VRF Multi-split Air Conditioning System

This is an e-waste product and should not be mixed with general household waste at the end of its life. For more details kindly visit our website or contact Hitachi Dial-a-Care.
SET-FREE FSXNK
Hitachi Home & Life Solutions (India) Limited.
Head Office: Hitachi Complex, Karan Nagar, Kadi, Distt. Mehsana - 382727, Gujarat, India. Tel: (02764) 277571.
KYOSHO
Email: sales@hitachi-hli.com; Website: www.hitachi-hli.com
Hitachi air conditioning successfully meets installer and
customer demands - offering greater functionality,
control and cost savings

Introducing a new addition to Hitachi’s SET-FREE


range of VRF air conditioning units - enhancing
efficiency and user experience

Hitachi has over 25 years of experience on VRF system


There is increasing demand for a holistic approach to air conditioning in modern offices - units that are
capable of cooling and heating, adapting to the different seasons and various temperature requirements of
rooms. Needs of End Users Needs of Consultants Needs of Contractor and installer

Customers also want to save time, money and space with their air conditioning and have the flexibility to ■ Energy efficient ■ Time saving with equipment ■ Modular and lightweight for

extend or modify their air conditioning set-up to suit changing needs. ■ Greater user control layout design  quicker (or phased) installations
■ Flexibility to extend system ■ Flexible, modular system designs ■ Increased piping lengths
And of course there is a growing demand for air conditioning to be as environmentally friendly as possible ■ Intelligent controls  for flexibility
- enabled through an air-conditioning management system that makes it easier for users to have simple,
effective control of their air conditioning units to avoid unnecessary energy wastage, including overheating,
overcooling and unattended operation.
To meet and exceed these important requirements, Hitachi has developed the SET-FREE FSXNK air
Fresh air inspired by fresh technology
conditioning system.

Focus on health, improve


interior air quality
Sophisticated Antibacterial
Technology (Indoor Units)
Hitachi high performance antibacterial filter
adopts double – layer antibacterial structure

SET-FREE FSXNK (long acting antibacterial filter and high


performance antibacterial filter), adds active
enzymes with a strong bactericidal function,
Compatible with Hitachi’s system free indoor units which can restrain and kill bacteria and
mould attached to the filter surface, as well
Wide product range
as inhibit the reproduction of bacteria and
-FSXNK 8 to 54HP
mould on the high performance filter
Energy saving material and maintain fresh air in the room.
-DC Inverter Driven Compressor
Flexibility of Installation
-Compact and light design and flexible refrigerant piping
Fresh Air Introduction
Comfort and Reliability
-Capable of impressively low noise levels with Hitachi FSXNK series introduces outdoor
noise reduction preference mode (option) fresh air into indoor space via the all-fresh
Control by Network System air indoor units connected, improves the
indoor oxygen content, constantly remains
Off coil temperature control the interior fresh degree and create a healthy
environment for people’s lives.

Optional features with select Indoor Units.


Energy Efficient System Configuration Hitachi Advanced Technologies
Outdoor Unit Refrigerant Piping Transmission New Type DC Inverter Scroll Compressor
Module type (external connection) Max. length: 165m Corresponding to H-LINK II

2-pipe heat pump operations unit Total length: 1,000m Max. 64 refrigerant groups
Discharge Pressure Space
Max. 160 indoor units
Valve Open
Pressure
Control Valve
(Release Valve)
Optimization scroll spec.
Connectable Indoor Unit Hole for Release Valve Performance optimization by simulator

Max. 64 units
Compression
Capacity range: 50-130% Optimum oil supply
Space Fixed Scroll Mini. tradeoff, leak heat-loss

Pressure at More coiled DC brushless motor


Discharge Pressure
Compression Space High flux neodymium magnet

Improved Intermediate Pressure Performance


The intermediate pressure performance is drastically improved by using a release valve and optimizing orbiting scroll lifting force in
the improved new compression mechanism. Therefore, intermediate pressure performance is largely improved for energy-saving.
• Release valve adoption prevents over compression.
• Orbiting scroll lifting force optimization has achieved leakage loss reduction.

Exclusive Asymmetric Scroll Technology


The Asymmetric scroll structure of Hitachi compressor effectively helps reduce the refrigerant gas leakage loss in the process of
suction and compression, enhances operating efficiency and reliability.
Asymmetric scroll: the time difference between the suction of outside chamber and inside chamber is 1800. The pressure of outside
chamber and inside chamber are different. The pressure distribution in compressing chambers are asymmetric.
Symmetric scroll: the outside chamber and inside chamber end gas suction at the same time, the pressures of outside chamber and
inside chamber are equal. The pressure distribution in compressing chambers are symmetric.

