Professional Documents
Culture Documents
A Simplified Algorithm For OLTC Control in Active Distribution MV Networks
A Simplified Algorithm For OLTC Control in Active Distribution MV Networks
Abstract—The increasing penetration of Distributed networks by the communication exchange among the
Generation (DG) in distribution electrical systems may cause remote terminals and a network supervisor [6].
alteration of voltage profiles on the lines. Traditionally, The basic hypothesis for the regulation strategy
distribution networks with radial configuration are designed development presented in [6] is a bi-directional
as a passive top-down architecture where voltage regulation
is mainly performed by an On-Load Tap Changer (OLTC)
communication among the end-users and the central
transformer located at the Primary Substation. Therefore it controller (called Network Supervisor), allowing an
becomes rather difficult to compensate lines radiating out adaptive area selection for the evaluation of suitable zonal
from the same bus-bar where some of these are subject to control signals to be forwarded to the local regulators
overvoltages due to the power injection by DGs connected including the OLTC action.
whereas others are subject to voltage drops due to the In this paper, a control strategy suitable for the On Load
presence of passive loads only. A first step in regulation and Tap Changer, installed at the Primary Station HV/MV
managing the voltage levels, in order to be consistent with the transformer, based on few remote current and voltage
contingent needs of the network, may be a decentralized local measures is presented. An algorithm for the voltage drop
control strategy performed by the DG units, however better
estimation knowing only a restricted number of measures
results will be obtained with a coordinated OLTC
intervention. regarding the DG connection buses along the distribution
In this paper an OLTC control strategy, based on only few feeders has been developed and briefly discussed in the
remote measurements, is proposed. This procedure allows the following.
tap changer controller to infer the state of network node In this work, a case study MV distribution network
voltages and to act accordingly. The performance of the equipped with several inverter-interfaced DGs is used to
proposed control method is demonstrated through investigate the dynamic behavior of the local controllers
simulations on a realistic MV distribution network. when they are included in the coordination strategy which
Index Terms— Active networks; Distributed generation; includes an OLTC control for dynamic adjustment of the
OLTC; Voltage control. tap position of the PS transformer.
Studies have been conducted through the co-simulation
between two software environments: DigSilent
I. INTRODUCTION Powerfactory, used to simulate dynamic control of OLTC
The growing connection to the grid of non- and distributed inverters, operating on the basis of the
programmable renewable energy resources raises several signals concurrently elaborated by an estimation algorithm
issues in the operation of modern distribution networks. implemented and running on the Matlab platform.
Due to the of traditional radially structured MV distribution
networks, some technical factors limit the diffusion of DG II. VOLTAGE DROP ESTIMATION ALGORITHM
units: fault current level increase, possible power flow
The algorithm for the voltage drop estimation is based
inversion with risk of ampacity violations and impact on
on the use of innovative not expensive TATV sensors
voltage regulation.
(examples of which are shown in Fig.1), developed as
The diffusion of DGs in distribution networks requires
innovative integrated current and voltage measurement
the application of more sophisticated control schemes in
equipment for the fault detection in MV systems (see for
order to avoid technical issues related to the unpredictable
instance [7]).
power flow alterations (e.g. voltage level violations).
This sensor has already been proposed for exploiting a
The possibility of performing the network regulation,
voltage regulation strategy based on the reactive power
through complex voltage monitoring and communications
exchange among adjacent buses [8].
systems coordinated by a central unit is a topic of actual
discussion, see for instance [1-5].
In a previous work, a strategy for the coordination of
the DG intervention for voltage regulation in MV networks
has been proposed, also including the participation of LV
A
A. Calculatee the unitary cuurrent (associaated to each buus)
as (indicaating Ltot as thee branch total length):
l
I A IB
iload (2)
Ltot
B
B. Calculatee the relative vvoltage drop foor each sectionn of
the consiidered branch,, separating thhe effects of the
active andd reactive com
mponents İa andd İr:
Loads
Commerccial 4,70 3,68 1,57 0,775
Industriaal - - 3,87 1,889
Wind - - 4,00 0
DGs
Photovoltaaic - - 4,50 0
F
Figure 3. Concepptual diagram of
o the OLTC conntrol, given the
reemote measuredd/estimated volttages.
When bothh the maxim mum and miinimum voltaages S li ffactor
oovercome or respect
r the connsidered regulation band (hhere
t
Time [h]
F
Figure 5. Daily load
l (a) and genneration (b) scalling factors.
The loads’ power factor is maintainedd constant durring
thhe 24-hour simulation, whiile the DG unnits are equippped
wwith local conttrols enabling the reactive ppower modulattion
fo
for voltage suppport stated byy the Italian sttandard CEI 0-16
0
[9].
The DG unnits are required to exchangge reactive pow wer
wwith the netwoork following a droop characteristic Q=ff(V)
oof the type reported in Figg. 6, using thee local measuured
vvoltage, in a ±((48,43%)Pn power range.
