Project:

ETAP Page: 1
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard


3-Phase, LG, LL, & LLG Fault Currents

Swing V-Control Load Total


Number of Buses: 1 0 26 27

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 15 0 0 0 0 13 28

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of Machines: 6 0 0 0 12 18

System Frequency: 50.00 Hz

Unit System: Metric

Project Filename: tania wulandari

Output Filename: C:\tania wulandari (2015-11-054)\modul 3\tania wulandari\load flow\tania


wulandari\Untitled.SI2
Project:
ETAP Page: 2
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project:
ETAP Page: 3
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 Load 150.000 150.000 1 100.00 30.00

Bus2 Load 20.000 20.000 1 100.00 0.00

Bus3 Load 20.000 20.000 1 100.00 0.00

Bus4 Load 20.000 20.000 1 100.00 0.00

Bus5 Load 0.400 0.400 1 100.00 -30.00

Bus10 Load 20.000 20.000 1 100.00 0.00

Bus11 Load 20.000 20.000 1 100.00 0.00

Bus12 Load 20.000 20.000 1 100.00 0.00

Bus13 Load 0.400 0.400 1 100.00 -30.00

Bus14 Load 20.000 20.000 1 100.00 0.00

Bus15 Load 20.000 20.000 1 100.00 0.00

Bus16 Load 20.000 20.000 1 100.00 0.00

Bus17 Load 0.400 0.400 1 100.00 -30.00

Bus18 Load 20.000 20.000 1 100.00 0.00

Bus19 Load 20.000 20.000 1 100.00 0.00

Bus20 Load 20.000 20.000 1 100.00 0.00

Bus21 Load 0.400 0.400 1 100.00 -30.00

Bus22 Load 20.000 20.000 1 100.00 0.00

Bus23 Load 20.000 20.000 1 100.00 0.00

Bus24 Load 20.000 20.000 1 100.00 0.00

Bus25 Load 0.400 0.400 1 100.00 -30.00

Bus26 Load 20.000 20.000 1 100.00 0.00

Bus27 Load 20.000 20.000 1 100.00 0.00

Bus28 Load 20.000 20.000 1 100.00 0.00

Bus29 Load 0.400 0.400 1 100.00 -30.00

Bus30 Load 150.000 150.000 1 100.00 30.00

Bus31 SWNG 0.400 0.400 1 100.00 0.00

27 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project:
ETAP Page: 4
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift


ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

T1 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T2 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T5 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T6 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T7 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T8 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T9 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T10 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T11 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T12 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T13 0.630 150.000 20.000 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T14 0.630 20.000 0.400 4.00 1.50 0 0 0 0 0 4.0000 Dyn 30.000

T15 2.000 150.000 0.400 6.25 6.00 0 0 0 0 0 6.2500 Dyn 30.000

T17 2.000 150.000 0.400 6.25 6.00 0 0 0 0 0 6.2500 Dyn 30.000

T18 2.000 150.000 0.400 6.25 6.00 0 0 0 0 0 6.2500 Dyn 30.000

2-Winding Transformer Grounding Input Data

Grounding

Transformer Rating Conn. Primary Secondary


ID MVA Prim. kV Sec. kV Type Type kV Amp Ohm Type kV Amp Ohm

T1 0.630 150.000 20.000 D/Y Solid

T2 0.630 20.000 0.400 D/Y Solid

T5 0.630 150.000 20.000 D/Y Solid

T6 0.630 20.000 0.400 D/Y Solid

T7 0.630 150.000 20.000 D/Y Solid

T8 0.630 20.000 0.400 D/Y Solid

T9 0.630 150.000 20.000 D/Y Solid

T10 0.630 20.000 0.400 D/Y Solid

T11 0.630 150.000 20.000 D/Y Solid

T12 0.630 20.000 0.400 D/Y Solid

T13 0.630 150.000 20.000 D/Y Solid

T14 0.630 20.000 0.400 D/Y Solid

T15 2.000 150.000 0.400 D/Y Solid


Project:
ETAP Page: 5
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

2-Winding Transformer Grounding Input Data

Grounding

Transformer Rating Conn. Primary Secondary


ID MVA Prim. kV Sec. kV Type Type kV Amp Ohm Type kV Amp Ohm

T17 2.000 150.000 0.400 D/Y Solid

T18 2.000 150.000 0.400 D/Y Solid


Project:
ETAP Page: 6
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus1 Bus2 360.83 541.25 650.50

