Water Supply and Toilets Bylaws
Water Supply and Toilets Bylaws
The requirements of water supply for various occupancies shall be as given in Table No. 26,27,28
or as specified by the Municipal Commissioner from time to time.
Table No. 27
PER CAPITA WATER REQUIREMENT OF VARIOUS USES / OCCUPANCIES
Consumption
per head per
Sr. No. Types of Occupancy
day
(in litres)
(1) (2) (3)
RESIDENTIAL
a) In living unit located on plots less than 50 sq.m. 90
1.
b) In living units 135
c) Hotels with lodging accommodation (per bed) 180
EDUCATIONAL
2. a) Day schools 45
b) Boarding schools 135
INSTITUTIONAL (Medical Hospitals)
3.
a) Number of beds not exceeding 100 340
*The values in parenthesis are for stations where bathing facilities are not provided.
Note : The number of persons for Serial Number (10) to (13) shall be determined by the average
number of passengers handled by the station daily ; due consideration may be given to the staff
and workers likely to use the facilities.
Table No. 28
FLUSHING STORAGE CAPACITIES
Sr.No Classification of Buildings Storage Capacity
For tenements having common
1. 900 litres net per w.c. seat.
convenience.
270 litres for one w.c. seat &180 litres
For residential premises other than
2. for each additional seat in the same
tenements having common convenience.
flat.
900 litres per w.c. seat and 180 litres
3. For factories and workshops.
per urinal seat.
900 litres per w.c. seat & 350 litres per
4. For cinemas, public assembly halls etc.
urinal seat.
Table No. 29
Sanitation requirement for shops and commercial offices
Sr.No. Fitments For personnel
(1) (2) (3)
1. Water-closet One for every 25 persons or part thereof exceeding 15 (including
employees and customers). For female personnel, 1 per every 15
persons or part thereof exceeding 10.
2. Drinking water One per every 100 persons with a minimum of one on each floor.
fountain
3. Wash basin One for every 25 persons or part thereof. One of such wash basins on
each floor shall be fixed at height of 80 cm. with tap at 100 cm. above
finished floor level for the use of handicapped disabled, old and
infirm persons.
4. Urinals One for 50 persons or part thereof.
5. &OHDQHU¶VVLQN One per floor minimum, preferably in or adjacent to sanitary rooms.
Note: Number of customers for the purposes of the above calculations shall be the average number of
persons in the premises for a time interval of one hour during the peak period. For male-female calculation a
ratio of 1:1 may be assumed
Table No. 30
Sanitation Requirements for Institutional (Medical) Occupancy - (Staff Quarters & Hostels)
Sr. Fitments 'RFWRU¶V'RUPLWRULHV 1XUVH¶V
No. For Male Staff For Female Staff Hostel
Table No.31
Sanitation Requirements For Government And Public / Business Occupancies And Offices
Sr. Fitments For Male Personnel For Female
No. Personnel
(1) (2) (3) (4)
1. Water-closet One for every 25 persons or part thereof. One for every 15
persons or part thereof.
2. Ablution taps One in each water closet One in each water
closet
3. Urinals Nil upto 6 persons. One for 7-20 persons, 2 for
21-45 persons, 3 for 46-70 persons, 4 for 71-
100 persons.
From 101 to 200 persons add at the rate of 3
percent. For over 200 persons add at the rate
of 2.5 percent.
4. Wash basin One for every 25 persons or part thereof. One
of such wash basins on each floor shall be
fixed at height of 80 cm. with tap at 100 cm.
above finished floor level for the use of
persons with disabilities, old and infirm
persons.
5. Drinking water One for every 100 persons with a minimum of
fountains. one for each floor.
6. Baths Preferably one on each floor
7. &OHDQHU¶VVLQNV One per floor minimum preferably in or
adjacent to sanitary rooms.
Table No.33
Sanitation Requirements For Assembly Occupancy Buildings
(Cinemas, Theatres And Auditoria)