You are on page 1of 28

Vacuum Circuit-Breaker 3AH3

7.2kV to 36kV
3AH3
7.2kV 36kV

Operating Instructions/ Order-No:/ : 3ZX1812-0AH30-0AN1/9229 9860 174-SLC PTD MC

All right reserved /


©S iemens AG 1996 & SLC PTD MC 2001

Operating Instruction Siemens 3AH3 / 3AH3


Central legend

13. Checking marking 59. ON-OFF indicator


15. Pole plate 59.1 Opening for
16.1 Upper post insulator ″closed/open″
indicator
16.2 Lower post insulator
60. Mechanism housing
19. Pole assembly,
60.1 Cover
complete
20. Upper interrupter 60.2 Transport hole
support 60.3 Crane hook symbol
27. Upper terminal 61. Dashpot
28. Strut 62. Closing spring
28.1 Centering piece 63. Breaker shaft
29. Lower terminal 64. Opening spring
29.1 Flexible connector 66. Closing damper
29.2 Clamp 68. Auxiliary switch S1 S1
30. Vacuum interrupter (6NO+6NC) (6 +6 )
31. Fixed contact piece 68.0.1.Extended auxiliary S1
31.1 Connection surface switch S1 (12 +12 )
(12NO+12NC)
32. Insulator
68.1 Operating rod (for (
33. Arcing chamber
auxiliary switch S1) S1)
34. Metal bellows
68.7.1 Low voltage plug 64 X0
35. Guide connector X0 (64-
36. Moving contact piece pole)
36.1 Drive and terminal 69. Contactor
bolt 70. Earthing bolt M12
40. Lower interrupter 90. Mechanical
support interlocking
48. Insulating operate
rod
48.6 Angled lever
49. Contact pressure
spring
50. Hand crank
50.1 Opening for fitting
hand crank
50.2 (Charging) gearing
50.4 Motor M1 M1
50.4.1Position switch
50.5 Hand crank coupling
50.6 Adapter for hand
crank
51. Rating plate
51.1 Opening for rating
plate
53. ″Close″pushbutton
53.1 Closing solenoid Y9 Y9
54. ″Open″pushbutton
54.1 Shunt release Y1 Y1
54.2 Shunt release Y2 Y1
54.3 Current transformer-
operated release Y4 Y4
54.4 Undervoltage release Y7
Y7
55. ″Closing spring ″ ″
charged″ indicator
55.1. Opening for indicator ″ ″
″Closing spring
charged″
58. Operating cycle
counter
58.1 Opening for
operating-cycle
counter

Operating Instruction Siemens 3AH3 / 3AH3


Contents Page
General 1/1 1/1
Technical data 1/2~1/9 1/2~1/9
Type designation 1/2 1/2
Rating plate 1/2 1/2
Standards and specification 1/3 1/3
Ambient temperature/humidity ,
loadability 1/3 1/3
Site altitude 1/4 1/4
Electrical data 1/5 1/5
Operating times 1/6 1/6
Switching duties 1/6 1/6
Motor operating mechanism 1/6 1/6
Auxiliary switch 1/7 1/7
Low-voltage plug connector 1/7 1/7
Shunt closing release 1/7 1/7
Shunt release 1/7~1/8 1/7~1/8
Undervoltage release 1/8 1/8
CT-operated release 1/8 1/8
Breaker tripping signal, cut-out
Switches (S6 and S7) 1/9 (S6 S7) 1/9
Varistor module (V1 to V3) 1/9 (V1 V3) 1/9
Electrical local closing/ /
Electrical interlocking 1/9 1/9
Mechanical interlocking 1/9 1/9
Dimensions and weights 1/9 1/9

Description 2/1~2/5 2/1~2/5


Construction 2/1~2/3 2/1~2/3
Vacuum interrupters 2/4 2/4
Complement 2/5 2/5

Installation 3/1~3/4 3/1~3/4


Installing in cubicle or on truck 3/1 3/1
Flat bar connection 3/1~3/2 3/1~3/2
Control leads 3/2 3/2
Earthing 3/2 3/2
Circuit documents 3/2 3/2
Function schematic diagram 3/3~3/4 3/3~3/4

Operation 4/1~4/2 4/1~4/2


Commissioning 4/1~4/2 4/1~4/2
Charging and closing spring 4/2 4/2
Closing 4/2 4/2
Tripping 4/2 4/2

Maintenance 5/1~5/5 5/1~5/5


Safety measures 5/1 5/1
Servicing 5/1 5/1
Cleaning 5/1 5/1
Abnormal operating conditions 5/2 5/2
Checking the contact systems 5/3 5/3
Checking the vacuum 5/3 5/3
Service life 5/4 5/4
Accessories and spare parts 5/5 5/5

Note: The items illustrated in the Figures are : .


enumerated in the fold–out central
legend.

When ordering the operating instructions please 3ZX1812-0AH30-


quote the order No.3ZX1812-0AH30-0AN1/9229 0AN1/9229 9860 174 - SLC PTD MC.
9860 174 - SLC PTD MC.

Operating Instruction Siemens 3AH3 / 3AH3


! WARNING !
This equipment contains hazardous volt- ,
ages and mechanical parts which move .
at high speed and may be controlled
remotely.

Non-observance of the safety instructions


can result in severe personal injury or .
property damage.

Only qualified personnel should work on ,


or around this equipment after becoming
thoroughly familiar with all warnings, .
safety notices, and maintenance procedu-
res contained herein.

The successful and safe operation of this


equipment is dependent on proper , , .
handling, installation, operation and
maintenance.

General: :
Siemens 3AH3 vacuum circuit-breakers (V- 3AH3 ,
breaker) are of the triple-pole indoor type for rated 7.2kV 36kV.
voltages between 7.2 and 36kV.

The vacuum circuit-breaker consists of the ,


mechanism housing complete with stored-energy , ,
mechanism and control elements, the three poles .
with vacuum interrupters, cast-resin insulators and
operating rods.

The mounting position (relative to the vacuum ( ).


interrupters) is vertical. The vacuum circuit- .
breaker can be used in practically any system
design.

Under normal operating conditions, the vacuum , .


circuit-breaker is maintenance free.

- 1/1 -

Operating Instruction Siemens 3AH3 / 3AH3


Technical data
Type designation
3AH3 vacuum circuit-breakers are identified by a 3AH3
machine-readable product designation made up of a .
series of figures and letters.

