

Start Delay Timers Range Step Accuracy


IOC Start Delay .03 - 1.00 sec. .01 s + 32 ms
GOC Start Delay .03 - 1.00 sec. .01 s + 32 ms
Underload Start Delay 0 - 1200 sec. 1s + 60ms, - 0 ms
(l) Unbal. Start Delay 0 - 1200 sec. 1s + 60ms, - 0 ms
Jam Start Delay 0.03 - 1200.00 sec. 0.01 s + 60ms, - 0 ms
Undervoltage Start Delay 0 - 1200 sec. 1s + 60ms, - 0 ms
Overvoltage Start Delay 0 - 1200 sec. 1s + 60ms, - 0 ms
Power Start Delay 0.03 - 1200.00 sec. 0.01 s + 60ms, - 0 ms
Power Factor Start Delay 0.03 - 1200.00 sec. 0.01 s + 60ms, - 0 ms
Frequency Start Delay 0 - 1200 sec. 1s + 60ms, - 0 ms
Current Differential Start Delay 0.03 - 1.00 sec. 0.01 s + 60ms, - 0 ms
Generic 1 0 - 1200 sec. 1s + 60ms, - 0 ms
Generic 2 0 - 1200 sec. 1s + 60ms, - 0 ms
Generic 3 0 - 1200 sec. 1s + 60ms, - 0 ms
Generic 4 0 - 1200 sec. 1s + 60ms, - 0 ms
Generic 5 0 - 1200 sec. 1s + 60ms, - 0 ms

EATON www.eaton.com 19
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Ordering Information
Sample Catalog Number
The catalog number identification chart defines the electrical characteristics and operation features included in the EMR-4000. For example, if
the catalog number were EMR-4000-2A0BA1, the device would have the following:

EMR-4000
(A) - 8 Digital Inputs, 5 Output Relays, 4 4-20 mA Analog Output, URTD Interface
(0) - 5A/1A phase and ground CTs, Power Supply Range: 19-300 Vdc, 40-250 Vac
(B) - Modbus/DNP3 RTU (RS-485)
(A) - Without Conformal Coating
(1) - Projection Panel Mount

Table 1.  Catalog Ordering Information for EMR-4000 Eaton Motor Relay
EMR-4000 Eaton Motor Relay Removable Terminals
EMR-4000-2 A 0 B A 1
Choose from the following options.
Hardware Option 1
8 DI, 5 Outputs, 4AO, Removable Terminals, Zone Interlocking, URTD interface, IRIG-B A

Hardware Option 2
Phase Current 5A/1A, Ground Current 5A/1A, Power Supply Range: 19-300 Vdc, 40-250 Vac 0 (Zero)
Phase Current 5A/1A Sensitive Ground Current, 0.5A/0.1A, Power Supply Range: 19-300 Vdc, 40-250 Vac 1

Communication Options
Modbus/DNP3 RTU over RS485 B
Modbus/DNP3 TCP over Ethernet RJ45 C
Profibus-DP over Fiber Optic ST D
Profibus-DP over D-SUB / RS48 E
Modbus RTU or DNP3 RTU over Fiber Optic ST F
Modbus/DNP3 RTU over D-SUB / RS485 G
IEC61850/Modbus/DNP3 TCP over Ethernet RJ45 H
Modbus/DNP3 RTU over RS485 or Modbus/DNP3 TCP over Ethernet RJ45 I
IEC61850/Modbus/DNP3 TCP over LC duplex FO Ethernet K
Modbus/DNP3 TCP over LC duplex FO Ethernet L

Conformal Coating Options


None A
Conformal Coated Circuit Boards B

Mounting Options
Standard Mount 0 (Zero)
Projection Panel Mount 1

20 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Table 2.  Standard Accessories EMR-4000


Catalogue Number Description
URTDII-01 UNVL RTD Mod with Modbus-RTU 48-240VAC/48-250VDC
URTDII-02 UNVL RTD Mod with Modbus-RTU 24-48VDC
MPFO-25 25 M FIBER OPTIC CABLE FOR RELAYS/URTD COMMUNICATIONS
MPFO-1 1 M FIBER OPTIC CABLE FOR RELAYS/URTD COMMUNICATIONS
MPFO-10 1 OM FIBER OPTIC CABLE FOR RELAYS/URTD COMMUNICATIONS
MPFO-5 5 M FIBER OPTIC CABLE FOR RELAYS/URTD COMMUNICATIONS
ESERIESUSBCBL E-Series mini USB cable 6 foot

EATON www.eaton.com 21
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

Notes:

22 EATON www.eaton.com
EMR-4000 Technical Data TD02600004E
Motor Protection Relay Effective May 2016

Notes:

EATON www.eaton.com 23
Technical Data TD02600004E EMR-4000
Effective May 2016 Motor Protection Relay

These technical data materials are published solely for information


purposes and should not be considered all-inclusive. If further infor-
mation is required, you should consult an authorized Eaton sales
representative.
The sale of the product shown in this literature is subject to the
terms and conditions outlined in appropriate Eaton selling policies
or other contractual agreement between the parties. This literature
is not intended to and does not enlarge or add to any such contract.
The sole source governing the rights and remedies of any purchaser
of this equipment is the contract between the purchaser and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS
CONTAINED HEREIN. In no event will Eaton be responsible to the
purchaser or user in contract, in tort (including negligence), strict
liability or otherwise for any special, indirect, incidental or conse-
quential damage or loss whatsoever, including but not limited to
damage or loss of use of equipment, plant or power system, cost
of capital, loss of power, additional expenses in the use of existing
power facilities, or claims against the purchaser or user by its cus-
tomers resulting from the use of the information, recommendations
and description contained herein.

Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com

© 2016 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD02600004E / TBG000852 All other trademarks are property of their
May 2016 respective owners.

You might also like