You are on page 1of 5

Dynamic Ramp Rate Control for Voltage Regulation in

Distribution Systems with High Penetration


Photovoltaic Power Generations
Manohar Chamana, Farbod Jahanbakhsh, Badrul H. Chowdhury, Babak Parkhideh

Abstract— Multiple voltage regulating devices, such as on-load A Battery Energy Storage System (BESS) connected in
tap changer (OLTC), step voltage regulators (SVRs), switching parallel with the PV could be an ideal solution for this purpose
capacitors banks work in tandem with each other to regulate as it possesses sub-second response capability that can be
voltage in the distribution network. These conventional devices
utilized to offset the sudden changes in PV output. Although
are based on volt/var optimization strategies that work in a time
coordinated method. However, in case of distribution systems continuous operation of the BESS is not economically
with Photovoltaic (PV) generations, a dynamically responsive feasible, it is still advantageous to use them for ramp-rate
voltage regulating device is required. Case studies are control because of the reduced energy requirement. Batteries
performed investigating voltage regulation at the PV bus during with deep-discharge cycles and high power capacity (the rate
ramp up/down case. An alternate method using an energy at which energy can be transferred into or out of the device)
storage device to regulate the target PV bus voltage during ramp
are required for this purpose. By utilizing local regulation
up/down of PV power is proposed. A novel ramp rate control
algorithm based on the current state of charge is also discussed. services, there would be a lower requirement for ancillary
A benchmark MV distribution network model is developed and services from conventional generation. By properly
simulated in PSCAD/EMTD environment and the results coordinating with the local conventional voltage regulating
validate the proposed coordinated voltage control strategy. devices the wear and tear due mechanical switching can be
Index Terms—Photovoltaic, battery energy storage, ramp reduced [2]. A BESS would be charged during ramp-up case
up/down, voltage regulation, dynamic var compensator
and discharged during ramp-down case which would be
I. INTRODUCTION economically beneficial as compared to the costly ancillary
services provided by the conventional generators [3].
The injection of megawatt (MW) scale renewable power
generations into the medium-voltage grid poses various In this paper, the interplay between a distribution system
stability issues in the distribution system. With high
with high penetration solar PV and voltage regulation devices
penetration distributed solar photovoltaic (PV) power plants
is investigated. The issue of response and coordination among
connected to a strong grid, there are usually fewer issues with
frequency stability and more issues with voltage stability the existing devices are discussed via simulations. The
locally. The stochastic nature of PV plant output needs to be motivation behind this study is to suggest a superior solution
countered with the help of regulation devices in the for PV-related voltage regulation issues as compared to the
distribution system. Most of the present voltage regulating existing solution. By using a storage device, such as a battery
devices in the distribution system are static in nature and take with sub-second response capability, the abrupt change in
several minutes to respond to the fast rise and drop in power photovoltaic power may be compensated. The advantage of
which may result from the variability in the solar insolation. using a battery to slow down the increment in the PV
There is a requirement for distribution stations to collect sub- generation with time is to allow the voltage regulating devices.
minute (1 to 5 sec) data resolutions for load and solar
insolation in various regions to co-ordinate the voltage II. RAMP RATE CONTROL
regulation devices. PV plants are conventionally operated at
A novel algorithm for ramp rate control based on the BESS
unity power factor to comply with the requirement of no
State of Charge (SoC) is designed to reduce the impact on
active regulation of the voltage at the point of common
coupling as detailed in IEEE standard 1547-2003: Standard local voltages due to PV rise/drop. The purpose of the BESS is
for Interconnecting Distributed Resources with Electric to provide power to the PV plant in the ramp-down mode or
Power Systems [1]. absorb power from the PV plant in the ramp-up mode. In other
words, by changing the ramp rate of PV power variations, the
BESS prevents sudden changes in solar power injection levels,
M. Chamana, B.H. Chowdhury and B. Parkhideh are with the which can make the system operation difficult for distributed
Department of Electrical and Computer Engineering, University of North generators when the PV penetration is high. The BESS, as a
Carolina, Charlotte, USA (e-mails: mchamana@uncc.edu, power smoothing device, will provide back-up power to the
b.h.chowdhury@ieee.org, BParkhideh@uncc.edu, Imazhari@uncc.edu).
F. Jahanbakhsh is a Senior Advisor, Power System Consultant at Quanta grid while the generators ramp up and down – reducing the
Technology, Raleigh, USA (e-mails: Farbod@Quanta-Technology.com) long term wear and tear of the static voltage regulating

