Professional Documents
Culture Documents
Abstract- Transformers are an important part of the electrical disruption in transformer operation and power supply
power system network, therefore, its fault detection is vital. Off- interruption. The investigation of condition monitoring and
line methods are commonly used for their fault detection. These evaluation techniques of power transformers has become a
methods have associated costs derived from the necessity of subject of interest for many researchers, e.g. [9]. Improving
taking the transformer out of service. The application of on-line
understanding of the relationship between transformer fault
methods reduces the expected costs and the possibility of
unpredicted failures. In the present study, off-line and on-line types and their indicators will help asset managers to
methods are applied to the detection of short circuits in maintain equipment. In this study, an off-line and an on-line
transformers, demonstrating the possibility of moving from off- method for detecting and identifying internal faults are
line to on-line methods. Short circuits between sections in a investigated. SFRA is applied as an off-line method to
transformer winding, between winding and core and between investigate the indicators of short-circuit conditions that may
windings have been considered. PSPICE software is used to be expected to occur between sections and between winding
simulate the transformer for both detection methods. A to core. The method correlates the frequency response of the
comparison of the fault indication in both techniques proves the winding, which is affected by the transformer construction
possibility of moving from off-line to on-line method. Sweep
and resulting coil parameters of resistance, inductance and
Frequency Response Analysis (SFRA) is considered an accurate
technique for off-line tests. The changes in the windings capacitance. It can provide an indication for winding and core
inductance and capacitance affect the number of poles in the conditions by relating changes in frequency response to
system response, so the number of poles will indicate the number changes in coil parameters. In addition, the possibility of
of healthy sections. For on-line method, measurement of moving to an on-line method is considered through
primary/secondary voltage/current is used to determine the determining the impact of short-circuit occurring between
measurable values which would result from a range of internal sections in one winding, between windings and core and
short circuit faults. From the simulated results, it is found that between both windings on the measurement of voltages and
primary current can be used as the main indicator for the currents for the standard AC frequency.
primary winding short circuits; a combination of secondary
voltage and primary current is found to be useful for detecting
secondary winding faults. Secondary winding voltage can be the
II. OFF-LINE FAULT DETECTION METHOD
main indicator for the cross windings short circuits. SFRA is an advanced method for defining transformer
health conditions, by applying low and constant voltage with
Index Terms—Power Transformer monitoring, off-line and on-
varying frequencies to the transformer windings, the ratio of
line method, SFRA, Section-to-section faults
the measured input and output signals gives the required state
I. INTRODUCTION of the transformer [10]. This method must integrate the
measurement and analyze the data while the device is not
Power transformer failures have a high financial impact in connected to the electrical supply in order to provide winding
the distribution and transmission companies, due to failure to health conditions [11]. Typically the SFRA method consists
meet commercial contract and transformer replacement cost. of measuring the transformer response in a range of
The majority of the transformers in service in the network frequency from 0.1 Hz to 5 MHz (based on the transformer
have been installed since 1970 [1]. Power transformer construction), to find the resonant frequencies of the winding.
reliability is dependent on the condition of its insulation The identification of changes to these frequencies from a
system. Most transformer failures are caused by the electrical, known baseline measurement, or in comparison with
thermal and mechanical stresses [2], [3] that appears in the transformers of the same type, allows the detection of
transformer under certain operating conditions. 70%-80% of changes in the geometry of the winding.
power transformer faults occur as result of internal short
circuit and, as indicated in research papers such as [4], [5], A. Winding Model and faults
[6], the very high current under short circuit conditions leads A transformer model has been implemented in PSPICE
to high mechanical force on the windings, These forces cause based on the data for transformer following the example of
changes in the dimensions through axial or radial deformation [12], the transformer is iron-core insulated winding. The
[7]. Internal faults such as winding faults can lead to massive transformer is modeled as 5 sections of coil that are
damage in a short time [8] and are the most likely cause of connected in series (Fig. 1). Each section is represented by
B. Healthy winding
The model is initially run as a healthy winding connected to a
constant resistive load of 100 Ω and with a fixed supply of voltage
230 V to obtain the SFRA response of a healthy winding, which will
be later compared to those of faulty models. The output voltage is
measured on the load side. Any change of any section’s impedance
leads to changes in the winding impedance which theoretically
impacts on the measured voltage.