Basic type

Rated voltage

Rated short circuit breaking current

Rated normal current

3 A H 3 1 1 7 - 7
(See catalog HG11 for selection and ordering data of ( 11)
the respective circuit-breaker)

Rating plate

The rating plate which can be read in the operating , :


position, contains the following information:
1 Manufacturer 7 Rated short-circuit 1 7
duration
2 Type designation 8 Weight 2 8
3 Serial number 9 Rated operation 3 9
sequence
4 Design code 10 Rated frequency 4 10
5 Year of manufacture 11 Rated lightning impulse 5 11
6 Rated normal current withstand voltage 6
12 Rated short-circuit 12
breaking current
13 Rated voltage 13

3117-7 2Y 3117-7 2Y

3150 3150
50 50

O- O-

Fig.1/1 .1/1
Rating plate

Note: in the event of any queries state the type : (2), (4),
designation(2), designation code(4) and the serial (3).
number(3).
- 1/2 -

Operating Instruction Siemens 3AH3 / 3AH3


Standard specifications
The 3AH3 vacuum circuit-breaker comply with the 3AH3 IEC 56, IEC 694, BS
standards of IEC 56, IEC 694, BS 5311 and DIN VDE 5311 DIN VDE 0670 , 15kV
0670. The V-breakers 3AH3 for 15kV rated voltage ANSI C37 .
meet the requirements of the American standards
ANSI C37 with respect to their insulating capacity.

Ambient temperature/humidity and loadability ,


The 3AH3 V-breakers are designed for the normal 3AH3
operating conditions laid down in the standards. .
Permissible ambient temperatures:

Maximum value =+40°C =+40°C


Average over a period of 24 hours =+35°C 24 =+35°C
Minimum value = -5°C = -5°C
Permissible atmospheric humidity: :
Relative humidity, 24 hours mean <95% 24 <95%
Relative humidity, 1month mean <90% 1 <90%

Under these conditions condensation may occasionally , . 1/4 DIN


occur. The rated normal currents listed in Fig. 1/4 were VDE/IEC 40°C .
laid down for 40°C ambience in accordance with DIN .
VDE/IEC. Use under conditions other than normal is
possible with certain measures that can be implemen-
ted on request.

The maximum permissible load current as a function of 3AH3 , 1


the 3AH3 V-breaker ambient temperature has been . .
plotted in Fig.1/2. The load currents indicated apply to , ,
open-type switchgear. Metal-enclosed switchgear must .
be derated as specified by switchgear manufacturer.

Load current A

Determination of the load characteristic number

Rated normal current load characteristic number

1250A 2
2000A 4
2500A 5
3150A 6
4000A 7

Ambient temperature °C
Fig.1/2 Maximum permissible load current as a function of the
switch ambient temperature
. 1/2

-1/3 -

Operating Instruction Siemens 3AH3 / 3AH3


Site Altitude
The rated insulating capacity values (rated impulse ( ,
1
withstand voltage, rated power frequency withstand ) ) VDE 0111 IEC-71
20 °C
1 3
voltage) ) specified for the equipment are, in accord- ( 1013 h Pa, 11g/m )
ance with the provisions if VDE Standard 0111 and IEC , .
Publication 71, based on standard atmospheric , , .
3
conditions (1013 h Pa, 20 ºC, and 11g/m water 1000m, 9%, ,
content ).i.e. sea lever. The insulating capacity of an VDE,IEC .
insulation in air decreases with increasing altitude as a
result of change in the air density, Standards prom-
ulgated by VDE, IEC and other disregard this decrease
in insulating capacity for altitude of up to 1000m, i.e.
the decrease of approximately 9% at this altitude is still
permissible.

The standards provide no guideline for altitudes of 1000m


more than 1000 m with respect to insulation ratings; , .
they leave this up to an agreement between manufa-
cture and user.

Our own recommendation is as follows: , :


Since this method used for rating insulation up to 1000m
altitudes of 1000 m has proved to be satisfactory, it , . a
should also be applied to higher altitudes. The altitude 1000m ,
correction factor a should therefore be based on the 9%( 0.91 1/1.1).
insulating capacity at 1000m, which is lower by 9%
(corresponding to 0.91 or 1/1.1) than the capacity at
sea level.
The following expression thus applies for the selection :
of the equipment:
2 2
Rated withstand voltage to be selected ) )
2 2
Required rated withstand voltage ) )
> >
(1.1xa) (1.1xa)
Example: :
Site altitude above sea level 3000 m 3000 m
Required rated impulse withstand voltage 95kV 95kV
(For a 15kV system according to ANSI) ( 15kV ANSI )
Correction factor a 0,73 a 0.73
(According to Fig. 1/3) ( 1/3)
Rated impulse withstand voltage to be selected: :
95kV 95kV
=118kV =118kV
1.1x0.73 1.1x0.73
Switchgear with a rated voltage of 24kV, List2 (rated 24kV, 2( 125 kV)
lightning impulse withstand voltage of 125kV) meet this .
requirement.
The actual insulating capacity at the site is then
3 2 3 2
withstand voltage ) = a* rated withstand voltage ) )=a* )
of the selected switchgear unit.
Correction factor/
.1/3
Relationship between the correction factor a and the
site altitude.
a .

Altitude of site above sea level/


The following definitions apply: :
1
) Rated withstand voltage2)=require value corresponding to 1
) 2
)= DIN,VDE,IEC
the provision of DIN ,VDE,IEC for sea level.
Withstand voltage 3)= actual value for the given altitude 3
)= .
2 2
) Rated lightning impulse withstand voltage )
Rated power frequency withstand voltage
3 3
) Lightning impulse withstand voltage )
Power frequency withstand voltage
-1/4 -

Operating Instruction Siemens 3AH3 / 3AH3


Electrical data
3AH3 vacuum circuit-breaker 3AH3

¬ - ® ¯ ° ± ² ³ ´ µ (11)