978-1-4799-6415-4/14/$31.00 ©2014 IEEE


devices. In order to do that, the change in power with respect
to time becomes an important factor. If a decrease or increase ݀‫ܴܦ‬ ݇ ௗ௥௢௣ ͳ ݀ܲ௉௏
in power with time beyond the limits is detected, the BESS  ൌ െ ሺͷሻ
݀‫ݐ‬ ᐭ௜௡௩ ܸ஻ ܸ஻ ݀‫ݐ‬
would have to respond to the change much quicker. A sudden
decrease in PV power is associated with a negative slope; Where ݇ ௗ௥௢௣ is the slope of desired rate of change of
therefore the BESS needs to supply ramped power with a injected power with respect to time. ݇ ௗ௥௢௣ is the interpolation
positive slope to reduce the change in power with time which
value between ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ ܽ݊݀݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖ . ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ is
ultimately smoothens the injected power to the grid [4, 5]. The
the desired injected power slope at 90% SoC which is the
injected power from the PV/BESS system is given as:
maximum limit of the battery while ݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖ is the
௦௠௢௢௧௛ desired injected power slope at 10% SoC which is the
 ܲ௜௡௝ ൌ ᐭ௜௡௩ ሺܲ௉௏ ൅ ܲ஻ாௌௌ ሻ െ ܲ௅ ሺͳሻ
minimum limit of the battery. ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ could be a zero
slope line in order to inject power without any change with
The injected power at the inverter terminals of the
time, while ݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖ could be the ݇ ௟௜௠௜௧ Ǥ
PV/BESS system with charge/discharge rate is
Similarly for the ramp up case, if the rate of change of
ௗ௉ುೇ
ܲ௜௡௝ ൌ െܲ௅ ൅ ᐭ௜௡௩ ሺܲ௉௏ േ ‫ܫ‬஻ ‫ܸ כ‬஻ ሻሺʹሻ increase in power, ቚ ቚ > |݇ ௟௜௠௜௧ ȁ, the equation for charging
ௗ௧
rate is given as below:
Where ܲ௜௡௝ is the injected power to the grid from the
PV/BESS system, ܲ௅ is the load at the system bus, ܲ௉௏ is the ݀‫ܴܥ‬ ͳ ݀ܲ௉௏ ݇ ௥௜௦௘
 ൌ െ ሺ͸ሻ
power from the PV modules, ܸ஻ is the voltage at the battery ݀‫ݐ‬ ܸ஻ ݀‫ݐ‬ ᐭ௜௡௩ ܸ஻
terminals, ‫ܫ‬஻ is the battery current which could either be the
charging rate (CR) or discharging rate (DR) and ᐭ௜௡௩ is the Where ݇ ௥௜௦௘ is the slope of desired rate of change of
efficiency of the inverter. injected power with respect to time. ݇ ௥௜௦௘ is the interpolation
By assuming that the change in load power, ܲ௅ is not value between ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ ܽ݊݀݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖ . ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ is
significant for small time instants, the change in injected the desired injected power slope at 90% state of charge (SoC)
power with time can be measured by differentiating with which is the maximum limit of the battery while ݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖
respect to time is the desired injected power slope at 10% state of charge
 (SoC) which is the minimum limit of the battery.
݀ܲ௜௡௝ ݀ܲ௉௏ ݀‫ܫ‬஻ ݇ ௗ௥௢௣ǡଽ଴Ψ௦௢௖ could be ݇ ௟௜௠௜௧ while ݇ ௗ௥௢௣ǡଵ଴Ψ௦௢௖ could a zero
 ൌ ᐭ௜௡௩ ൬ ൅ ‫ܸ כ‬஻ ൰ሺ͵ሻ slope line in order to inject power without any change with
݀‫ݐ‬ ݀‫ݐ‬ ݀‫ݐ‬
time. The overall design of the ramp rate control is shown in
ௗூ Figure 2. These ramp rate controls are initiated every time the
Where ಳ is either positive or negative based on charging
ௗ௧ PV ramp rise /drop is steep. As a result the battery might be
or discharging command. The rate of PV power change with charged/discharged to any level abruptly. As the current SoC
time step is calculated by: indicates the capability of a battery to charge/discharge
further, the ramp commands change accordingly.
݀ܲ௉௏ ሺ‫ݐ‬ሻ ܲ௉௏ ሺ‫ݐ‬ሻ െ ܲ௉௏ ሺ‫ ݐ‬െ ο‫ݐ‬ሻ
 ൌ ሺͶሻ
݀‫ݐ‬ ο‫ݐ‬
dPPV No
! k limit PP V Pinj
dt
The ramp down and up windows for each time step is
shown in Figure 1. A slope ݇ ௟௜௠௜௧ is also shown in the window
Yes

