Manufacturer T2 Electrical & Data 22. IP20 is required for all switchgear and live parts.
Standards AS 3000, AS 3439.1 23. Provide warning labeling on doors and removable covers which provide
Current & Frequency AC 50Hz direct access to live busbars.
Rated Operational Voltage Ue 415 VAC
Rated Insulation Voltage Ui 0.6 / 1 kV BUSBARS
Rated Control Voltage 240 VAC 24. Busbars to be hard drawn, high conductivity, natural finish, insulated in 100
Rated Current 400 A air.
20 250 20
Short Circuit Current Isc 10kA for 1 sec 25. IP20 shrouding required in sections containing switchgear.
Degree of Protection IP56 26. Phase and neutral to be minimum 1x20x10mm Cu 220
Internal Degree of Protection IP2x 27. Earth to be minimum 1x20x10mm Cu
Service Conditions Outdoors 20
PAINTING
18. Finish smooth all exposed welds, clean, descale, and degrease all
surfaces.
19. Paint Type, 40 Micron Minimum thickness polyester powdercoat and to
manufacturer's recommendations.
20. Cubicle exterior, interior & external components: No.4 finish
21. Interior items (mounting panels, hat sections, escutcheons): bright white.
Contractor Client