Inside chamber Pi=Ps


achieve suction

BMS Central Station DX


Inside chamber Pi=Ps
Reduce suction loss and Outside chamber Po=Ps
leakage loss Achieve suction
NETWORK SYSTEM Outside chamber Po>Pi
High efficiency during compression
Centralized ON/OFF
Central Station Controller 7 Day Timer Remote Controller Central Station EZ
Coil Motor Efficiency
New Type DC Motor (%)
Motor Efficiency at Low Rotation is Improved
95
New type DC motor is increased the number of turns in a DC Motor
coil. This achieves to set inductive voltage high and
down the current at low rotation.

Rotor Stator 0 RPM

4 5
The Originated 2-Stage Oil Separating Gas Discharge
Optimization of Heat Exchanger
Refrigerant Gas
Technique Improves Reliability of System Newly designed heat exchanger is increased its layers for sustainable high ambient temperature.

Oil Seperator
with a Little Oil
The originated 2-stage oil separating technique adopts Hitachi
• Heat exchanger has been High Sufficient heat exchange performance in 48°C can
propriety compressor which has high efficient function on oil be obtained
Second Stage optimised by increasing heat
separating to conduct the final stage of oil separation. Oil Separating transfer area.
There is only a small proportion of refrigeration oil which is circulated
Gas Suction First Stage • Increased Heat transfer area is New
together with refrigerant gas to oil separator and then separated as the Oil Separating
achieved by increasing no. of row
second stage oil separating. Therefore, much less oil enters

HXE performance
of heat exchanger. This has

Accumulator
refrigerating circulation, accordingly enough oil can be guaranteed for Necessary Performance for 48°C
Compressor Compressor improved the performance of the
lubricating compressor. The system can operate safely and reliably.
Refrigerant Gas with Minimum Oil unit at high ambient temperature.

Refrigerant Gas with Minimum Oil

Optimized Inverter Control Low


Achieve the balance between intermediate
Low area High area
performance and rated performance, optimize the 7% up New HP
Lesser voltage

Efficiency (index)
Applied voltage

inverter control for high rotation required area. shortage 107.0


Max rise Current
If set inductive voltage high, result in restriction Trapezoid-shape 100
voltage by
of rotation frequency at high area. However, this sine rotation control
wave trapezoid Artificially applied
optimized inverter control ensure the operating
voltage up Intermediate
area by trapezoid the voltage. performance ratio Fin Specification Improvement
Fin Specification Improvement: Highly effficient super slit aluminium fin design has been opted for improving heat transfer efficiency.

Figure of Fin

Capacity Control by 1 Hz 4.7% up

Performance is greatly improved by the high efficiency DC inverter


New

Surface Heat-transfer
compressor and 100% load compressor, and loss-less energy saving 104.7

Coefficient (Index)
Current
operation is achieved (depending on the building). DIP-IPM Inverter 100.0
15~100Hz
Hitachi Precise Inverter-driven

27-Step Fan Speed Control


Adoption of Super Slit Fins Ratio of Fin specifications
The DC variable-speed motor is adapted in outdoor unit, which
results in efficiency promotion and power input reduction. The
outdoor fan speed can be adjusted by 27 steps.
Air Streamline Grill
Fan Rotating Speed

High
Oil Return Optimization
Oil return circuit Solenoid valve
Hitachi SETFREE outdoor unit is modular type and connected to one
refrigerant cycle. The oil should allocate back from refrigerant cycle
Oil separator
to outdoor unit equally therefore each outdoor unit has oil equalizing
system. The oil equalizing system consist of oil separator,
accumulator and oil return circuit. Hitachi unique technology of
Low
accumulator suction the oil by the gas pressure difference and it is
Efficient Axial Fan
ompressor is assured.
• The stability of discharge pressure and suction pressure of compressor assured able to adjust the oil feeding level depends on refrigerant circulating
Accumulator
Compressor
• The stability of dynamic flow (capacity) allocation of indoor unit is assured. volume. This is the reason to satisfy both of intermediate
• Quick response of control system is improved, accordingly the system stability, durability and reliability are assured. performance and rated performance. EER & COP Improved by 3.4%

6 7
Dummy Copy
Energy Efficiency Ratio (EER) is the most Important tool for checking
4.63
Product Line-up
performance of any Air-conditioning system at Given parameters. In 5 4.04
Up by 20%
absence of widely suitable and acceptable energy efficiency ratios 4.5 Up by 18% Choose the best suited model from a selection of each base unit used individually or in combinations.
3.85
and geographically changing ambient conditions. Significance of EER
4
3.41 All integrating heat pump operation suits the customer requirements.
3.5
is more predominant in India then any other ratios. 3
Hitachi offers some of the best EER values for its VRF systems. These 2.5

performances are the resultants of Hitachi’s innovative technologies 2 Outdoor Unit


8HP 12HP
i.e. High efficiency Inverter Compressor fitted with brushless DC
COP Cooling
Base Unit (6 models)
motor, Innovative High performance Heat exchangers using Super slit
Old FSXN New FSXNK
fin design and Invocative Oil Optimization technology.