U UW Us ISC tth Ima D.C. PA


1250A 2000A 2500A 3150A 4000A
(kV) (kV) (kV) (kA) (s) (kA) (%) (mm)
7.2 60 20 50 3 ™ 125 36 210 EU 3AH3 057-2*
™ EU 3AH3 057-6*
™ EU 3AH3 057-7*
63 3 ™ 160 36 275 EU 3AH3 078-2*
™ EU 3AH3 078-6*
™ EU 3AH3 078-7*
™ EU 3AH3 078-8*
12 75 28 50 3 ™ 125 36 210 EU 3AH3 117-2
™ EU 3AH3 117-6
™ EU 3AH3 117-7
63 3 ™ 160 36 275 EU 3AH3 128-2**
™ EU 3AH3 128-6**
™ EU 3AH3 128-7**
™ EU 3AH3 128-8**
15 95 36 50 3 ™ 125 36 210 EU 3AH3 167-2**
™ EU 3AH3 167-6**
™ EU 3AH3 167-7**
63 3 ™ 160 36 275 EU 3AH3 178-2**
™ EU 3AH3 178-6**
™ EU 3AH3 178-7**
™ EU 3AH3 178-8**
17.5 95 38 50 3 ™ 125 36 210 EU 3AH3 217-2**
™ EU 3AH3 217-6**
™ EU 3AH3 217-7**
63 3 ™ 160 36 275 EU 3AH3 228-2**
™ EU 3AH3 228-6**
™ EU 3AH3 228-7**
™ EU 3AH3 228-8**
24 125 50 40 3 ™ 100 36 275 EU 3AH3 266-6
36 170 70 31.5 3 ™ 80 36 350 EK 3AH3 305-2***
™ EK 3AH3 305-4***
™ EK 3AH3 305-6***
40 3 ™ 100 36 350 EU 3AH3 306-6***

* Us up to 32kV on request; ** Us up to 42 kV on request * 32 kV; ** 42kV


*** Us up to 85kV on request; Uw up to 185 kV on request *** 85 kV; 185kV

Note: available :
1. Rated voltage (maximum permissible system voltage) at 50 to 1. ( ) 50-60Hz
60Hz.
2. Rated lightning impulse withstand voltage (peak value) 2. ( )
3. Rated power frequency withstand voltage (RMS value) 3. ( )
4. Rated short-circuit current 4.
5. Rated short-circuit duration 5.
6. Type designation 6.
7. Rated normal current 7.
8. Rated short-circuit making current 8.
9. DC component of rated short-circuit breaking current 9.
10. Pole center distance 10.
11. Switching duties U= Rapid load transfer 11. U=
K= rapid auto-reclosure +U K= +U
E= electrical operating energy E=

Fig.1/4 electrical data for 3AH3 vacuum circuit-breaker .1/4 3AH3

- 1/5 -

Operating Instruction Siemens 3AH3 / 3AH3


Operating times

Closing time/ ms <80


Spring charging time/ s <15
Opening time/ Shunt release/ (Y1) ms <65
Supplementary release 3AX11/ (Y2,Y4,Y7) ms <45
3AX11

Arcing time/ ms <15


Break time/ Shunt release/ (Y1) ms <80
Supplementary release 3AX11/ (Y2,Y4,Y7) ms <60
3AX11

Dead time/ ms 300


Close-open-time/ Shunt release/ (Y1) ms <90
Supplementary release 3AX11/ (Y2,Y4,Y7) ms <70
3AX11

Minimum pulse duration/

″Close″/″ ″ Closing solenoid/ (Y9) ms 45


″Trip″ / ″ ″ Shunt release/ (Y1) ms 40
″Trip″ / ″ ″ Supplementary release 3AX11 (Y2,Y4,Y7) ms 20
3AX11

ms >15
Shortest pulse duration of breaker tripping signal for 1st shunt release /
ms >10
Shortest pulse duration of breaker tripping signal for 2nd and 3rd shunt release
/2 3
Fig.1/5 operating times/ .1/5

Closing time = the interval of time between the initiation of =


the closing operation and the instant when the contacts .
touch in all poles.
Opening time = the interval of time between the initiation of =
the opening operation and the instant when the contacts .
separate in all poles.
Arc time = the interval of time between the instant of the = .
first initiation of an arc and the instant of final arc extinction
in all poles.
Breaking time = the interval of time between the beginning = .
of the opening time of a circuit breaker and the end of the
arcing time.
Close-open-time = the interval of time (in a make-break - =
operation cycle) between the instant when the contacts .
touch in the first pole in the closing process, and the instant
when the arcing contacts separate in all poles in the
subsequent opening process
Switching duties 3AH3 .
The operating mechanisms of the 3AH3 circuit-breakers are
40kA ; 31.5kA
suitable for rapid auto-reclosure. Breakers for a rated short-
circuit breaking current of 40kA are, at rated data levels,
suitable for rapid load transfer; up to 31.5kA they can also
be used for rapid auto-reclosure.
Motor operating mechanism
The maximum DC power input is 500 W (approx.) the 500W. 650VA.
maximum AC power input is 650VA (approx.). During part .
of the short spring charging time the motor operate in the .1/6 .(
overload range. The recommended rating for motion , )
protection devices are shown in Fig.1/6 (the protection
devices are not supplied with the vacuum breakers and
must be ordered separately)
Rated supply voltage DC24V DC48V DC60V DC/AC 110V DC220V/AC230V
50/60HZ 50/60HZ
Recommended rating of protection device* 8A 6A 4A 2A 1.6A
*

*) 8RL74, G

*) MCB assembly TYPE 8RL54 or MCB with G characteristic *) 8RL54 G


Fig.1/6 Rated currents of motor protection device. .1/6
The supply voltage may deviate from the rated value by
-15% to +10%. -15% +10% .
- 1/6 -

Operating Instruction Siemens 3AH3 / 3AH3


Auxiliary switch (S1) 3SV92 (S1) 3SV92
Two versions of the auxiliary switch can be supplied. .
The standard version is fitted with 6 NO contacts and 6 6 . 12 12 .
6 NC contacts. The extended version is fitted with
12NO contacts and 12NC contracts.

Rated insulation voltage: AC/DC 250 V : AC/DC 250V


Insulation class: C acc. to DIN VDE 0110 : C DIN VDE 0110
Current: 10A : 10A
Making capacity: 50A : 50A

Breaking capacity/
AC 40 to 60 Hz/ 40~60Hz DC/
Voltage Operational current Voltage Operational current/
I (A)
U (V) I (A) U (V) Resistive load/ Inductive load/
(T=20ms)
<230V 10 24 10 10
48 10 9
60 9 7
110 5 4
220 2.5 2
Fig.1/7 Breaking capacity of 3SV92 auxiliary switch
.1/7 3SV92

Low-voltage plug connector (X0) (X0)

The control elements of the 3AH3 vacuum circuit- 3AH3


breaker provided in the mechanism housing are wired (X0), 64 .
for external connection to the plug connector(X0). The
standard version is provided with a 64-pole plug
connector.

