You are on page 1of 5

CCM3

5 motores de 50 Hp a 480 volts L=30 mts


Tabla 430 – 150 pag. 26
37.3 KW = 50Hp , 65 A
In cond=1.25 x 65A = 81.25 A = IC
Tabla 310 – 16 a 60°C
Pag. 98  #2
81.25 𝐴
If= = 90.277 A
0.9
(2)(480)
Zc= (173)(65)(0.03) = 2.8457 𝑜ℎ𝑚𝑠
(173)(65)(0.03)(2.3)
e%= = 1.61%
480

Conductor seleccionado cal. #8 pag.4


Ip = (2.5)(65A) = 162 A 3P x 152A
1 – 2  1 x 86 = 86  pag. 1
3 – 8  3 x 28.19 = 84.57  pag. 1
86 + 84.57 = 170.57
Pag. 18  2 cond. Fr = 31%
27 (1)
T = 27 mm (1)
CCM3
5 motores de 40 Hp a 480 Volts con L = 30 mts
Tabla 430 – 150 de la pag. 26
29.8 KW = 40 Hp , In = 52 A
I cond = 1.25 x 52 A = 65 A = Ic
65𝐴
If = = 70.21 𝐴
0.9

Tabla 310 – 16 a 60°C


Pag 98  #4
(2)(480)
Zc = (173)(52)(0.03) = 3.557 𝑜ℎ𝑚𝑠

(173) (52) (0.03)(2.3)


e% = = 1.2931%
480

Conductor seleccionado Cal. # 8 de la pag. 4


IP = 2.5 x 52 A = 130 A 3P x 130 A
1 – 4  1 x 62.77 = 62.77  pag. 1
3 – 8  3 x 28.19 = 84.57  pag. 1
62.77 + 84.57 = 147.34
Pag. 18  2 cond = Fr = 31%
27 (1)
T = 27 mm (1)
CCM4
2 motores de 50 Hp a 480 volts con L = 40 mts
Tabla 430 – 150 de la pag. 26
37.5 KW = 50 Hp , 65 A
1.25 𝑥 65 𝐴
In cond = = 81.25 𝐴 = 𝐼𝑐
1.0 𝑥 1.0

Tabla 310 – 16 a 60 °C
Pag. 98  #2
81.25𝐴
If = = 90.277 𝐴
0.9
𝑒% (𝑉𝑓) (2)(480)
Zc = (173)(𝐼𝑛)(𝐿) = (173)(65)(0.04)
= 2.134 𝑜ℎ𝑚𝑠
(173)(65)(0.04)(1.48)
e% = = 1.38%
480

Conductor seleccionado Cal.#16 pag.4


Ip = 2.5 x 65 A = 162.5 A 3P x 162A
1-2 1 x 86 = 86  pag. 1
3-6  3 x 46.84 = 140.52  pag. 1
86 + 140.52 = 276 .52
Pag. 18  2 conductores, Fr = 31%
1-2 y 3-6, #1 y #6 dos tipos diferentes de conductores.
35 (1)
T = 35 mm (1)
CCM4
2 motores de 100 Hp a 480 volts con L = 40 mts
Tabla 430 – 150 Pag. 26
100 Hp = 75 KW , In = 124 A
In cond = 1.25 x 124 A = 155 A = Ic
155
If = = 164.84 𝐴
0.94

Pag. 98  #3/0
(2)(480)
Zc= (173)(124)(0.04) = 1.118 𝑜ℎ𝑚𝑠
(173)(65)(0.04)(0.98)
e% = = 0.9183%
480

Cond. Seleccionado cal. #4 pag. 4


Ip = 2.5 x 124 A =310 A 3p x 310ª
1 - 3/0  1 x 201.1 = 201.1  pag. 2
2 – 4  3 x 73.16 = 214.48  pag 1
Pag 18  2 cond, fr = 31%
53 (1)
T = 53 mm (1)
CCM4
6 motores de 25 Hp a 480 Volts con L=40 mts
Tabla 430 – 150, pag 26
18.7 KW = 25 Hp , In = 34 A
In Cond = 1.25 x 34 A = 42.5 A = Ic
Tabla 310 – 16 a 60°C
Pag 98  #6
(2)(480)
Zc = (173)(34)(0.04) = 4.08 𝑜ℎ𝑚𝑠
(173)(34)(0.04)(3.6)
e% = = 1.7646 %
480

Cond Seleccionado Cal.#10 pag 4


Ip = 2.5 x 34 = 85 A 3P x 85 A
1 – 6  1 x 46.84 = 46.84  pag 1
3 – 10  3 x 15.68 = 47.04  pag 1
46.84 + 47.04 = 93.86
Pag 18  2 cond, Fr=31%
21(1/2)
T = 21 mm (1/2)

You might also like