8HP 12HP
Wide Working Range Heating
10HP 14HP
SET-FREE FSXNK can handle a wide range of outside air conditions, -20˚C 15˚C
Cooling 16HP
thus extending the flexibility of installation space and climatic 20HP 26HP
-5˚C 48˚C
environment. This unit is designed for cooling operation under high 18 HP
-20 -10 0 10 20 30 40 50
ambient temperature upto 48° C. 22HP 28HP

24HP 30HP

Power Setting Excessive power supply


32HP
Self-Demand Control Selectable from 100%, 80%,
70% and 40% of the rated
consumption exceeding the
A newly developed self-demand function has largely improved power setting range is
power consumption for
cooling operation. restricted.
energy-saving effects.
Power Consumption

Since the current is self-detected and demand control is performed


automatically, no signal wiring work is required. Conventional
demand control using demand signals is also available, and you can
Maximum efficiency is secured within
select various operations as required. the power setting range.
NEW
Morning Daytime Night
Operation Hours

34HP 36HP 40HP


<Setting example: Schedule Setting for Each Group by Central Station DX>
Group A Group B
38HP 42HP
Various operating methods are
Power Setting

Group A available depending on purpose


Power Setting: 80%
and needs.

Group B
Power Setting: 60%
8A.M. 12 P.M. 3 P.M. 6 P.M. Time
Central Station DX
(PSC-A128WX, PSC-AS2048WXB)
The specific outdoor unit and the period of
time can be set from Central Station DX.

NOTES
1. The demand current control (%) is indicated by approximate values. The values in this control which is calculated by the current is different precision from the value 44HP 48HP 52HP
in the wattmeter. If it is required that the maximum power consumption is managed precisely, a field-supplied demand controller should be used.
2. The range may temporarily be higher than the power setting range (%) depending on the operating control condition such as protection control.
3. When the above self-demand control is set, the performance is restricted because the rotation frequency of compressor is forcibly decreased.
46HP 50HP 54HP

8 9
Indoor Unit
Flexibility of Installation
Compact and Light Design
Transportation and Handling using Elevator
1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0 8.0 10.0 (HP)
The elevator can be used to transport the base unit separately.

Premium 4-Way Cassette

4-Way Cassette RAS-8 to 10FSXNK RAS-12-18FSXNK

Compact Cassette Even the Largest Basic


Unit (18HP Model) Can

1,720mm

1,720mm
Be Carried in an Elevator

Elevator
2-Way Cassette
Door Opening: 800 mm
Depth: 1350 mm

In the Ceiling
In-the-Ceiling
(Low-Height) 765mm 765mm
950mm 1,210mm

In-the-Ceiling Type
(Low Static Pressure)

In-the-Ceiling Type
(High Air Quantity)
Improvement of Workability
The piping connection work is newly available from the refrigerant piping outlet (right bottom side of the front cover) in addition to
three directions (front, rear or bottom) from the bottom base.

Ceiling Type

Newly Added
Wall Type
2 Control Power Source
Cable Outlets Cable Outlet

No trap is
required.
Wall Type

Front Cover
Refrigerant Piping Outlet
Floor Type

A new piping outlet is provided on the lower right side of the front cover and so
the piping connection kit can be installed at the lower position.
Floor Concealed Type
This makes an easy and clear installation of the piping from multiple outdoor
units possible.

10 11
More Flexible Refrigerant Piping Work
Improved flexibility of design by increasing the total pipe length Other Advanced Technologies
to 1,000 m max.
Rotational Operation*1 to Distribute Load of Outdoor Units
Heat Pump System
Regulating the operation time of each outdoor unit leads to load reduction on compressors.*2 During multiple unit operation, the
1 Max. piping length 165 m same rotation frequency of inverter compressor results in an equivalent load on each compressor. Therefore, outdoor unit endurance
is improved.
2 Between first branch
and indoor unit
90m or less 4
5
Height difference between Inverter Compressor Rotation Frequency Control (Example) Last Time
3
highest and lowest indoor units
30m or less 3
Compressor
Compressor