Shunt closing release (Y9) 3AY1510 (Y9) 3AY1510


The closing solenoid unlatches the charged closing ,
spring and thus closes the circuit-breaker electrically . , , .
It is available for both AC and DC operation. After
completion of a closing operation, the closing solenoid
is de-energized internally.

Power consumption approx. 100 W/VA 100 W/VA

Shunt releases (shunt opening releases) ( )


The shunt releases are used for automatic tripping of
circuit-breakers by means of appropriate protective ,
relays and for deliberate tripping by other electrical . ,
means. They are designed for connection to external ,
voltage (DC or AC voltage). In special cases, for
deliberate tripping, they can also be connected to a
voltage transformer.

Shunt releases based on two different operating


principles are used.

Shunt release (Y1) 3AY1510 (Y1) 3AY1510


The 3AY1510 shunt release is used as standard in the 3AY1510 .
basic circuit-breaker version, with this design, the " " ,
electrically supplied tripping pulse is passed to the .
″open″ latching mechanism by means of a direct-action
solenoid armature and the circuit-breaker is thus
opened.

Power consumption approx. 100 W/VA 100 W/VA


- 1/7 -

Operating Instruction Siemens 3AH3 / 3AH3


Shunt release (Y2) 3AX1101 1) (Y2) 3AX1101 1).
The 3AX1101 shunt release is fitted if more than one , 3AX1101 .
shunt release is required. With its design, the electrical , ,
opening command is transferred in boosted form to the , .
″Open″ latching mechanism via a solenoid armature
through unlatching of a energy store and thus the
circuit-breaker is opened.
Power consumption: <60W or <55VA : <60W <55VA
Undervoltage release (Y7) 3AX1103 1) (Y7) 3AX1103 1)
Undervoltage release consist of a stored-energy ,
mechanism, an unlatching mechanism and an , ,
electromagnet system which is connected continuously . , ,
to the supply when the circuit-breaker is in the close .
state. If this voltage drops to below a certain value the
unlatching mechanism is released and opening of the
circuit-breaker is thus initiated via the stored-energy
mechanism.

The deliberate tripping of undervoltage release


generally takes place via an NC contact in the tripping .
circuit. But it can also be carried out via an NO contact
by short-circuiting of the magnet coil. With this type of , (
tripping, the short-circuit current is limited by the built-in 4/3)
resistors (see circuit diagram Fig.3/4)

Under voltage releases can also be connected to


voltage transformers. When the operating voltage ,
drops to impermissibly low levels, the circuit-breaker is , .
tripped automatically.
Power consumption: <6.5 W or <7.5 VA
CT-Operated release (Y4) 3AX1102 1) : <6.5 W <7.5 VA
(Y4) 3AX1102 1)
CT-operated releases consist of a stored-energy
mechanism, an unlatching mechanism and an ,
electromagnet system. When the tripping current is .
exceeded (90% of the CT-operated release rated 90% , ,
current) the unlatching device of the stored-energy . ,
mechanism is released and thus opening of the circuit- .
breaker is initiated. In addition to the primary current
transformer, matching transformers are required for
application of the CT-operated releases.
Power consumption for 0.5A and 1A<6VA at 90% of
the rated current and with open armature. 0.5A 1A , 90%
, , <6VA
CT-operated release (Y6) 3AX11041)
(Low-energy release 0.1Ws) (Y6) 3AX11041)
( 0.1Ws)
In connection with a solid-state release (7SJ41
overcurrent time protection or similar) and low-power ( 7SJ41 )
primary current transformers (window-type ( ) ,
transformers), it is possible with the 3AX1104 to create 3AX1104
a CT-operated release without additional supply .
voltage.

The 3AX1104 is of similar design as the 3AX1101


/1102 releases. With its coil data and its low energy 3AX1104 3AX1101/3AX1102
requirement of < 0.1Ws, its designend to be directly . <0.1Ws ,
actuated by a release impulse provided by a capacitor
of the above-mentioned electronic release systems. .

1 1
) Can be ordered on request, retrofitting possible. ) , .
- 1/8 -

Operating Instruction Siemens 3AH3 / 3AH3


Breaker tripping signal, cut-out switches (S6 S6 S7
and S7)
When the vacuum circuit-breaker is tripped by means , S6
of a release, the position switch S6 briefly makes , . ,
contact. This contact making can be used for S7 .
signalling. In the event of intentional mechanical
tripping, the cut-out switch S7 breaks this contact.

Varistor module (V1 to V3) 3AX1526 1) (V1 to V3) 3AX1526 1)


The disconnection of inductive loads in DC circuits may
cause switching overvoltage which pose a risk to . ,
electronic control units. In order to prevent this, the ( , ,
inductances of the circuit-breaker mechanism and ( ). 3AX1526
control (motor, closing solenoid, shunt release and 60V-220V;
auxiliary contactor) can be connected to varistor (with 500V .
DC operation). For rated operating voltage of 60V to .
220V DC the varistor module 3AX1526 is available as
an accessory; it limits the overvoltage to about 500V.
The module contains 2 separate varistor circuits.

Electrical local closing/electrical interlocking1) 1


/ )
In the basic version, the closing spring must be
released mechanically if the breaker is to be closed , ,
locally. A version with electrical local closing can also . .
be supplied. In this version, the making circuit of the .
circuit-breaker is activated electrically via a push-
button. In this way, allowance can also be made for . ,
station-specific interlocks, and undesired making .
operations prevented. For example, interlocking of the
circuit-breaker is possible via the auxiliary contact of a
disconnector.
Circuit-breaker with electrical local closing cannot be
closed mechanical.

Mechanical interlocking1) .
Operating mechanism of disconnectors can be fitted
1
with a mechanical switchgear interlocking facility. The )
disconnector and the associated circuit-breaker are in .
this case interlocked mechanically. .
The sensing parts check the switch position of the
circuit-breaker and prevent if from closing mechanically
and electrically if the associated disconnector is not in , ,
a position to allow safe operation. On the other hand,
the disconnector is prevented from being operated , . ,
when the circuit-breaker is closed. , .