In this paaper three sccenarios considering differrent
OOLTC automaations are propposed in ordeer to compare the
standard AVR control, basedd on the transfformer seconddary
bbusbar voltagee, with the cooordinated regulation strattegy
bbased on the proposed alggorithm; finallly an applicattion
cconsidering alsso the influennce of the locaal voltage conntrol
F
Figure 4. Single--line diagram of the case studyy network. bby DGs is pressented.
liimit 0,95 pu aand no further actions are takken by the OL
LTC
ccontroller.
B
B. Scenario B (AVR equippeed with estimaation algorithm
m)
Scenario B considers thhe application of the propoosed
eestimation alggorithm, knowwing the volttage measuress at
F
Figure 6. CEI 0--16 Voltage-Reaactive droop currve. nnode N2 (trannsformer secoondary busbarr), N9 and N N12,
wwhere DGs aree connected. TThe coordinatiion procedure can
A
A. Scenario A (AVR with voltage referrence at startting bbe summarizedd as follows:
bus)
x the contrrol algorithm estimates thee maximum and
In scenarioo A, the AV VR control is adopted for the minimumm voltages in oorder to evaluaate the tap chaange
OOLTC, so thhe goal is tto maintain the transform mer necessaryy, following thhe logic presennted in sec. II;
ssecondary busbbar (node N2)) voltage withhin the dead-bband
x OLTC chhanges the tapp position aftter an intentioonal
±±(1,5%)Vn. Inn this case thee local voltagge control by the
delay of 30s, in ordeer not to folllow fast volttage
DDG units is not enabled inn order to focuus on the OL LTC
fluctuatioons;
ooperation, so tthe generated ppower is mainntained at unittary
pp.f.. The adoptted procedure is the followinng: x After thee 30s intentiional delay ((if the objecttive
remains constant)
c one tap is changeed every 5s time
x The OLT TC constantly receives the m
measured volttage
delay (i.ee. mechanical delay).
d
at the N2 busbar;
This scenarrio considers tthe same netw work conditions of
x When thee voltage is ooutside the im mposed threshoolds
scenario A, so the DG units are still not ennabled to suppport
for longeer than the inteentional delayy time of 30s, the
thhe voltage witth a local reacttive power conntrol.
control unnits operate too change one tap of the OL LTC
Fig. 8 shhows the vooltage values in a 24-hoours
position, in order to rrestore the vooltage inside the
simulation connsidering the daily scaling factors in figg. 5.
dead-band;
TThe violet soolid curve shhows the estimated minim mum
x After the 30s intentionnal delay (if thhe secondary bus vvoltage level which differss from the acctual value (bblue
voltage rremains outsidde the dead-bband) one tapp is ddashed line) aat most for 0,01 pu, as a result of a non- n
changed every
e 5s time delay (i.e. meechanical delayy). uuniform load distribution on the feedder. In orderr to
Loads andd generators vary durinng the 24-hoours ccompensate suuch error, a m more restrictivee lower threshhold
ssimulations foollowing the ddaily scaling factors shownn in iss considered byb the controlller, i.e. 0,96 puu rather than 00,95
FFig. 5. ppu.
Voltage p.u.
Voltage p.u.
pu
pu
T
Time [h] T
Time [h]
F
Figure 7. Voltagge levels during the 24h simulaation in the scennario F
Figure 8. Voltagge levels during the 24h simulaation in the scennario
A application. B application.
Fig. 7 shoows the maxiimum and minimum voltaages The OLTC C control is aiimed at reduccing the netw work
aalong with thee transformerr secondary bbusbar voltagee in vvoltage deviatiions within thhe ±5%Vn baand, adopting the
ccase of an unccoordinated action by the O OLTC. It cann be ccontrol schemee in Fig. 3.
nnoticed that during the low productiion periods the Although tthe efficiencyy of the cooordinated conntrol
mmaximum volttage is measuured at node N N2, while durring strategy is prooven by a reeduced voltage deviation w with
thhe high prodduction periood (due to the photovolltaic respect to scennario A, it shhould be noticced that in soome
ccontribution) thhe two feederrs have opposiite voltage trennds. innstances, evenn with voltagee issues not coompletely solvved,
AAs a result, thee N2 busbar vvoltage settles around the vaalue nno further actioon is taken byy the OLTC controller in orrder
1 pu, even if the minimum m voltage overrcomes the lower too avoid adversse effects on thhe other voltages.
1.075
OLTC AVR reg. OLTC coordinated reg.
1.05
1.025
Voltage [p.u.]
1 aa)
0.975
0.95
0.925
0 5 10 15 20 2
25
L
Length [km]
F
Figure 9. Com mparison betweeen the networkk voltages in one
bb)
simulation instannce (t=8 h) undder different opeerating scenarios: in
reed scenario A, in
i blue scenarioo B.
VI. REFERENCES