Professional Documents
Culture Documents
Maximum Constant Boost Control of Z Source Inverter
Maximum Constant Boost Control of Z Source Inverter
Z-Source Inverter
Miaosen Shen1, Jin Wang1, Alan Joseph1, Fang Z. Peng1, Leon M. Tolbert2, and Donald J. Adams3
1
Michigan State University
Department of Electrical and Computer Engineering
2120 Engineering Building, East Lansing, MI 48824
Phone: 517-432-3331, Fax: 517-353-1980, Email: fzpeng@egr.msu.edu
2
University of Tennessee, 3 Oak Ridge National Laboratory
Abstract: This paper proposes two maximum constant boost Ⅱ. VOLTAGE BOOST, STRESS AND CURRENT RIPPLE
control methods for the Z-source inverter, which can obtain
maximum voltage gain at any given modulation index without As described in [1], the voltage gain of the Z-source
producing any low-frequency ripple that is related to the output inverter can be expressed as
frequency. Thus the Z-network requirement will be independent
of the output frequency and determined only by the switching Vˆo
frequency. The relationship of voltage gain to modulation index is = MB , (1)
Vdc / 2
analyzed in detail and verified by simulation and experiment.
Keywords- Z-source inverter; PWM; Voltage boost; where Vˆo is the output peak phase voltage, Vdc is the input dc
voltage, M is the modulation index, and B is the boost factor.
B is determined by
Ⅰ. INTRODUCTION
1
In a traditional voltage source inverter, the two switches B= , (2)
T
of the same phase leg can never be gated on at the same time 1− 2 0
because doing so would cause a short circuit (shoot-through) T
to occur that would destroy the inverter. In addition, the where T0 is the shoot-through time interval over a switching
maximum output voltage obtainable can never exceed the dc T
bus voltage. These limitations can be overcome by the new cycle T, or 0 = D0 is the shoot-through duty ratio.
T
Z-source inverter [1], shown in Fig. 1, that uses an impedance
network (Z-network) to replace the traditional dc link. The In [1], a simple boost control method was used to control
Z-source inverter advantageously utilizes the shoot-through the shoot-through duty ratio. The Z-source inverter
states to boost the dc bus voltage by gating on both the upper maintains the six active states unchanged as in traditional
and lower switches of a phase leg. Therefore, the Z-source carrier-based pulse width modulation (PWM) control. In this
inverter can buck and boost voltage to a desired output voltage case, the shoot-through time per switching cycle is constant,
that is greater than the available dc bus voltage. In addition, which means the boost factor is a constant. Therefore, under
the reliability of the inverter is greatly improved because the this condition, the dc inductor current and capacitor voltage
shoot-through can no longer destroy the circuit. Thus it have no ripples that are associated with the output frequency.
provides a low-cost, reliable, and highly efficient single-stage As has been examined in [2], for this simple boost control, the
structure for buck and boost power conversion. obtainable shoot-through duty ratio decreases with the
increase of M, and the resulting voltage stress across the
The main circuit of the Z-source inverter and its
devices is fairly high. To obtain the maximum voltage boost,
operating principle have been described in [1]. Maximum
[2] presents the maximum boost control method as shown in
boost control is presented in [2]. In this paper, we will present
Fig. 2, which shoots through all zero-voltage vectors entirely.
two control methods to achieve maximum voltage boost/gain
Based on the map in Fig. 2, the shoot-through duty cycle D0
while maintaining a constant boost viewed from the Z-source
varies at six times the output frequency. As can be seen from
network and producing no low-frequency ripple associated
[2], the voltage boost is inversely related to the shoot-though
with the output frequency. This maximum constant boost
duty ratio; therefore, the ripple in shoot-through duty ratio will
control can greatly reduce the L and C requirements of the
result in ripple in the current through the inductor, as well as
Z-network. The relationship of voltage boost and modulation
in the voltage across the capacitor. When the output frequency
index, as well as the voltage stress on the devices, will be
is low, the inductor current ripple becomes significant, and a
investigated.
large inductor is required.
0
0.5 0.6 0.7 0.8 0.9 1 Vp
Modulation index (M) Vc
0 π 2π
3 3
For the first half-period, (0, π/3) in Fig. 4, the upper
and lower envelope curves can be expressed by Eqs. (8) and
(9), respectively. Vn
Sap
2π π
V p1 = 3M + sin(θ − )M 0 <θ < . (8) Sbp
3 3 Scp
San
2π π
Sbn
3 3
Fig. 6 Sketch map of constant boost control with third harmonic
For the second half-period (π/3, 2π/3), the curves meet injection
Eqs. (10) and (11), respectively.