The mechanical interlocking facility can also be used to


interlock breaker trucks or draw-out breaker parts.
.
Adjustment instruction: 3G 460 00127 (3AX 1520-3C)

Dimensions and weight : 3G 460 00127 (3AX 1520-3C)


The dimensions and weights of the vacuum circuit-
breaker are shown in the relevant drawings.
.
For planning purposes, the drawings showing detailed
overall dimensions, can be ordered through the
appropriate Siemens agency. ,
.
The weight is also stated on the breaker rating plate.

.
1) Can be ordered on request, retrofitting possible. 1) , .
- 1/9 -

Operating Instruction Siemens 3AH3 / 3AH3


Description
Construction
The vacuum circuit-breaker consists of the mechanism (60.), 3 (19.)
housing (60.), the 3-pole assemblies (19.) with vacuum (30.), (16.1 16.2),
interrupter (30.), cast-resin post insulators (16.1and (28.) (49) (48.).
16.2), struts (28.) and of the operating rods (48.) with
contact pressure springs (49).

Each of three pole assemblies (19.) is supported by (19.) (16.1


two cast-resin post insulators (16.1and 16.2), which are 16.2) ,
bolted to the pole plate (15) respectively. (15).

The main feature of the 3AH3 vacuum circuit-breaker 3AH3 2/1.


are shown in Fig.2/1.

Fig.2/1 3AH3 vacuum circuit-breaker


.2/1 3AH3

The mechanism housing (60.) accommodates all (60.)


electrical and mechanical elements required for . .2/2 .
opening and closing the vacuum circuit-breaker. Fig.
2/2 shows the arrangement of the individual modules in
the mechanism housing.

The mechanism housing has a detachable cover 60.1( .2/3).


60.1(Fig.2/3).
This cover (60.1) has cutouts for the actuating and (60.1) .
indicating devices.
The vacuum circuit-breaker is closed by means of the (53.) . (50.4)
pushbutton (53.). The motor (50.4) immediately (62.) . ,
recharges the closing spring (62.). In the event of (50.) .
motor power supply failure, the closing spring can be (50.1), (50.2)
charged by means of a hand crank (50.). The cover (50.5). (55.)
includes an opening (50.1) for the hand crank, behind . (59.) ( - ).
which the hand crank coupling (50.5) of the gearing (58.) . (51.)
(50.2) is located. The stored-energy mechanism state (51.1) .
is shown by the indicator (55.). The indicator (59.)
shows the breaker state (ON-OFF). The operating
cycle counter (58.) indicates the number of charging
operations. The rating plate (51.) is attached to the
mechanism housing but visible through an opening
(51.1) in the cover.
The movement is transmitted to the pole assemblies (48.) .
via moulded-plastic operating rods (48.).

- 2/1 -

Operating Instruction Siemens 3AH3 / 3AH3


Fig. 2/2 View of an open mechanism housing
. 2/2

Tightening torque:10Nm
: 10Nm

Fig. 2/3 Actuating and indicating devices


. 2/3

- 2/2 -

Operating Instruction Siemens 3AH3 / 3AH3


The pole assembly (19.) consists of the upper (19.) (30.)
interrupter support (20.) with the upper terminal (27.), (27.), (29.) ,
the vacuum interrupter (30.), the lower interrupter (29.1) (29.2) (48.6).
support (40.) with the lower terminal (29.), the clamp (28.1) (28.)
(29.2) with the flexible connector (29.1) and angled ( .2/4).
lever (48.6). The centering piece (28.1) and the struts
(28.) relieve the vacuum interrupters of external forces
see (Fig. 2/4).

Fig. 2/4 3AH3 pole assembly


. 2/4 3AH3

- 2/3 -

Operating Instruction Siemens 3AH3 / 3AH3


Vacuum interrupters

The basic construction of the vacuum interrupters for 3AH3 2/6.


the 3AH3 vacuum circuit-breaker is shown in the
sectional view in Fig.2/5.

Depending on its type, the vacuum interrupter (30.) is , (30) ( )


fixed to the upper interrupter support (20.). The arcing (20.) . (33.)
chamber (33.) is located between two ceramic insulator . (31.) .
(32.). The fixed contact piece (31.) is connected (36.) (36.1) (35.)
directly with the housing. The moving contact piece (34.) .
(36.) is fixed to the terminal bolt (36.1) and is located
centrally in the guide (35.). The metal bellows (34.)
forms the vacuum-proof connection to the interrupter
housing.

Fig.2/5 vacuum interrupter


. 2/5

The vacuum interrupters fitted in the 3AH3 vacuum 3AH3 ,


circuit-breaker are type-approved in accordance with X . (
the X-ray regulations of the Federal Republic of 144 ) 5 8 DIN VDE/IEC
Germany. They conform to the requirements of the X- X .
ray regulations of January 8, 1987 (Federal LAW
Gazette Page 144) §8 and annex section 5 up to
rated short-time AC voltage stipulated in accordance
with DIN VDE/IEC.

- 2/4 -

Operating Instruction Siemens 3AH3 / 3AH3


Complement

The basic version of the vacuum circuit-breaker :


comprises:

Electrical operating mechanism (charging motor) ( )


With mechanical and electrical
anti-pumping feature (M1) (M1)
Closing solenoid (Y9) (Y9)
Shunt release (Y1) 1 (Y1)
Low-voltage plug connector, 64-pole (X0) 64 (X0)
with grommet sleeve housing
Auxiliary switch 6NO+6NC (S1) 6 +6 (S1)
Position switch for signaling
"Closing spring charged" (S41, S42) " " (S41, S42)
Breaker tripping signal, cut-out switch (S6, S7) (S6, S7)
Operating cycle counter

Each 3AH3 vacuum circuit-breaker can be equipped 3AH3 :


with the following supplementary devices:

Terminal block (X0) (X0)


Extended auxiliary switch 12NO+12NC (S1) 12 +12 (S1)
Shunt release 3AX1101 (Y2) 2 3AX1101 (Y2)
Current transformer-operated release 3AX1102 3AX1102
(Y4, Y5) (Y4, Y5)
Current transformer-operated release 3AX1104(0.1Ws) 3AX1104(0.1Ws)
(Y6) (Y6)
Undervoltage release 3AX1103 (Y7) 3AX1103 (Y7)
Electrical manual closing (S14, S15) (S14, S15)
Mechanical interlock

In addition to the standard shunt release Y1, the 3AH3 Y1 , 3AH3


vacuum circuit-breaker can be fitted with a maximum of 3AX 11.
two release of type 3AX 11

The permissible combination of supplementary HG 11.


equipment and special versions are stated in catalogue
HG 11.