Height difference between At the time of compressor Compressor


4
outdoor and indoor units
50m
start-up, or when 2 hours has
2 Activatio
1 One Unit Two Units Three Units passed from start of operation. n
Sales on order 90m or less Operation Operation Operation
Order
3
2
1
Max. length between branch
5
from indoor units
40m It is operated so that the
This Time

Revolution of Inverter Compressor


revolution of the inverter
compressor 1 and 2 may Compressor
Compressor

3 become the same. Compressor

Activatio
n
Order 1
Revolution of 2 3
2 2 2

Flexibility of Facility Design


Revolution of 1
Improvement of Piping Installation 1 1 1 Next Time Compressor
Compressor
Compressor

Height difference between the outdoor units and indoor units and height difference between the indoor units have been changed as
shown below. Low
Operating Load
Hi Activatio
n
Order
2
1
ITEM HEAT PUMP SYSTEM NOTES 3

Current Model New Model *1: At least 2 outdoor units are required for this function.
(FSXN) (FSXNK) *2: Comparison between rotation operation function and non-rotation operation
function based on the same system.
Height Difference Outdoor Unit ≤50m ≤50m
Between Outdoor Units is Heigher
& Indoor Units
Sales on ≤70m ≤90m
Orders (*2)

Height Diffenece between indoor units ≤15m ≤30m


Backup Operation Function for Emergency
The Backup Operation Function prevents the system from coming to a complete stop when outdoor unit failure occurs.*1 Emergency
operation starts with the remote control switch after an alarm.*3

Even if one unit fails, Emergency Operation Indication


Connectable to 64 Indoor Units Max. the other can be operated continuously.*2
Press " TEMP.
simultaneously
"

The number of connectable indoor units has been increased to 64 maximum. Thus, the system can be used in buildings where there for 3 seconds.
are many indoor units to be connected.
Connection Capacity: 50 to 130% Compresso
r

x
Compresso
r
Outdoor units Capacity (HP) 8 10 12 14 16 18 20 22 24 26 28 30 Compresso
r

Max. Number of [EMG] is displayed on the LCD of


Connectable FSXNK Series 13 16 19 23 26 26 33 36 40 43 47 50 the remote control switch,
Indoor Units Failed Outdoor Unit and emergency operation starts.

Outdoor units Capacity (HP) 32 34 36 38 40 42 44 46 48 50 52 54 NOTES

Max. Number of *1: At least 2 outdoor units are required for this function.
Connectable FSXNK Series 53 56 59 64 64 64 64 64 64 64 64 64 *2: Emergency operation can be performed within 8 hours after unit stoppage. After 8 hours pass from unit stoppage, emergency operation can not be performed.
Indoor Units
*3: Emergency operation can be performed when the specified alarm code occurs. Refer to “Alarm Code for Emergency Operation”.

12 13
Noise Reduction Preference Mode (Optional Function)
With the new Noise Reduction Preference Mode, the sound pressure level for a particular time zone can be set based upon the usa ge General Data
environment. *1 Therefore, the operation/management of air conditioners is facilitated in areas where the noise level at night time is
Model RAS8FSXNK RAS10FSXNK RAS12FSXNK RAS14FSXNK RAS16FSXNK RAS18FSXNK
restricted by laws and regulations.
…………………. …………………. …………………. …………………. …………………. ………………….
Combination of Base Unit
…………………. …………………. …………………. …………………. …………………. ………………….
Power Supply AC 3Ph, 400V/50Hz
You can select from 3 sound pressure levels Nominal Cooling Capacity kW 22.4 28.0 33.5 40.0 45.0 50.0
Setting Example Nominal Heating Capacity kW 25.0 31.5 37.5 45.0 50.0 52.5
Optional Sound Pressure Low-Sound Operation during Night Time only by Using Timer Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Setting from Outdoor Unit
Noise Reduction Level (dB) Sound Pressure Level Maximum
Input and Output Function
Function (Approx. Value) Input Signal * [Overall A Scale] (Night-Shift) dB 58 (53) 58 (53) 61 (56) 62 (57) 64 (57) 64 (57)
Daytime Daytime Outer Dimensions Height x Width x Depth mm 1,720 x 950 x 765 1,720 x 950 x 765 1,720 x 1,210 x 765 1,720 x 1,210 x 765 1,720 x 1,210 x 765 1,720 x 1,210 x 765
100%
55 *
2
11 Setting 1 Capacity Net Weight 380-415V/50Hz kg 210 225 255 305 305 325
Night time
(Ratio) Gross Weight 380-415V/50Hz kg 225 240 270 320 320 340
60%
Refrigerant (Flow Control) R410A(Micro Computer Control Expansion Valve)
12 Setting 2 50
QTY 1 1 1 1+1 1+1 1+1
Compressor (Scroll)
Daytime Daytime Motor Output ( Pole ) KW 4.8 (6) 6.0 (6) 7.2 (6) 4.8 (6) + 4.4 (2) 6.0 (6) + 4.4 (2) 6.0 (6) + 5.6 (2)
13 Setting 3 45 Sound Pressure Night time Quantity 1 1 1 1 1 1
Level Condenser Fan (Propeller Fan) Air Flow Rate m3/min. 155 170 195 195 210 210
NOTES Motor Output (Pole) kW 0.33 (8) 0.44 (8) 0.66 (8) 0.66 (8) 0.91 (8) 0.91 (8)
50dB
*1: The range of performance and operation is restricted, because the rotation
frequency of the compressor and outdoor fan is forcibly decreased. Main Refrigerant Piping Heat
Liquid Line mm (in.) φ9.52 (3/8) * φ9.52 (3/8) * φ12.7 (1/2) * φ12.7 (1/2) * φ12.7 (1/2) * φ15.88 (5/8) *
Time Pump System (2 Pipes) Gas Line high / low mm (in.) φ19.05 (3/4) * φ22.2 (7/8) * φ25.4 (1) * φ25.4 (1) * φ28.58 (1-1/8) * φ28.58 (1-1/8) *
pressure
*: Perform the electrical wiring work on site when setting input signal. Refrigerant Charge kg 5.4 6.4 8.3 8.5 9.5 10.5
(before Shipment)
Packing Dimensions H X W X D mm 1,895 x 990 x 810 1,895 x 990 x 810 1,895 x 1,250 x 810 1,895 x 1,250 x 810 1,895 x 1,250 x 810 1,895 x 1,250 x 810
Approx. Packing Measurement mm 1.52 1.52 1.92 1.92 1.92 1.92