which indicates the limit of ramp down/up. dPPV Yes


!0
No dt
Ramp Down Ramp Up
Window Window dDR k drop

1 dPPV dCR 1 dPPV k drop
dt KinvVB VB dt

k limit dt VB dt KinvVB
dPPV
dPPV Yes
ΔP ΔP dt Yes
dt
dPPV dPPV
k limit
! k lim it ! k lim it
dt dt
ΔT ΔT
No No

Figure 1. Sliding window with width ο‫ݐ‬ Stop Stop


Charging
Discharging

ௗ௉ುೇ
For a discharging rate command when ቚ ቚ ൐|݇ ௟௜௠௜௧ ȁthe
ௗ௧ Figure 2. Ramp rate control algorithm
equation can be rewritten as:
The required ramp rate usually depends on the system
control delays but always limited to the battery capacity.
Ideally, the size of the battery can be calculated based on the 0.4 Miles POI
PV 2000 kW
equation shown below [6]: 1.07 Miles Equivalent
Voltage for 138 kV
Regulator 2
system
ͳ 0.55 Miles
ο‫ ܧ‬ൌ ܲ ܶ ሺ͹ሻ
ʹ ௉௏ǡ௠௔௫ ௥௔௠௣ǡ௠௔௫

1.3 Miles
Voltgae Substation
Regulator 3
Voltgae
Feeder 138/12 kV
Regulator 1 source 15 MVA
Where ܲ௉௏ǡ௠௔௫ is the rated PV output, ܶ௥௔௠௣ǡ௠௔௫ is the
1.95 Miles
1.05 Miles 4.01 Miles 1.68 Miles
G
maximum desired time taken to either drop from ܲ௉௏ǡ௠௔௫ to 0 Mid point

or rise from 0 to ܲ௉௏ǡ௠௔௫ . The slope of such a ramp is


associated with ramp limit ȁ݇ ௟௜௠௜௧ ȁ.In this case the maximum
௉ುೇǡ೘ೌೣ
Figure 3. MV distribution feeder with PV as DG
ramp rate limit is ฬ ฬ. ο‫ ܧ‬is the maximum
்ೝೌ೘೛ǡ೘ೌೣ
discharge/charge energy which can be used to size the battery. IV. RESULTS
For example if ܲ௉௏ǡ௠௔௫ = 2 MW and ܶ௥௔௠௣ǡ௠௔௫ = 12 min, the During sunrise, the solar irradiance increases in a ramp
ideal battery can be sized to 0.2 MWhr. fashion from t=4 min, and within a few minutes, reaches its
In this paper the PV and BESS are connected in parallel to nominal value as shown in Figure 4. The irradiance value
the DC link capacitor of the three phase inverter. The PV is drops to a low value suddenly at t=16 min. The solar radiation
connected through a boost converter and the BESS is profile is from North California (a cloudy day) in the summer.
connected through a dc-dc buck-boost converter, so that when
it is charging, converter acts in the buck mode, and when
discharging it acts in the boost mode. There are three separate
controllers for the three converters [7].

