TRANSMISSION CORPORATION OF TELANGANA LIMITED

From, To,
Divisional Engineer, The Superintending Engineer,
MRT&Transformers/Metro-East OMC/Metro – East,
220KV SS Moulali, II Floor, 220KV GIS SS OU,
Hyderabad. Tarnaka, Hyderabad.

Lr. No.DE/MRT&T/F/Metro-East/F:Technical /D.No. 104/19, Dt. 06.07.2019


Sir,
Sub:- MRT & T/F./Metro East Division - Revision of Re-trip timings for LBB (Local Breaker
Backup) function in 220kV and 400kV network from 50msec to 100msec - Compliance
Report - Submitted - Reg

Ref:- Lr.No.CE/PS/SE/PS/DE/SP-1/121/F./D.No.131/19,Dated.01.06.2019.
*****

Vide reference cited, it was requested to adopt the re-trip time of 100msec and Back trip
time of 200msec for LBB in Bus bar protection schemes for all existing and upcoming 220kV and
400kV elements in TSTRANSCO network and requested to submit the report compliance.

Inview of the above, adopted the above revised settings for all 220kV and 400kV elements
in Metro-east circle.

Submitted for favor of information and taking further necessary action please.

Yours Faithfully,
Sd/-
Divisional Engineer,
MRT&Transformers/Metro-East