Model RAS20FSXNK RAS22FSXNK RAS24FSXNK RAS26FSXNK RAS28FSXNK RAS30FSXNK


RAS8FSXNK RAS8FSXNK RAS10FSXNK RAS12FSXNK RAS14FSXNK RAS14FSXNK
Automatic Simple Judgement System for Refrigerant Amount Combination of Base Unit
RAS12FSXNK RAS14FSXNK RAS14FSXNK RAS14FSXNK RAS14FSXNK RAS16FSXNK
Power Supply AC 3Ph, 400V/50Hz
Use this automatic judgement function to check whether or not the refrigerant amount is sufficient in one refrigerant cycle. Nominal Cooling Capacity kW 56.0 61.5 69.0 73.0 80.0 85.0
Nominal Heating Capacity kW 63.0 69.0 77.5 82.5 90.0 95.0
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Factor for Judgement Sound Pressure Level Maximum
The appropriate refrigerant amount is calculated based upon the following data. [Overall A Scale] (Night-Shift) dB 63 (58) 64 (59) 64 (59) 64 (59) 65 (60) 66 (61)
Outer Dimensions Height x Width x Depth mm 1,720 x 2,180 x 765 1,720 x 2,180 x 765 1,720 x 2,180 x 765 1,720 x 2,440 x 765 1,720 x 2,440 x 765 1,720 x 2,440 x 765
Net Weight 380-415V/50Hz kg 210 + 255 210 + 305 225 + 305 255 + 305 305 + 305 305 + 305
Gross Weight 380-415V/50Hz kg 225 + 270 225 + 320 240 + 320 270 + 320 320 + 320 320 + 320
Refrigerant Cycle Configuration [Schematic diagram]
Refrigerant (Flow Control) R410A(Micro Computer Control Expansion Valve)
Pressure QTY 1+1 1+1+1 1+1+1 1+1+1 1+1+1+1 1+1+1+1
Sensor
Compressor (Scroll) Motor Output ( Pole ) KW 4.8 (6) + 7.2 (6) 4.8 (6) + 4.8 (6) + 6.0 (6) + 4.8 (6) + 7.2 (6) + 4.8 (6) + 4.8 (6) + 4.4 (2) + 4.8 (6) + 4.4 (2) +
Refrigerant leakage
Adjustment 4.4 (2) 4.4 (2) 4.4 (2) 4.8 (6) + 4.4 (2) 6.0 (6) + 4.4 (2)
1 Refrigerant Cycle Temperature occurs
Thermistor
P
Quantity 2 2 2 2 2 2
Compressor