E. Number of poles
Table III indicates the number of poles for the different Fig. 6. Model of two windings transformer connected to a load
conditions that have been simulated. Note that the change in TABLE IV
SFRA response is the same for shorting the relevant section POWER TRANSFORMER MODEL PARAMETERS
to ground (core) as intra-turn shorting. Components Values
TABLE III Primary section resistance RP 1.2 Ω
HEALTHY AND UN-HEALTHY WINDING CONDITIONS 1.2 Ω
Secondary section resistance Rs
Number
Cases Condition Primary section inductance LP 7.2H
of Poles
1 Healthy winding 5 Secondary section inductance LS 7.2H
2 One section is shorted or section 4 to ground 4 Primary and secondary series capacitance C S 1 , C S 2 0.0133nF
3 Two sections are shorted or section 3 to ground 3 Primary and secondary shunt capacitance C g 1 , Cg 2 3nF
4 Three sections are shorted or section 2 to ground 2 Capacitance between windings C w 5nF
5 Four sections are shorted or section 1 to ground 1
TABLE V
III. ON-LINE FAULT DETECTION METHOD
LOAD PARAMETERS
In this case, internal fault detection is investigated by using the Total impedance 11309.7 Ω
Total reactance 6784.3Ω
measurement of both voltages and current in both transformer
Resistance 9048.9 Ω
windings for 50 Hz frequency and connected to constant load. Faults Inductance 27.9 H
between sections in one winding, between sections and ground and Capacitance 1.59µF
between two windings were studied. The impact of the faults on the Power factor 0.8
primary and secondary voltages and currents is considered, to detect
internal short circuit using measurable parameters. The simulation was run for both healthy and faulty
transformers and the primary and secondary voltage and
A. Healthy Transformer Model current were recorded. The measured parameters for healthy
A modified version of the transformer model set out in [13] transformer can be seen in Table VI.
and used in [14] is used. This model is a one to one power
transformer having two interleaved windings of five sections B. Faulty Transformer model
that contain twenty turns. Each section is represented by a Referring to the equivalent circuit of the transformer
lumped resistance, an inductance and a shunt and a set of winding, healthy winding impedances are constant. In an
series capacitances. Primary and secondary windings are unhealthy winding the values will vary from these, as is the
linked by mutual inductance that is dependent on the case when the transformer suffers from a short circuit or
transformer construction. The model modification considers mechanical deformation causing changes in winding
iron core instead of air core which increases the magnetic link impedance. Due to the changes induced by the faults, it is
between the windings and gives a truer indication of a power expected that the primary/secondary voltages/currents would
transformer construction. Insulation materials considered are deviate from the operating values under known load
paper of thickness of 0.1 mm wrapped around the conductor conditions. Interpreting the measurable signatures is to be
and oil to provide insulation and cooling. The construction of used to identify the un-healthy conditions of the transformer.
the healthy model and the connection to the load is shown in Figure 7 indicates the current flow during short circuit
Figure 6. The system is simulated using 230 V, 50 Hz supply between sections in each winding and between windings.
on the primary and the secondary side is connected to a A short circuit occurring between nodes 2 and 3 is equivalent
to removing one section from the overall model and, agreement with the work carried out in [15] and the
accordingly, the ratio of number of turns, the winding simulation conducted in [16].