- 2/5 -

Operating Instruction Siemens 3AH3 / 3AH3


Installation
Installing in cubicle or on truck
The 3AH3 vacuum circuit-breaker are supplied in the 3AH ″
open state with the ″closing spring discharged″ ″ (55.). 3AH3 ,
indication (55.) visible. Before installing the 3AH3 V- ( ).
breaker, remove the transport device (skids and
spacers). Mount face loose supplied phase barrier in
accordance with the supplied drawings.

Before installing the 3AH3 vacuum circuit-breaker in a ,


cubicle or a truck check its rating plate data (to avoid ( )
confusion) and compare the rated voltage indicated in .
the delivery papers with the power supply voltage
available at the site.

On the vacuum circuit-breaker with undervoltage (Y7) 3AX1103 ,


release (Y7) 3AX1103, the arresting screw of the A B (
hammer must be moved from position A to B (see (60.) ).
annex to operating instructions for release or note card
in mechanism housing [60.] of vacuum circuit-breaker).

On the pole plate (15.) and on the mechanism housing (15.) (60.) 14 –
(60.) there are a total of 14 fixing holes – to suit the ( .3/1). 50
various types of installation (Fig.3/1). For installation of kA .
vacuum circuit breakers with rated short circuit
breaking current > 50kA we recommend to only the
pole plate.

Use M12 fixing bolts - strength class 8 – making M1 - 8 - .


reference to the mandatory dimension drawings.

The rack or frame must be adapted to the operating


conditions and have adequate load bearing capacity . View Y/ Y
and stability.
.

* Holes for M12 bolts


* M12

Fig.3/1 Means of fixing 3AH3 vacuum circuit-breaker View Z/ Z


.3/1 3AH3
Flat bar connection
Prior to fitting the conductors fix them so as to ensure ,
smooth contact with their connecting parts and with the .
holes in full alignment.

Rub the contact faces to be bolted together with criss-


crossing strokes using a wire brush until bright metal .
shows and wipe then with a clean rag.

Note! Copper-sprayed and spray silver-plated surfaces ! .


should be cleaned a rag and not brushed. - 3/1 -

Operating Instruction Siemens 3AH3 / 3AH3


Differing contact materials (AL/CU) must not be worked ( / ) ,
with the same cleaning tool. Thinly grease the bright ( Shell 8420)
1
contact faces with acid-free Vaseline (e.g. Shell , ).
Vaseline 8420) or equivalent anti-corrosion agent and
1
bolt them together immediately ).

Note: :
Silver-plated parts must not be bolted together with .
aluminium bars.
Use the appropriate M12 nuts and bolts of strength 8 M12 ,
class 8 and corresponding spring elements and plain .
washers.

Note! When tightening the terminal screws, counteract ! , ,


the torque (70Nm~7mkp) by resisting it with a suitable 70Nm~7mkp.
spanner or socket wrench.

Control leads
Vacuum circuit-breaker of standard design are 64 X0 (68.7.1).
2
provided with a 64-pole low-voltage plug connector X0 1.5mm
(68.7.1). The corresponding plug for external , .(
connection is designed for crimp connection of control Harting 09 99 000 0110 09 99
2 2
leads with a nominal section area of 1.5mm . Use only 000 0111) ).
crimping tools (e.g. Harting crimp tongs 09 99 000 01
2
10 with positioning sleeve 09 99 000 0111) ).

Make reference to the circuit diagram supplied. .

Earthing

Connect the vacuum circuit-breaker to the appropriate (60.)


high voltage protective earth by means of the suitable M12 (70.)( .3/3)
marked M12 (70.)(see Fig.3/3) terminal on the top of ,
the mechanism housing (60.) using flat copper, copper (DIN VDE 0141/7.76 5.3).
cable or hot galvanized steel strip (DIN VDE 0141/7.76
Item 5.3).

If the V-breaker with the mechanism housing are ,


installed in an earth metal rack so that firm electrical . ( DIN
contact is established, the mechanism housing need 6789).
not be earthed separately. When installing the switch
externally, toothed serrated washers (DIN 6789) must
then be placed under the bolt heads.

Fig.3/2 70
.3/2

Circuit documents
The wiring and connection of circuit-breaker is shown ,
in the circuit diagram supplied, depending on the .
particular model and complement.

Typical circuit diagram for circuit-breaker are shown in . 3/3 3/5.


Fig. 3/3 and 3/5.
1
) Shell–Vaseline 8420, Deutsche Shell – AG Abt.
VSM Ü berseering 35, 22 297 Hamburg Postfach 60 05 55
2
) Harting Crimpzange, Harting Elektronic GmbH.
Marienwerder stra♣e3, D-32339 Espelkamp P.O.Box 11 40. - 3/2 -

Operating Instruction Siemens 3AH3 / 3AH3


Function schematic diagram

Release "off"
" "

-Y6 -Y5
-Y7

Motor drive Closing and anti- 1st shunt Switch closing spring charged signal
pumping device release tripping signal



HA Manual tripping/
Fig.3/3 V circuit-breaker 3AH3 with manual and electrical HE Manual closing/
closing with 64-way plug connector K1 Anti-pumping contactor
.3/3 , 64
3AH3 M1 Motor operating mechanism/
P Energy store/
R1 Resistor/
Tripping via S1 Auxiliary switch/
Tripping via NC NC contact S21, S22 Position switches (cut-out motor after
contact
System wiring charging)
( )
S3 Position switches
(open when closing spring charged )

( )
Breaker wiring
S41, S42 Position switch (signals charged state)
( )
S6, S7 Position switches (for switch tripped signal)
( )
X0 Low-voltage plug connector

Y1 1st shunt release/


Y2 2nd shunt release/
System wiring
Y4, Y5, Y6 CT operated release/
Y7 Undervoltage release/
Y9 Closing solenoid/
Fig.3/4 typical circuit for connection of the undervoltage release Y7 S10, S11 Position switches (mech. pumping prevention)
.3/4 Y7 ( )

- 3/3 -

Operating Instruction Siemens 3AH3 / 3AH3


Function schematic diagram

Extended auxiliary switch

Release "off"
"

-Y6 -Y5
-Y7
Electrical
manual 1st shunt 1st CT operated Switch
Motor drive Closing and anti- Closing spring charged signal
closing release release tripping signal
pumping device