Accumulator

2 Refrigerant Saturation Temperature Correct Incorrect Condenser Fan (Propeller Fan) Air Flow Rate m3/min. 155 + 195 155 + 195 170 + 195 195 + 195 195 + 195 195 + 210
Motor Output (Pole) kW 0.33 (8) + 0.66 (8) 0.33 (8) + 0.66 (8) 0.44 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) 0.66 (8) + 0.91 (8)
3 Outdoor Unit Expansion Valve Data
Measure Adequate Liquid Line mm (in.) φ15.88 (5/8) * φ15.88 (5/8) * φ15.88 (5/8) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) *
4 Indoor Unit Data Refrigerant Quantity Main Refrigerant Piping Heat
Pump System (2 Pipes) Gas Line high / low mm (in.) φ28.58 (1-1/8) * φ28.58 (1-1/8) * φ28.58 (1-1/8) * φ31.75 (1-1/4) * φ31.75 (1-1/4) * φ31.75 (1-1/4) *
pressure
Work Quantity Refrigerant Charge (before kg 13.7 13.9 14.9 16.8 17.0 18.0
Improvement Shipment)
Overcooler Outdoor Heat
Exchanger
1 The cooling and heating performances are the values when combined with our specified indoor units
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27.0oC DB (80.0oF DB) Indoor Air Inlet Temperature: 20.0oC DB (68.0oF DB)
NOTES 19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7.0oC DB (45.0oF DB)
Outdoor Air Inlet Temperature: 35.0oC DB (95.0oF DB) 6.0oC WB (43.0oF WB)
*: Refrigerant over-charging is not detected. Over-charging can be detected by gradually adding refrigerant from the under-charged state at test run or when refrigerant leakage occurs. Piping Length: 7.5 Meters Piping Lift: 0 Meter

*: This function does not provide automatic refrigerant charging. 2 The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level
*: The adjustment (estimate) is changed according to the operation condition (the number of operating units and temperature). The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3 If the specified main refrigerant piping on the table is not available on site, follow the allowable piping size in parentheses.
When using the main refrigerant piping indicated in parentheses, prepare an appropriate reducer on site.
4 Except for the specified combination in the table (20~54HP), there is no other combination of the base unit
5 The width of outer dimension, it is the value when each distance between the base outdoor units is specified to 20mm.

