NI 9208E
16-Channel, ±20 mA, 24-Bit Analog Input Module
This document describes how to use the National Instruments 9208E
and includes dimensions, pin assignments, and specifications for the
NI 9208E. Visit ni.com/info and enter rdsoftwareversion to
determine which software you need for the modules you are using.
For information about installing, configuring, and programming the
system, refer to the system documentation. Visit ni.com/info and
enter cseriesdoc for information about C Series documentation.
73.4 (2.89)
0.0 (0.00)
58.4 (2.30)
66.0 (2.60)
26.7 (1.05)
0.0 (0.00)
1 AI0
Vsup 20
2 AI1
Vsup 21
3 AI2
Vsup 22
4 AI3
Vsup 23
5 AI4
Vsup 24
6 AI5
Vsup 25
7 AI6
Vsup 26
8 AI7
Vsup 27
9 COM
COM 28
10 COM
COM 29
11 AI8
Vsup 30
12 AI9
Vsup 31
13 AI10
Vsup 32
14 AI11
Vsup 33
15 AI12
Vsup 34
16 AI13
Vsup 35
17 AI14
Vsup 36
18 AI15
Vsup 37
19 Vsup
Vsup
AI0 Isolated
MUX Amp
ADC
AI15
R R
COM
COM
NI 9208E
2A
Max Vsup
+
External
Power
Supply – COM
Vsup
Loop-Powered
Current
Transducer AI0
COM
NI 9208E
Vsup
Three-Wire + AI0
Current OUT
Transducer –
COM
NI 9208E
Input Characteristics
Number of channels.......................... 16 analog input channels
ADC resolution................................. 24 bits
Type of ADC..................................... Delta-Sigma
Sampling mode ................................. Scanned
Input range
Minimum.................................... ±21.5 mA
Typical ........................................ ±22 mA
Conversion time (per channel)
High-resolution mode................. 52 ms
High-speed mode........................ 2 ms
Overvoltage protection,
channel-to-COM ............................... ±30 V max on one channel at
a time
Input noise
High-resolution mode................. 50 nArms
High-speed mode........................ 200 nArms
Stability
Gain drift .................................... 20 ppm/°C
Offset drift .................................. 62 nA/°C
Power Requirements
Power consumption from chassis
Active mode ............................... 282 mW max
Sleep mode ................................. 25 μW max
Thermal dissipation (at 85 °C)
Active mode ............................... 1.29 W max
Sleep mode ................................. 0.72 W max
Safety
Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM .............................. ±30 V
Isolation
Channel-to-channel .................... None
Channel-to-earth ground
Continuous ........................... 60 VDC,
Measurement Category I,
(Double insulation)
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more
information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... –40 to 85 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... –40 to 85 °C
Operating humidity
(IEC 60068-2-56).............................. 10 to 90% RH,
noncondensing
Environmental Management
National Instruments is committed to designing and manufacturing
products in an environmentally responsible manner. NI recognizes
that eliminating certain hazardous substances from our products is
beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the
Environment Web page at ni.com/environment. This page
contains the environmental regulations and directives with which
NI complies, as well as other environmental information not
included in this document.
Calibration
You can obtain the calibration certificate and information about
calibration services for the NI 9208E at ni.com/calibration.
Calibration interval ........................... 2 years
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products/technology, refer to the appropriate location: Help»Patents
in your software, the patents.txt file on your media, or the National Instruments Patent Notice
at ni.com/patents.
372948A-01 Sep09