T2 2W XFMR Bus4 Bus5 344.43 516.65 620.93

T5 2W XFMR Bus1 Bus10 360.83 541.25 650.50

T6 2W XFMR Bus12 Bus13 344.43 516.65 620.93

T7 2W XFMR Bus1 Bus14 360.83 541.25 650.50

T8 2W XFMR Bus16 Bus17 344.43 516.65 620.93

T9 2W XFMR Bus1 Bus18 360.83 541.25 650.50

T10 2W XFMR Bus20 Bus21 344.43 516.65 620.93

T11 2W XFMR Bus1 Bus22 360.83 541.25 650.50

T12 2W XFMR Bus24 Bus25 344.43 516.65 620.93

T13 2W XFMR Bus1 Bus26 360.83 541.25 650.50

T14 2W XFMR Bus28 Bus29 344.43 516.65 620.93

T15 2W XFMR Bus30 Bus31 49.42 296.51 300.60

T17 2W XFMR Bus30 Bus31 49.42 296.51 300.60

T18 2W XFMR Bus30 Bus31 49.42 296.51 300.60

CB1 Tie Breakr Bus2 Bus3

CB2 Tie Breakr Bus3 Bus4

CB5 Tie Breakr Bus10 Bus11

CB6 Tie Breakr Bus11 Bus12

CB7 Tie Breakr Bus14 Bus15

CB8 Tie Breakr Bus15 Bus16

CB9 Tie Breakr Bus18 Bus19

CB10 Tie Breakr Bus19 Bus20

CB11 Tie Breakr Bus22 Bus23

CB12 Tie Breakr Bus23 Bus24

CB13 Tie Breakr Bus26 Bus27

CB14 Tie Breakr Bus27 Bus28

CB15 Tie Breakr Bus1 Bus30


Project:
ETAP Page: 7
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Synchronous Generator Input Data


% Impedance in Machine Base
Synchronous Generator Rating Xd" Grounding Excitation
ID Type MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Conn. Type Amp Type

Gen1 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Gen2 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Gen3 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Gen4 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Gen5 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Gen6 Turbo 1.176 0.400 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Total Connected Synchronous Generators ( = 6.00 ) : 7.059 MVA


Project:
ETAP Page: 8
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Lumped Load Input Data

Motor Loads
Lumped Load % Impedance
Lumped Load Rating % Load Loading Machine Base Grounding mFact.
ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" Conn. Type Amp MW/PP
Lump1 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump2 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump5 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump6 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump7 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump8 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump9 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump10 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump11 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump12 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump13 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Lump14 50.0 20.000 0.00 85.00 80 20 34.00 21.07 2.47 16.48 0.15 Delta 0.03

Total Connected Lumped Loads ( = 12 ): 600.0 kVA


Project:
ETAP Page: 9
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus1


Nominal kV = 150.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus1 Total 0.00 0.130 0.00 173.21 173.21 0.000 0.000 2.96E+001 3.23E+002

Bus2 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus10 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus14 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus18 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus22 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus26 Bus1 3.04 0.002 100.00 100.00 100.00 0.000 0.000 3.45E+003 2.11E+004

Bus31 Bus30 28.07 0.040 100.00 100.00 100.00 0.000 0.000 9.00E+001 1.07E+003

Bus31 Bus30 28.07 0.040 100.00 100.00 100.00 0.000 0.000 9.00E+001 1.07E+003

Bus31 Bus30 28.07 0.040 100.00 100.00 100.00 0.000 0.000 9.00E+001 1.07E+003

Lump1 Bus2 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump2 Bus3 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus5 Bus4 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Lump5 Bus10 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump6 Bus11 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus13 Bus12 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Lump7 Bus14 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump8 Bus15 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus17 Bus16 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Lump9 Bus18 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump10 Bus19 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus21 Bus20 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Lump11 Bus22 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump12 Bus23 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus25 Bus24 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Lump13 Bus26 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Lump14 Bus27 100.00 0.007 100.00 100.00 100.00 0.000 0.000 6.18E+003 4.12E+004

Bus29 Bus28 3.04 0.000 100.00 100.00 100.00 0.000 0.000

Gen1 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002
Project:
ETAP Page: 10
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

(Cont.)