III. DISTRIBUTION FEEDER


The system used for the simulation purpose was a medium
voltage (MV) distribution substation feeder belonging to
Pacific Gas and Electric (P G & E) located in California, with
regular voltage regulation devices that are mostly static in Figure 4. Solar Irradiance during sunrise
nature. The system is shown in Figure 3. The feeder is at 12
kV base. The transformer is rated at 15 MVA. At the feeder A. Without Ramp Rate Control
side, an on-load tap changing (OLTC) transformer is used. During the increase in solar irradiance, the active power
Step voltage regulators (SVR) are located at various locations from the PV array increases as expected and the reactive
on the distribution system. The highest stress would be on power output remains near zero. As the PV power increases,
voltage regulators SVR 1 and 3 which are directly in radial the active power flow through the feeder decreases since the
line with the PV. These static devices take around 1 ~ 1.5 min local load is fed by the PV array instead of the grid.
to respond to a voltage violation case initially and 15 sec delay Simulation results of PV power flows are shown in Figure
for the next steps. A switching capacitor, rated at 1.2 MVAR, 5(a). As the PV power keeps increasing, at around time t = 5.1
is used at a specific location on the feeder. A Dynamic Var min, the voltage hits the upper limit of 1.05 pu as shown in
Compensator (DVC) is utilized nearer to the PV location that Figure 5(b) which causes the SVR 1 and 3 to change its tap
behaves similar to a STATCOM [8]. There is some distance ratios to a lower value. The voltage at the PV terminals
between the DVC and PV which would create different reaches around 1.07 p.u.
voltage profiles. It takes around 3 sec for a DVC to respond to
any voltage violation case. The DVC voltage is regulated at (a)
1.019 p.u, with a bandwidth set at +/- 0.002 p.u. The DVC is
around 1.47 miles away from the PV point of interconnection
(POI). A PV is connected far away from the feeder and
operated with unity power factor. In the first case study the
PV is connected directly at the POI without considering a
battery and hence without any ramp rate control. In the
second case study the battery is connected inside the PV to
perform the ramp rate control as mentioned in the previous
section. Both charging and discharging processes would be
discussed in the ramp rate control process.
(b) (b)

Figure 7. (a) Phase tap ratios in p.u for SVR 1 (b) Phase tap ratios in p.u for
SVR 3.
Figure 5. (a) PV active and reactive power, (b) PV node rms voltage
B. With Ramp Rate Control
The DVC, as mentioned earlier, is the closest voltage
In this case, the change in the solar irradiance is the same
regulating device with the fastest response time. The DVC
as in the previous section for the case with no ramp rate
operates in order to reduce the reactive power injection when control. After the ramp-rate control is applied to the PV, the
the PV active power increases. The reactive power absorbed rise in PV power at the terminals takes longer to reach its
by the DVC during this operation is shown in Figure 6(a). The rated value. Similarly, when the irradiance drops at 16 min,
DVC voltage, VDVC is shown in Figure 6(b). the drop in PV terminal power is delayed. Figure 8(a) shows
the power flow at the PV terminals. Due to the delayed ramp
(a) rate increase, the battery charges or absorbs power, whereas
the delayed ramp rate decrease leads to the battery
discharging or releasing power, which can be seen in the
Figure 8(b). The state of charge during the simulation period
is shown in Figure 8(c). As can be seen from Figure 8(d), the
voltage at the PV bus, VPV rises slowly, which gives time for
the SVR 1 and 3 to respond with its delay settings. The ramp
rate is 0.166 MW/min and the results show negligible voltage
violation (0.005 pu) in the worst case.
(b)
(a)

Figure 6. (a) DVC Reactive Power Output, (b) DVC node rms voltage
(b)
The tap setting change for SVR 1 is shown in Figure 7(a)
and for SVR 3 in Figure 7(b). It can be seen that as the PV
output increases in the time frame, the voltage at the nearby
buses increases, not giving enough time for the SVRs to
respond to the change.