π 2π The shoot-through duty ratio can be calculated by
V p 2 = sin(θ ) M <θ < . (10)
3 3
T0 2 − 3M 3M
π 2π = = 1− . (15)
Vn 2 = sin(θ ) M − 3M <θ < . (11) T 2 2
3 3
As we can see, it is identical to the previous maximum
Obviously, the distance between these two curves is constant boost control method. Therefore, the voltage gain can
always constant, that is, 3M . Therefore the shoot-through also be calculated by the same equation. The difference is that
duty ratio is constant and can be expressed as 2
in this control method, the range of M is increased to 3.
3
T0 2 − 3M 3M
= = 1− . (12) The voltage gain versus M is shown in Fig.7. The voltage gain
T 2 2 can be varied from infinity to zero smoothly by increasing M
16 4
14 3
2
12
Voltage gain (MB)
1
10
0
8 1 2 3 4 5
Voltage gain
6
2
Ⅴ. SIMULATION AND EXPERIMENTAL RESULTS
0
0 0 .2 0 .4 0 .6 0 .8 1 1 .2
M o d u la tio n in d e x (M ) To verify the validity of the control strategies, simulation
and experiments were conducted with the following
Fig. 7 Vac/0.5V0 versus M parameters: Z-source network: L1 = L2 = 1 mH (60 Hz
inductor), C1 = C2 = 1,300 µF; switching frequency: 10 kHz;
output power: 6 kW. The simulation results with the
Ⅳ. VOLTAGE STRESS COMPARISON modulation index M = 0.812, M = 1, and M = 1.1 with third
harmonic injection are shown in Figs. 9 through 11,
As defined in [2], voltage gain G is
respectively, where the input voltages are 145, 250, and 250 V,
M respectively. Table Ⅰ lists the theoretical voltage stress and
G = MB = . (16)
3M − 1 output line-to-line rms voltage based on the previous analysis.
Table Ⅰ. Theoretical voltage stress and output voltage under different
We have conditions
G Operating Voltage stress Output voltage VL-L
M= . (17)
3G − 1 condition
(V) (V)
The voltage across the devices, Vs, can be expressed as M = 0.812, 357 177
Vs = BVdc = ( 3G − 1)Vdc . (18) Vdc = 145V
The voltage stresses across the devices with different control M = 1, 342 209
methods are shown in Fig. 8. Vdc= 250 V
As can be seen from Fig. 8, the proposed method will M = 1.1, 276 186
cause a slightly higher voltage stress across the devices than
the maximum control method, but a much lower voltage stress Vdc = 250 V
than the simple control method. However, since the proposed
method eliminates line frequency related ripple, the passive
components in the Z-network will be smaller, which will be The simulation results in Figs. 9–11 are consistent with
advantageous in many applications. the theoretical analysis, which verifies the previous analysis
and the control concept.
(V)
(V)
145.0 250.0
245.0
(V)
(V)
200.0 200.0
(A)
(A)
40.0
(V)
(V)
0.0 0.0
-200.0 -200.0
-400.0 -400.0
0.25 0.26 0.27 0.28 0.29 0.15 0.16 0.17 0.18 0.19
t(s) t(s)
Fig. 9 Simulation results with M = 0.8 Fig. 11 Simulation results with M = 1.1
(V) : t(s)
260.0 Input
Voltage
255.0 V dc Vdc (200 V/div)
(V)
250.0
245.0
200.0
IL1 (20 A/div)
0.0 (A) : t(s)
Inductor
vLab (200 V/div)
Current
40.0 IL
(A)
0.0
-200.0
Vdc (200 V/div)
-400.0
0.15 0.16 0.17
t(s)
0.18 0.19
VPN (200 V/div)
Fig. 10 Simulation results with M = 1
The experimental results with the same operating IL1 (20 A/div)
conditions are shown in Figs. 12, 13, and 14, respectively.
Based on these results, the experimental results agree with vLab (200 V/div)
the analysis and simulation results very well. The validity of the
control method is verified.
Fig. 14 Experimental results with Vdc = 250V and M = 1.1 [4] Bimal K. Bose, Power Electronics and Variable Frequency Drives, Upper
Saddle River, NJ: Prentice-Hall PTR, 2002.
[5] P. T. Krein, Elements of Power Electronics, London, UK: Oxford Univ.
Press, 1998.
Ⅵ. CONCLUSION
[6] W. Leonard, Control of Electric Drives, New York: Springer-Verlag,
Two control methods to obtain maximum voltage gain 1985
with constant boost have been presented that achieve
maximum voltage boost without introducing any
low-frequency ripple related to the output frequency. The