Fault at bus: Bus1


Nominal kV = 150.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Gen2 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002

Gen3 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002

Gen4 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002

Gen5 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002

Gen6 Bus31 100.00 7.412 100.00 100.00 100.00 0.000 0.000 8.11E+001 1.54E+003 8.11E+001 5.68E+002

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.130 0.000 0.115 0.115
Peak Current (kA), Method C : 0.326 0.000 0.287 0.287
Breaking Current (kA, rms, symm) : 0.000 0.115 0.115
Steady State Current (kA, rms) : 0.119 0.000 0.115 0.115

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 11
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus2


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus2 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Bus1 Bus2 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump1 Bus2 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Lump2 Bus3 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus5 Bus4 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus18 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 12
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus4


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus4 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Bus5 Bus4 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Lump2 Bus3 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus1 Bus2 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump1 Bus2 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus18 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 13
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus11


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus11 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Lump6 Bus11 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus13 Bus12 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Bus1 Bus10 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump5 Bus10 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus2 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus18 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 14
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus18


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus18 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Bus1 Bus18 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump9 Bus18 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Lump10 Bus19 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus21 Bus20 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Bus2 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 15
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus19


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus19 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Lump10 Bus19 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus21 Bus20 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Bus1 Bus18 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump9 Bus18 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus2 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 16
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus20


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus20 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Bus21 Bus20 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Lump10 Bus19 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus1 Bus18 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump9 Bus18 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus2 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus22 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 17
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Fault at bus: Bus23


Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus23 Total 0.00 0.348 0.00 90.69 99.28 0.387 0.387 3.64E+002 8.37E+002 3.61E+002 5.41E+002

Lump12 Bus23 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus25 Bus24 0.00 0.000 57.32 52.36 99.82 0.000 0.000

Bus1 Bus22 68.24 0.333 78.70 99.80 87.60 0.376 0.387 * 3.90E+002 8.70E+002 3.61E+002 5.41E+002

Lump11 Bus22 100.00 0.008 100.00 100.00 100.00 0.006 0.000 6.18E+003 4.12E+004

Bus2 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus10 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus14 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus18 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus26 Bus1 69.29 0.001 77.74 90.77 98.63 0.000 0.000 2.68E+004 8.45E+002

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

Bus31 Bus30 77.22 0.014 83.59 93.11 98.82 0.009 0.000 1.34E+003 6.18E+001

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.348 0.387 0.302 0.387
Peak Current (kA), Method C : 0.636 0.707 0.553 0.708
Breaking Current (kA, rms, symm) : 0.387 0.302 0.387
Steady State Current (kA, rms) : 0.325 0.387 0.302 0.387

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 18
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground

ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus1 150.000 0.130 0.326 0.119 0.000 0.000 0.000 0.000 0.115 0.287 0.115 0.115 0.115 0.287 0.115 0.115
Bus2 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus4 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus11 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus18 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus19 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus20 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387
Bus23 20.000 0.348 0.636 0.325 0.387 0.707 0.387 0.387 0.302 0.553 0.302 0.302 0.387 0.708 0.387 0.387

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project:
ETAP Page: 19
12.6.0H
Location: Date: 13-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: tania wulandari Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus1 150.000 66.49774 727.40640 730.43960 91.46928 701.92250 707.85720 0.00000 0.00000 0.00000

Bus2 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus4 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus11 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus18 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus19 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus20 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000

Bus23 20.000 14.56431 33.48603 36.51621 14.99503 33.06860 36.30955 14.43334 21.65002 26.02008 0.00000 0.00000 0.00000