Fig.3/5 V circuit-breaker 3AH3 with electrical manual closing with HA Manual tripping/
64-way plug connector HE Manual closing/
Example for extended fitting with Y4 and varistor circuit for DC K1 Anti-pumping contactor
.3/5 64 3AH3
Y4
M1 Motor operating mechanism/
P Energy store/
R1 Resistor/
S1 Auxiliary switch/
S21, S22 Position switches (cut-out motor after charging)
With this model, the auxiliary switch terminals are wired to the plug connector as illustrated
( )
S3 Position switches
(open when closing spring charged )
Auxiliary switch standard Auxiliary switch extended
( )
S41, S42 Position switches (signals charged state)
( )
S6, S7 Position switches (for switch tripped signal)
( )
X0 Low-voltage plug connector

Y1 1st shunt release/


Y2 2nd shunt release/
Y7 Y4, Y5, Y6CT operated release/
Y9 Y7 Undervoltage release/
D7 B3 B8 C5 D8 D9 B9 C9 Y9 Closing solenoid/
S10, S11 Position switches (mech. pumping prevention)
Wiring not applicable if ( )
B Y2 (2nd shunt release) fitted B 2 Y2
E Y7 (undervoltage release) fitted E Y7 - 3/4 -

Operating Instruction Siemens 3AH3 / 3AH3


! DANGER !
High voltage! !
Touching of live will result in death or severe .
personal injury.

This equipment shall be operated only by


qualified personnel after becoming thoroughly .
familiar with the respective instruction manual
and in particular all safety instructions.

! WARNING !
This equipment contains hazardous voltages ,
and mechanical parts which move at high .
speed and may be control remotely.

Non-observance of the safety instructions .


can result in severe personal injury or
property damage.

In particular: :
Do not remove the cover (60.1). Do not reach (60.1).
inside any openings in the operating mecha- .
nism. Dot not touch pole assemblies(19.) (19.) (48.).
and operating rods (48.).

Commissioning

Prior to commissioning, check the V-breaker in accordance :


with the following points:

1. Clean them as applicable (for details refer to ″cleaning″ 1. ( ″ ″ 5/1.).


page 5/1.).
2. Check all fixing and terminal screws for tightness. 2. .
3. Examine the circuit-breaker for any external damage, 3. , ,
especially to the control leads, post insulators .
and interrupters.

! CAUTION !
The V-breaker may be operated only with the ,
original hand crank (50.), in order to avoid (50.).
injures as a result of the motor suddenly
starting up.

4. Charge the closing spring (62.) with the hand crank (50.) 4. (50.) (62.) ( .4/1), ″ ″
(see Fig.4/1), press the ″close″ push-button (53.) and (53.), , ″ ″ (54.) .
after closing, trip the breaker by pressing the ″open″
push-button (54.).

On the 3AH3 V-breaker with undervoltage release (Y7) 3AX1103 3AH3 ,


(Y7) 3AX1103, the arresting screw of the hammer A B ( 3AH3
must be moved from position A to B (see note card in ).
mechanism housing [60.] of 3AH3 vacuum circuit-
breaker)

- 4/1 -

Operating Instruction Siemens 3AH3 / 3AH3


5. For test operations with the motor mechanism switch on 5. ,
the supply voltage. The motor will start immediately and (62.) .
charge the closing spring (62.). check the mechanical . 4 ,
and electrical indication of the charging state of the .
closing spring. Actuate the mechanism as indicated
under 4. And check the mechanical and electrical state
indication.

6. Check the auxiliary switch S1 (68.) and position switches 6. 3AH3 , S1 (68.)
(50.4.1) electrically in both end positions by actuating the (50.4.1) .
3AH3 vacuum circuit-breaker.

7. Also check-by electrical actuation – the function of the 7. Y9 (53.1)


closing solenoid Y9 (53.1) and all fitted shunt release. .

When correct functioning of the 3AH3 V-breaker has been 3AH3 , .


ascertained it can be put into service.

Charging the closing spring


When the supply voltage is applied the motor (50.4) , (50.4) (62.) .
automatically charges the closing spring (62.). Should , (50.) . ,
the supply fail the closing spring (62.) can also be charged by .4/1 , (50) (50.6) (50.1)
hand crank (50.). In the lattercase, as shown in Fig.4/1,the (50.5) , (55.3)
hand crank(50.) is inserted with the forwards pushed adapter ( .4/2
(50.6) through the opening (50.1) onto hand crank coupling ).
(50.5) and turned clockwise, until the symbol "closing spring
discharged shown in the indicator opening (55.3) is
changed to "closing spring charged (Fig. 4/2).

Fig.4/1 Charging the closing spring with the hand crank


4/1
The adapter (50.6) is designed so that the hand crank (50.) is
decoupled on the recovery of the motor supply. (50.6)
.

Fig.4/2 ∀Closing spring discharged∀



″ Fig.4/2 ∀Closing spring charged∀

Closing

If operation is not blocked by the mechanical interlock, press


the ∀close∀ push-button (53.) or the corresponding control , ″ ″ (53.)
switch until the 3AH3 vacuum circuit-breaker closes and both 3AH3
indicates and signals this state. .

After closing (and, if applicable, releasing of the ∀close∀


push-button (53.) the closing spring (62.) is immediately and (∀ ∀ (53.) ), (62.)
automatically recharged the "closing spring charged (55.) ,
and indication becomes visible once again. (55.).

Tripping

The opening spring (64.) is charged during closing. (64.) .

To trip the breaker press the ∀open∀ push-button (54.) or (54.)


corresponding control switch until the V-breaker trips and .
both indicates and signals this state. - 4/2 -

Operating Instruction Siemens 3AH3 / 3AH3


Maintenance

Safety measure

! DANGER !
Maintenance, repair and subsequent conver- ,
sion work may be carried out only by specially .
trained personnel in accordance with the
operating instructions and/or special
conversions instructions. Training and
information sessions for personnel can be
provided by the competent Siemens
department
before starting any work on V-breakers, ,
reference must be made to the local safety , (DIN VDE 0105/07.83
regulations for high-voltage switchgear, e.g. 9 , 1 ).
the five safety rules (DIN VDE 0105/07.83 ( "
Part 1, Item 9). Switch off the power supply " ).
and then close and open the V-breaker by
hand ( V-breaker in open state "closing spring
discharged" indication visible).

Non-observation can result in death, severe .


personal injure or substantial property
damage.