14 15
General Data
Model RAS32FSXNK RAS34FSXNK RAS36FSXNK RAS38FSXNK RAS40FSXNK RAS42FSXNK Indoor Units
RAS16FSXNK RAS10FSXNK RAS12FSXNK RAS12FSXNK RAS12FSXNK RAS12FSXNK
Combination of Base Unit RAS16FSXNK
-
RAS12FSXNK
RAS12FSXNK
RAS12FSXNK
RAS12FSXNK
RAS12FSXNK
RAS14FSXNK
RAS12FSXNK
RAS16FSXNK
RAS14FSXNK
RAS16FSXNK 4-Way Cassette Type*
(Premium)
Power Supply AC 3Ph, 400V/50Hz
Nominal Cooling Capacity kW 90.0 95.0 100.0 109.0 112.0 118.0
Nominal Heating Capacity kW 100.0 106.0 112.0 118.0 125.0 132.0
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5)
Sound Pressure Level Maximum
Adopting New Structured Silky Flow Louver
[Overall A Scale] (Night-Shift) dB 66 (61) 65 (60) 66 (61) 66 (61) 67 (61) 67 (61)
Outer Dimensions Height x Width x Depth mm 1,720 x 2,440 x 765 1,720 x 3,410 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 The newly-structured silky flow 75mm
Net Weight 380-415V/50Hz kg 305 + 305 225 + 255 + 255 255 + 255 + 255 255 + 255 + 305 255 + 255 + 305 255 + 305 + 305
louver is adopted to soften the
Gross Weight 380-415V/50Hz kg 320 + 320 240 + 270 + 270 270 + 270 + 270 270 + 270 + 320 270 + 270 + 320 270 + 320 + 320
discomfort by the temperature
Refrigerant (Flow Control) R410A(Micro Computer Control Expansion Valve)
QTY 1+1+1+1 1+1+1 1+1+1 1+1+1+1 1+1+1+1 1+1+1+1+1
irregularity and the cold draft.
Compressor (Scroll) Motor Output (Pole) KW 6.0 (6) + 4.4 (2) + 6.0 (6) + 7.2 (6) + 7.2 (6) + 7.2 (6) + 7.2 (6) + 7.2 (6) + 7.2 (6) + 7.2 (6) + “7.2 (6) + 4.8 (6) + The individual control setting
6.0 (6) + 4.4 (2) 7.2 (6) 7.2 (6) 4.8 (6) + 4.4 (2) 6.0 (6) + 4.4 (2) 4.4 (2) + 6.0 (6) + for each louver is available. New Silky Flow Louver Motion Sensor Control (Option)
4.4 (2)”
Detecting Area The air conditioning capacity is saved automatically depending
Quantity 2 3 3 3 3 3
Air Flow Rate m3/min. 210 + 210 170 + 195 + 195 195 + 195 + 195 195 + 195 + 195 195 + 195 + 210 195 + 195 + 210 Example of 4.0HP and 6.0HP
on a situation and detecting amount of human activity by
Condenser Fan (Propeller Fan)
Motor Output (Pole) kW 0.91 (8) + 0.91 (8) 0.44 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) 0.66 (8) + 0.66 (8) adopting the motion sensor on the corner of the air panel. The
Angle
+ 0.66 (8) + 0.66 (8) + 0.66 (8) + 0.91 (8) + 0.91 (8) Approx. 123˚ energy saving can be improved more with the individual
Main Refrigerant Piping Heat
Liquid Line mm (in.) φ19.05 (3/4) * φ1 9.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) *
operating function. In addition, the operation can be stopped
Gas Line high / low mm (in.) φ31.75 (1-1/4) * φ31.75 (1-1/4) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) *
automatically if the absent situation continues for more than 30
Dia. Approx. 7m (1.0~3.0FSN3)
Pump System (2 Pipes) Dia. Approx. 8.8m (4.0~6.0FSN3) Ceiling Height
pressure
3.2m 1
Refrigerant Charge (before kg 19.0 23.0 24.9 25.1 26.1 26.3 minutes* . The motion sensor can maintain the comfortable
2
Shipment) indoor environment and eliminating the unnecessary operation* .
0.8m
(From Floor Surface) *1): The default setting is “30 minutes”. However, the setting is changeable.
In the case of the ceiling height is 3.2m. *2): The default setting is “Running Operation”. However, “Automatic Stop” can be selected by setting
Model RAS44FSXNK RAS46FSXNK RAS48FSXNK RAS50FSXNK RAS52FSXNK RAS54FSXNK *3): The detecting area becomes smaller if the people stay motion less is few such as stretching on a chair, etc.
RAS12FSXNK RAS14FSXNK RAS16FSXNK RAS14FSXNK RAS16FSXNK RAS18FSXNK Specifications
Combination of Base Unit RAS16FSXNK RAS16FSXNK RAS16FSXNK RAS18FSXNK RAS18FSXNK RAS18FSXNK
Model RCI-1.0FSN3 RCI-1.5FSN3 RCI-2.0FSN3 RCI-2.5FSN3 RCI-3.0FSN3 RCI-4.0FSN3 RCI-5.0FSN3 RCI-6.0FSN3
RAS16FSXNK RAS16FSXNK RAS16FSXNK RAS18FSXNK RAS18FSXNK RAS18FSXNK
Indoor Unit Power Supply AC 1φ, 220-240V / 50Hz, 220V / 60Hz
Power Supply AC 3φ, 400V/50Hz kW 2.9 4.1 5.8 7.3 8.3 11.6 14.5 16.5
Nominal Cooling Capacity kW 125.0 132.0 136.0 140.0 145.0 150.0 Nominal Cooling
kcal/h 2,500 3,550 5,000 6,300 7,100 10,000 12,500 14,200
Capacity *1)
Nominal Heating Capacity kW 140.0 145.0 150.0 151.0 156.0 157.5 Btu/h 9,900 14,100 19,800 25,000 28,200 39,700 49,600 56,300
Cabinet Color (Munsell Code) Natural Gray (1.0Y 8.5/0.5) kW 2.8 4.0 5.6 7.1 8.0 11.2 14.0 16.0
Nominal Cooling
Sound Pressure Level Maximum kcal/h 2,400 3,400 4,800 6,100 6,900 9,600 12,000 13,800
Capacity *2)
[Overall A Scale] (Night-Shift) dB 68 (62) 68 (63) 69 (63) 68 (62) 69 (62) 69 (62) Btu/h 9,600 13,600 19,100 24,200 27,300 38,200 47,800 54,600
Outer Dimensions Height x Width x Depth mm 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 1,720 x 3,670 x 765 kW 3.2 4.8 6.3 8.5 9.0 12.5 16.0 18.0
Nominal Heating
Net Weight 380-415V/50Hz kg 255 + 305 + 305 305 + 305 + 305 305 + 305 + 305 305 + 325 + 325 305 + 325 + 325 325 + 325 + 325 kcal/h 2,800 4,100 5,400 7,300 7,700 10,700 13,800 15,500
Capacity
Gross Weight 380-415V/50Hz kg 270 + 320 + 320 320 + 320 + 320 320 + 320 + 320 320 + 340 + 340 320 + 340 + 340 340 + 340 + 340 Btu/h 10,900 16,400 21,500 29,000 30,700 42,600 54,600 61,400
Refrigerant (Flow Control) R410A(Micro Computer Control Expansion Valve) Sound Pressure Level
dB 33/30/28/27 35/31/30/27 37/32/30/27 42/36/32/28 42/36/32/28 48/43/39/33 48/45/40/35 48/46/41/37
(Overall A Scale) Hi2/Hi/Me/Lo
QTY 1+1+1+1+1 1 + 1 + 1 + 1 + 1 +1 1 + 1 + 1 + 1 + 1 +1 1 + 1 + 1 + 1 + 1 + 1 1 + 1 + 1 + 1 + 1 + 1 1 + 1 + 1 + 1 + 1 + 1
Dimensions H x W x D mm 248 x 840 x 840 298 x 840 x 840
Compressor (Scroll) Motor Output ( Pole ) KW “7.2 (6) + 6.0 (6) + “4.8 (6) + 4.4 (2) + “6.0 (6) + 4.4 (2) + “4.8 (6) + 4.4 (2) + “6.0 (6) + 4.4 (2) + “6.0 (6) + 5.6 (2) +
4.4 (2) + 6.0 (6) + 6.0 (6) + 4.4 (2) + 6.0 (6) + 4.4 (2) + 6.0 (6) + 5.6 (2) + 6.0 (6) + 5.6 (2) + 6.0 (6) + 5.6 (2) + Net Weight kg 20 21 22 26
4.4 (2)” 6.0 (6) + 4.4 (2)” 6.0 (6) + 4.4 (2)” 6.0 (6) + 5.6 (2)” 6.0 (6) + 5.6 (2)” 6.0 (6) + 5.6 (2)” Refrigerant R410A
Quantity 3 3 3 3 3 3 Air Flow Rate m3/min. 15/13/11/9 21/17/14/11 21/17/14/11 27/23/18/14 27/23/18/14 37/31/24/20 37/33/26/21 37/35/28/22
Hi2/Hi/Me/Lo (cfm) (530/459/388/318) (741/600/494/388) (777/600/494/388) (953/812/635/494) (953/812/635/494) (1,306/1,094/847/706) (1,306/1,165/918/741) (1,306/1,236/988/777)
Air Flow Rate m3/min. 195 + 210 + 210 195 + 210 + 210 210 + 210 + 210 195 + 210 + 210 210 + 210 + 210 210 + 210 + 210
Condenser Fan (Propeller Fan)
Motor Output (Pole) kW 0.66 (8) + 0.91 (8) 0.66 (8) + 0.91 (8) 0.91 (8) + 0.91 (8) 0.66 (8) + 0.91 (8) 0.91 (8) + 0.91 (8) 0.91 (8) + 0.91 (8) Motor W 57 127
+ 0.91 (8) + 0.91 (8) + 0.91 (8) + 0.91 (8) + 0.91 (8) + 0.91 (8) Connections Flare-Nut Connection (With Flare Nuts)
Liquid Line mm φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * φ19.05 (3/4) * Liquid / Gas mm φ6.35 /φ12.7 φ6.35 /φ15.88 φ9.52 /φ15.88
Main Refrigerant Piping Heat (in.) Condensate Drain VP25
Pump System (2 Pipes) Gas Line high / low mm φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * φ38.1 (1-1/2) * Approximate
pressure (in.) Packing Measurement m3 0.21 0.25