(a)

(c)
(d) V. CONCLUSION
A case study was performed on an actual MV distribution
feeder with conventional voltage regulating devices. A
dynamic compensator was also installed near the PV but
proved unsatisfactory as reactive control was not enough. In
many cases, like the example in this paper, ramp rate control
with BESS would be an ideal method to mitigate a PV plant’s
Figure 8. (a) PV active and reactive power, (b) Battery power, (c) Battery impact on voltage violations. Slowing down the rate of change
SoC and (d) PV node rms voltage
in a PV plant’s MW output may let other voltage controlled
equipment in the system have enough time to react properly,
The DVC responds to the voltage rise by changing its
and also save energy in comparison to other similar mitigation
reactive power based on the settings. Comparitively the DVC
methods There would be less wear and tear in the static
delays its reavtive support due to the delay in PV output. The
voltage regulating devices as they would not have to respond
change in the reactive power is shown in Figure 9(a). Figure
to fast increase in voltage which cause an increase in the tap
9(b) shows the voltage profile at the DVC terminals.
changing steps. Ideally, ramp rate control would be done by
(a)
fast battery storage inside of the PV system. Ramp up and
down control with the help of a battery can prove to be
beneficial as a result of the transfer of power from one period
to another. The advantage of ramp rate control is also on
reducing the range of voltage variation as well as improving
the maximum and minimum voltages.

REFERENCES
(b)

[1] F. Katiraei and J.R. Agüero, "Solar PV Integration Challenges," Power


and Energy Magazine, IEEE , vol.9, no.3, pp.62,71, May-June 2011.
[2] Liu Xiaohu, A. Aichhorn, Liu Liming, Li Hui, "Coordinated Control of
Distributed Energy Storage System With Tap Changer Transformers
for Voltage Rise Mitigation Under High Photovoltaic Penetration, " ,
IEEE Transactions on Smart Grid, vol.3, no.2, pp.897,906, June 2012.
[3] V. Gevorgian and D. Corbus, “Ramping Performance Analysis of the
Figure 9. (a) DVC Reactive Power Output, (b) DVC node rms voltage Kahuku Wind-Energy Battery Storage System,”
http://www.nrel.gov/docs/fy14osti/59003.pdf
The tap setting changes for SVR 1 and SVR 3 are shown in [4] I. Mazhari, M. Chamana, B. Parkhideh and B. H. Chowdhury,
“Distributed PV- Battery Architectures with Reconfigurable Power
Figures 10(a) and 10(b) respectively. Due to the delay in the Conversion Units”, Proc. (to appear) Twenty-Ninth Annual
rise in power, the voltage regulating devices were able to IEEE Applied Power Electronics Conference and Exposition (APEC),
respond to the voltage increase prior to the voltage violation. 2014, 16-20 March 2014.
[5] X. Li, D. Hui, X. Lai, "Battery Energy Storage Station (BESS)-Based
Smoothing Control of Photovoltaic (PV) and Wind Power Generation
(a) Fluctuations," Sustainable Energy, IEEE Transactions on , vol.4, no.2,
pp.464,473, April 2013.
[6] N. Kakimoto, H. Satoh, S. Takayama and K. Nakamura, "Ramp-Rate
Control of Photovoltaic Generator With Electric Double-Layer
Capacitor," , IEEE Transactions on Energy Conversion, vol.24, no.2,
pp.465,473, June 2009.
[7] R. Bhatt, B. Chowdhury, "Grid frequency and voltage support using PV
systems with energy storage," North American Power Symposium
(NAPS), 2011 , vol., no., pp.1,6, 4-6 Aug. 2011
(b)
[8] A. Moawwad, V. Khadkikar and J.L. Kirtley, "Photovoltaic power
plant as FACTS devices in multi-feeder systems," IECON 2011 - 37th
Annual Conference on IEEE Industrial Electronics Society , vol., no.,
pp.918,923, 7-10 Nov. 2011.

Figure 10. (a) Phase tap ratios in p.u for SVR 1 (b) Phase tap ratios in p.u for
SVR 3.

You might also like