Resisting System (MWFRS) of Low-Rise Buildings stated in Section 207C.4 of National Structural Code of the Philippines (NSCP) 2015.
Design wind pressure for low-rise buildings shall be
determined by the equation 207C.4-1,
𝐩𝐰 = 𝐪𝐡 [(𝐆𝐂𝐩𝐟 ) − (𝐆𝐂𝐩𝐢 )] (𝐍⁄ 𝟐 )
𝐦 where: o qh : velocity pressure evaluated on the mean roof height of the building and it is determined by the equation 207C.3-1. o GCpf : external pressure coefficient o GCpi : internal pressure coefficient
1. Velocity pressure (qh) shall be determined by the
equation 207C.3-1 of NSCP 2015, 𝐪𝐡 = 𝟎. 𝟔𝟏𝟑𝐊 h 𝐊 𝐳𝐭 𝐊 𝐝 𝐕 𝟐 where:
o Kh : velocity pressure coefficient given
by Table 207C.3-1 of NSPC 2015. Linear interpolation for the values of Kh is permitted by the code.
Height Above Exposure Category
Ground Level B 12.20 M. 1.04 13.50 M. Kh = 1.062 15.20 M. 1.09