TABLE VI
impedances and mutual inductance will be different . MEASURED PARAMETERS FOR PRIMARY WINDING FAULTS
In theory shorting one section in the transformer primary Vin Iin Vout Iout
No Case
winding will have the same impact irrespective of its actual (Volts) (Amps) (Volts) (Amps)
location. Similarly, a short across one section of the 1 Healthy Transformer 229.99 0.022 229.798 0.02
secondary will produce similar, but different, measurable 2 Section 1 to 2 229.99 9.599 229.809 0.02
3 Section 2 to 3 229.99 9.599 229.809 0.02
changes. Simulations were run for both healthy and damaged 4 Section 3 to 4 229.99 9.599 229.809 0.02
transformers and measured values in both transformer sides 5 Section 4 to 5 229.99 9.599 229.809 0.02
are taken to consider the relationships between transformer 6 Section 4 to Ground 229.99 9.599 229.809 0.02
health and measurable parameters. Table VI shows the 7 Section 1 to 3 229.99 25.572 229.803 0.02
measured parameters for healthy and damaged transformers, 8 Section 2 to 4 229.99 25.572 229.803 0.02
9 Section 3 to 5 229.99 25.572 229.803 0.02
with the faults outlined in the following sections. 10 Section 3 to Ground 229.99 25.572 229.803 0.02
11 Section 1 to 4 229.99 57.518 229.801 0.02
12 Section 2 to 5 229.99 57.518 229.801 0.02
13 Section 2 to Ground 229.99 57.518 229.801 0.02
14 Section 1 to 5 229.99 153.35 229.796 0.02
15 Section 1 to Ground 229.99 153.35 229.796 0.02
Similar sections short circuit Fig. 11. Primary current for short circuit between dissimilar primary and
secondary windings
A short circuit taking place between any two sections having
similar locations in different windings, ( such as, section 1 primary
winding and section 1 in secondary winding, etc ), does not affect
the ratio of turns in the transformer. It can be seen that this type of
fault has no effect on the input and output currents and has minimal
effect on the output voltage. The small change in output voltage is
graphed in Figure 10: this change in voltage would be difficult to
measure in practice.
Fig. 12. Secondary voltage for short circuit between dissimilar primary and
secondary windings
to lower sections in primary coil (shown in orange in Table X), the No Fault Vin Iin Vout Iout
(Volts) (Amps) (Volts) (Amps)
input current and output voltage are again affected in comparison to 1 1P-4S 229.99 34.541 367.751 0.032
the healthy state. 2 4P-1S 229.99 8.627 91.979 0.00807
E. Summary of applying On-line method current are considered to be strong contenders to detect the
Table XII summarizes the major and minor variables that could be secondary winding faults and (iii) a short circuit between two
used to detect the type of short circuit that exists in a transformer. windings can be determined from the output voltage and the
input and output currents. It has been shown fault type is
TABLE XII more easily determined than the fault location as, for most
HEALTHY AND UNHEALTHY CONDITIONS OF POWER TRANSFORMER USING
faults, location does not affect the measurable parameters
ON-LINE METHOD
Case High priority indicators Low priority indicators considered. However, in the case of a short circuit between
Healthy transformer Primary and secondary two windings, the measured values would give information
-
voltage and current on fault location.
Primary winding Primary current Secondary current Measuring on-line voltages and currents can be used to
faults
Secondary winding Secondary voltage and Secondary current
indicate faults that may occur within a winding and between
faults primary current windings of a power transformer during normal operation.
Short circuit between Secondary Voltage Primary and secondary This method also provides an ability to define fault severity
windings current from external measurements. Comparison of both methods
proves the possibility of shifting from off-line to on-line
IV. COMPARISON OF OFF-LINE AND ON-LINE METHODS method for power transformer condition monitoring and fault
diagnosis.
The possibility of moving from an off-line to an on-line method VI. REFERENCE
has been proved. The results obtained for defined faults when the
on-line and the off-line methods are applied are summarized in [1] B. J. Small and A. Abu-Siada, “A new method for analysing
transformer condition using frequency response analysis,” in IEEE
Table XIII. As can be seen, both methods are able to detect the
Power and Energy Society General Meeting, 2011, pp. 1–5.
studied faults with same indication. [2] S. Ab Ghani, Y. M. Thayoob, Y. Ghazali, M. Khiar “Evaluation of
transformer core and winding conditions from SFRA measurement
TABLE XIII results using statistical techniques for distribution transformers,” in
COMPARISON BETWEEN OFF-LINE METHOD AND ON-LINE METHOD FOR ONE IEEE Int, PEOCO, no. 6-June 2012, pp. 448–453.
TYPE OF FAULT DETECTION [3] S. Rotby, A. El-Hag, M. Salama, and R. Bartnikas, “Partial discharge
Off-line faults On-line faults detection detection and localization inside the winding of power transformer,” in
detection using using measurement IEEE An Rep Conf on Ele Ins and Diel Phenomena, 2012, pp. 84–87.
No Case [4] K. Ramesh and M.Sushama, “Inter-Turn Fault Detection in Power
SFRA parameters
Number of Poles Primary current A Transformer Using Fuzzy Logic,” in IEEE (ICSEMR 2014).