Servicing

Under normal operating conditions, the 3AH3 vacuum , 3AH3 ,


circuit-breaker is maintenance-free. We recommend .
nonetheless a regular visual inspection.

Cleaning
To ensure the insulating capacity, it is necessary that . .
the insulating components are clean. Insulating .
components and external breaker parts must be wiped .
with a damp cloth. Use only warm water with the
addition of a mild liquid household detergent as
cleaning agent.

! WARNING !
Windings and terminals must not be touched ,
if the power supply has not been disconnect- .
ed.
Non-observance can result in death or
serious personnel injury.

! CAUTION !
All springs of the operating mechanism must ,
be relaxed and the vacuum circuit-breaker ,"
be brought into the open state, "closing spring " .
discharged" indication visible.
Non-observance can result in personnel injury. .

- 5/1 -

Operating Instruction Siemens 3AH3 / 3AH3


Abnormal conditions

If the 3AH3 vacuum circuit-breaker is used in 3AH3 ,


abnormally unfavourable indoor conditions (e.g. ( ).
frequent heavy condensation, dust-ridden air etc). , .
We recommend regular cleaning of the breaker .
external components and, if necessary, renewal of the
anti-corrosion protection. Only the following products
may be used for the respective working parts of the
VCB.

Bearing, sliding surface: , :


Isoflex Topas L32 Isoflex Topas L32
Klber- Lubrication KG Klber- Lubrication KG
Geisenhausener Stra♣e 7 Geisenhausener Stra♣e 7
Postfach 70 10 47 Postfach 70 10 47
81379 Munich 81379 Munich
Federal Republic of Germany Federal Republic of Germany

Bearings inaccessible to grease and bearings of the S1 :


auxiliary switch S1:
SHELL Tellus Oil 32 SHELL Tellus Oil 32
SHELL Oil trade company GmbH SHELL Oil trade company GmbH
Zitadellenstra♣e 5 Zitadellenstra♣e 5
P.O.Box 900915 P.O.Box 900915
21079 Humburg 21079 Humburg
Federal Republic of Germany Federal Republic of Germany

Joints and bearings which cannot be dismantled must


not be treated with a cleaning agent prior to .
reapplication of anti-corrosives.

After renewal of the anti-corrosion protection, several ,


mechanical test-switching operations should be .
performed on the vacuum circuit-breaker.

Lubricants (for special conditions) are available from ( )


the Siemens agent responsible: :

Order No
180 g Klber-Isoflex Topas L32 3AX1133-3A 180 g Klber-Isoflex Topas L32 3AX1133-3A
and 50 g SHELL Tellus Oil 32 and 50 g SHELL Tellus Oil 32

180 g Klber-Isoflex Topas L32 3AX1133-3H 180 g Klber-Isoflex Topas L32 3AX1133-3H

50 g SHELL Tellus Oil 32 3AX1133-2G 50 g SHELL Tellus Oil 32 3AX1133-2G

1kg SHELL Tellus Oil 32 3AX1133-2D 1kg SHELL Tellus Oil 32 3AX1133-2D

1kg Klber-Isoflex Topas L32 3AX1133-3E 1kg Klber-Isoflex Topas L32 3AX1133-3E

- 5/2 -

Operating Instruction Siemens 3AH3 / 3AH3


Checking the contact system
The contact system is subject to wear both by contact .
erosion and by compression of the contact pieces and , (30.)
the guide bolts. To check the contact wear, the moving (13.9) ( . 5/1).
terminal bolt (36.1) of the vacuum interrupter (30.) is ,
provided with the checking marking (13.9) Fig. 5/1. As .
long as the marking is wholly or partially visible when
the 3AH3 vacuum circuit breaker is closed, the
shortening of the contacts is within permissible range.

Fig.5/1 Check mark

Checking the vacuum

Such a check should be made if there is any risk of an , .


interrupter having developed a leak. Busbar and cable . .
connections must be split. The check is performed with .
an HV test unit. If necessary, further information may
be obtained from the appropriate Siemens Regional
Office.

- 5/3 -

Operating Instruction Siemens 3AH3 / 3AH3


Service life of vacuum interrupter

The maximum permissible number of mechanical 10,000 .


operating cycles is 10,000. The permissible number of .5/2.
operating cycles as a function of the breaking current is ,
shown in Fig.5/2. When this permissible maximum has / .
been attained, the interrupters or the complete pole
assemblies must be renewed. Detailed instructions are
supplied with the replacement interrupters/pole
assemblies.

When ordering replacement interrupters or pole / , ,


assemblies, state the circuit-breaker type, design code ( ).
and serial number (see name plate)

Determination of the load characteristic number/

Rated voltage Rated short-circuit breaking current Load characteristic number at rated normal current

kV kA 1250A 2000A 2500A 3150A 4000A


7.2 50 1 - 1 1 -
63 2 - 2 2 2
12 50 1 1 1 -
63 2 2 2 2
15 50 1 - 1 1 -
63 2 - 2 2 2
17.5 50 1 - 1 1 -
63 2 - 2 2 -
24 40 - - 3 -

36 31.5 4 4 4 - -
40 5 5 5 -
Number of breaking operations/

Number of breaking operations/

Breaking current I (kA)/ (kA) Breaking current I (kA)/ (kA)

Fig.5/2 Permissible number of operating cycle as a function of breaking current Ia


5/2 Ia
- 5/4 -

Operating Instruction Siemens 3AH3 / 3AH3


Accessories and spare parts

3AX 1530-2B :
A hand crank 3AX 1530-2B for charging the closing
spring can be supplied as an accessory:
,
Owing to the fact that all parts of this breaker type have ,
been optimized to the last the normal service life, it is .
not possible to recommend particular spare parts for
keeping in stock.
:
When ordering spare part state the following: 1. 3AH3 , ( ).
1. Type designation, design code and serial number
of the 3AH3 vacuum circuit-breaker (see rating
plate) 2. ,
2. The designation and part number, making , .
reference to illustrations in these operating
instructions or to a photograph or sketch as
applicable. Alternatively, a sample may be
submitted.

Published by the
Power Transmission and Distribution Group
Schaltwerk Berlin Schaltwerk

Translated by
SLC PTD MC
Edition 1/March 2001 1/03/2001

Subject to change

- 5/5 -

Order No. / : 3ZX1812-0AH30-0AN1 / 9229 9860 174 –SLC PTD MC


Operating Instruction Siemens 3AH3 / 3AH3 Place of order / : SLC PTD MC ShangHai