Professional Documents
Culture Documents
College of Architecture
2nd Term A.Y. 2018-2019
Building Utilities
Research by
CHEN, Maria Jennifer B.
MANALAD, Bianca Mari
NEPOMUCENO, Maria Anika
PADILLON, Christine
2AR 1
Each fire detection and alarm system therefore must be specifically designed to meet the
requirements for each building type. In designing a system particular consideration must be given
to the type of building, its construction and the purpose for which it is being used, so that in the
event of a fire, the fire detection system, combined with appropriate fire prevention procedures,
will keep fire risk to a minimum.
As provided in the Fire Code of the Philippines, RA 9514 divisions 8 through 17, activation of the
complete fire alarm system shall be initiated by, but not be limited to, any or all of the following
means of initiation;
A. Manual Initiation
B. Automatic Detection
C. Extinguishing System Operation
SYSTEM ELEMENTS
Detection systems today vary in the complexity of detection and signal equipment. The design,
installation, and approval of a fire detection and alarm system may also require acceptance testing
by regulatory agencies before new buildings are occupied or the system is placed in service. The
system is comprised of several elements such as:
1. Reliable Power Supply
a. Primary
b. Secondary
2. Fire Alarm Control Panel
3. Initiative Devices (Inputs)
4. Notification Appliances (Outputs)
5. Auxiliary Functions (Outputs)
In some modern FACP, it can provide public service announcements through prerecorded
evacuation messages.
INITIATING DEVICES
A fire detection system consists of manual and automatic alarm-initiating devices. These devices
are activated by the presence of smoke, flame, fire, or heat. The device the send the signal to the
fire alarm controlling panel (FACP), operated by either of these methods: hard-wire system or a
generated signal conveyed by radio wave over a special frequency to a radio receiver in the panel.
The IFSTA has classified alarm-initiating devices into two; manual and automatic initiation. The
manual initiation requires human interaction as it is activated by pull station or from central point.
On the other hand, the automatic initiation requires no human interaction as it employs detection
devices and it sets a sequence of events in motion. Both automatic and manual alarm initiating
devices include:
1. Manual pull stations
2. Smoke detectors 4. Flame detectors
3. Heat detectors 5. Waterflow devices
NOTIFICATION APPLIANCES
In the event that an alarm-initiating device send a signal to the FACP, it then processes the signal
and initiates the action. Normally, the primary action initiated is usually local notification. This
usually take the form of bells, buzzers, speakers, and the like. Depending on the design of the
system, the local alarm may trigger a single notification appliance or a notification appliance
within a specific zone. These notification appliances are categorized into the following:
● Audible
Most common type used for signaling a fire alarm. This makes use of Philippine
Fire Code approved sounding devices such as horns, bells, or speaker, all of which
indicate a fire or an emergency situation.
● Visual
This makes use of Philippine Fire Code approved lighting devices such as, strobes
or flashing lights that indicate a fire or emergency situation.
● Textual
Visual text or symbols that indicate a fire or emergency situation.
● Tactile
Indication of a fire or emergency condition through sense of touch or vibration.
Fire detection and alarm systems are designed to receive signals from devices and to perform an
action based on the signal received (Fig. 1). Some signals may indicate a fire condition, while
others may indicate that a device on the system needs to be serviced. The FACU should be
programmed to respond to different signal types in an appropriate manner. Fire detection and alarm
systems are equipped with three types of specialty signals, depending on the type and nature of the
alarm they are reporting
ALARM
SIGNAL
An
alarm signal is a
warning of a fire emergency demanding immediate response or attention. The Philippine Fire code
requires alarm signals from systems monitored by a supervising station to notify the responding
fire department (Fig 2). Activation of smoke detectors, manual pull stations, waterflow switches,
and other fire extinguishing systems are all initiating devices that send fire alarm signals.
SUPERVISORY SIGNAL
According to the IFSTA, a supervisory signal indicates an off-normal condition of the
complete fire protection system. Supervisory signals also include a returned-to-normal signal,
meaning that the condition has been resolved. These signals are used to monitor the integrity of
the fire protection features of the system.