1 H-Transformer 5 0.022 [5] O.Gouda, A. El Dein, and I. Moukhtar “Turn-to-earth fault modelling
2 Section 1 to 2 4 9.599 of power transformer based on symmetrical components,” IET Gener.
3 Section 2 to 3 4 9.599 Transm. Distrib., ISSN 1751-8687. vol. 7, no. 7, 2013, pp. 709–716.
4 Section 3 to 4 4 9.599 [6] H. Afkar and A. Vahedi, “Detecting and locating tum to tum Fault on
5 Section 4 to 5 4 9.599 layer winding of distribution transformer,” in The 5th IEEE
6 Section 4 to G 4 9.599 Conference on Thermal Power Plants (lPGC2014), Shahid Beheshti
University, Tehran, Iran.10-11 Jone,2014 . pp. 109-116.
7 Section 1 to 3 3 25.572
[7] X. Liu and M. Chen, “An on-line monitoring method for winding
8 Section 2 to 4 3 25.572
deformation of power transformers,” IEEE 8th Conf. Ind. Electron.
9 Section 3 to 5 3 25.572 Application, Jun. 2013, pp. 255–260.
10 Section 3 to G 3 25.572 [8] N. Joshi, Y. Sood, R. Jarial, and R. Thapliyal, “Transformer Internal
11 Section 1 to 4 2 57.518 Winding Faults Diagnosis Methods: A Review,” MIT Int. J. Electr.
12 Section 2 to 5 2 57.518 Instrum. Eng. ISSN 2230-7656 Publ, vol. 2, no. 2, 2012. pp. 77–81,
13 Section 2 to G 2 57.518 [9] R. Schwarz and M. Muhr, “Diagnostic methods for transformers,” Int.
14 Section 1 to 5 1 153.352 Conf. Cond. Monit. Diagnosis. China, Apr 21-24, 2008, pp. 974–977.
15 Section 1 to G 1 153.352 [10] A. Pandya, B. Parekh “Sweep Frequency Response Analysis (SFRA)
an Approach To Detect Hidden Transformer Fault,” Int Journal of Adv
Res in El,Electr and Inst Eng. vol. 2,5 May,2013 no. 5, pp. 1893–1896.
V. CONCLUSION [11] J. Kumar, U. Prasadr “Expert System for Sweep Frequency Response
Analysis of Transformer Using MATLAB,” Int Journal of Scie and
In this paper, healthy and unhealthy conditions of a power Res Pub, vol. 2, no. 12, 2012. pp. 1–13.
transformer are investigated using off-line and on-line [12] T. Mariprasath and V. Kirubakaran, “Power Transformer Faults
methods. SFRA is used for range of 0.1 Hz up to 5MHz that Identification using SFRA,” Int. Journal. Sci. Eng. Res. ISSN 2229-
5518, vol. 5, no. 5 May, 2014. pp. 81–87.
was found suitable for the selected transformer parameters. [13] L. Satish and S. K. Sahoo, “An effort to understand what factors affect
Each healthy section will give rise to one pole in the the transfer function of a two-winding transformer,” IEEE Trans.
frequency spectra, which means that the number of healthy Power Deliv, vol. 20, no. 2 April, 2005. pp. 1430–1440.
sections is indicated by number of poles. Shorted section [14] E. Aburaghiega, M. E. Farrag, and D. M. Hepburn “Investigation and
Understanding the Conditions of Power Transformer Internal Faults
leads to a reduction of the number of poles according to the using On-line Technique” in (ICREPQ’15), no. 13. Mar 25-27, 2015
sections that are out of circuit. It is not possible to identify [15] G. Díaz, A. Barbon, J. aleixandre and J. Coto “Currnet sequence
which sections are short circuited but it is possible to tell the analysis of transformer under Turn-to-Turn faults,” 14th PSCC,
number of sections short circuited from the number of poles Sevilla, June 24–28, 2002, session 03, Paper 6, page 6.
[16] L. M. R. Oliveira and A. J. M. Cardoso, “Power transformers behavior
present. For on-line method, the simulations indicate that: (i) under the occurrence of inrush currents and turn-to-turn winding
the primary current can be used as the main indication for insulation faults,” in IEEE 19th ICEM, Rome, 2010.
primary winding short circuits; (ii) output voltage and input