Tr Rating 60 MVA

HV Side Voltage Ratio 132 kV


HV Side CT Ratio 300 A
LV1 Side VT Ratio 13.8 kV
LV1 Side CT Ratio 3000 A

HV side
Full Load Current on HV side 262.44 A
Matching Factor - Kma1 1.1431 0.874799 261
Differential 0.2058 0.18 Injected current

LV1 Side
Full Load Current on LV1 Side 2510.3 A
Matching Factor - Kma2 1.1951 0.836764
0.3466 0.29 Injected Current

BIAS Char
Idiff > 0.35
m1 0.3
m2 1
IRm2 4

First Slope
I1 -Winding A Injected Current 3.65 A
I2 -Winding B Injected Current 2.4 A
Bias Current
Ibias =( I1xKma1 + I2 x Kma2)/2 = (3.65*1.143+2.4*1.195)/2
3.52
Actual - Differential
Idiff=I1xKma1-I2xkma2 = 3.65*1.143-2.4*1.195
1.30
Calculated - Differential
Idiff=m1xIbias+Idiff>(1-0.5m1) = 0.3*3.52+0.35*(1-0.5*0.3)
1.35

Second Slope
I1 -Winding A Injected Current 6.12 A
I2 -Winding B Injected Current 3.25 A
Bias Current
Ibias =( I1xKma1 + I2 x Kma2)/2 = (6.12*1.143+3.25*1.195)/2
5.44 A
Actual - Differential
Idiff=I1xKma1-I2xkma2 = 6.12*1.143-3.25*1.195
3.11 A
Calculated - Differential
Idiff=m2xIbias+Idiff>(1-0.5m1)+IRm2(m1-m2) = 1*5.44+0.35*(1-0.5*0.3)+4*(0.3-1)
2.94 A