TROUBLE SIGNAL
A trouble signal indicates a problem with a monitored circuit or component of the fire
alarm system or the system’s power supply. Each signal must be audibly and visually displayed at
the FACU in a distinct manner that differentiates one type of signal from another. Trouble
conditions include loss of primary power or failure or removal of an initiating device, such as a
smoke detector.
PROTECTED PREMISES SYSTEM (LOCAL)
Protected premises systems is the system is inside the walls of the property, not transmitting
signals to a central alarm point, either on the property or off premises. Protected premises systems
can be interfaced with any other type of fire alarm or fire safety system, such as elevator recall,
and can be provided with emergency voice alarm systems for occupant notification. The level of
requirements that have to be met by the protected premises system is determined by reference to
other codes and standards, such as the local building code requirements.
CONVENTIONAL ALARM SYSTEMS
Conventional panels are no longer used frequently in large buildings, but are still used on
smaller sites such as small schools, stores, restaurants, and apartments. A conventional system uses
one or more initiating circuits, connected to sensors (initiating devices) wired in parallel (Fig.5).
These sensors are devised to decrease the circuits resistance when the environmental influence on
any sensor exceeds a predetermined threshold. In a conventional system the information density is
limited to the number of such circuits used.
Fig.
5 Diagram showing the parallel connection of a conventional system
HYBRID SYSTEM
According do the National Fire Protection Association (NFPA), a hybrid system has a
combination of features from both the conventional and addressable alarm systems (Fig.7). In
practice, it can either be built from a basic conventional system with add-on hardwire
addressable features or built from an addressable system with a conventional module and event
recording and alarm management event recording and alarm management feature feature.
Fig. 7 Typical hybrid fire alarm system configuration Fig. 8
Conventional with addressable add-on
In comparing the three alarm systems available in use today, conventional are more cost efficient
to buy, however, the installation is expensive as each device is connected to the control panel
through its own wire, as opposed to a shared one in an addressable system. With addressable
systems, one wire loop will connect several devices. This means conventional systems require
more wire and more man hours during the installation phase.
Overall the addressable alarm system is also the more reliable of the two. This is because the
wire connects to the control panel at both ends (Fig. 10). This means that If one end of the loop
becomes severed, signals can still be sent to the control panel via the other end of the loop. Loop
isolation modules are also used to separate devices on the loop. This means that if one device
becomes disconnected, it won’t disable the circuit. With a conventional system, if a wire has
become severed, the device will become disconnected.
Fig. 10 Wire connection diagram of the alarm systems
PROPRIETARY SYSTEM
Proprietary station fire alarm systems are used by owners of properties that want to control
the fire alarm signaling systems themselves. Basically, the owner establishes the fire alarm
monitoring station in one of their properties and connects all of their buildings to that system. The
properties can be in the same geographic area, in different areas, or in a large single building or
campus, such as a high-rise structure or college campus.
False alarms can be due to several unwanted factors such as: environmental influence, fire
like phenomena, being set by the people in the building, accidental damage, and most commonly,
faulty equipment. All these can be prevented if the system design takes into account of the
guidance provided the Code of Practices. The Code dictates the standards to be followed by the
designer. Locally, we have RA 9514 which is the Fire Code of the Philippines and the Philippine
Electric Code as the standard for system designs. It is also important to note that the building owner
and users are responsible to engage with reputable manufacturers and contractors.
To reduce the effects of transient environmental conditions which may cause various types
of detectors to be activated, an automatic fire alarm system may be provided with an alarm
verification feature, subject to the approval of the relevant authority.The provision of following
components of the fire alarm system shall not be subject to this feature;
International Fire Service Training Association. (n.d.). Fire Inspection and Code
Clary, S. (May 8 2018). Psa - Public Emergency Alarm Systems retrieved from
https://www.securitysales.com/columns/psa-public-emergency-alarm-systems/
Hughes, J. (n.d.) Remote and Protected Premises Fire Alarm Systems retrieved from
https://www.jensenhughesacademy.com/catalog/product/remote_station_and_protected_p
remises_fire_alarm_systems