Refrigerant Charge (before kg 27.3 27.5 28.5 29.5 30.5 31.5 Adaptable Panel Model P-AP160NA1 (without Motion Sensor) / P-AP160NAE (with Motion Sensor)
Shipment) Color Natural White
Dimensions H x W x D mm 37 x 950 x 950
1 The cooling and heating performances are the values when combined with our specified indoor units Net Weight kg 6.5
Cooling Operation Conditions Heating Operation Conditions Approximate
Indoor Air Inlet Temperature: 27.0oC DB (80.0oF DB) Indoor Air Inlet Temperature: 20.0oC DB (68.0oF DB) Packing Measurement m3 0.10
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7.0oC DB (45.0oF DB)
Outdoor Air Inlet Temperature: 35.0oC DB (95.0oF DB) 6.0oC WB (43.0oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
NOTES:
2 The sound pressure is based on the following conditions.
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level
The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. Cooling Operation Conditions Heating Operation Conditions
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
*1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
3 If the specified main refrigerant piping on the table is not available on site, follow the allowable piping size in parentheses. *2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
When using the main refrigerant piping indicated in parentheses, prepare an appropriate reducer on site. Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
4 Except for the specified combination in the table (20~54HP), there is no other combination of the base unit 2. The sound pressure level is based on following conditions.
5 The width of outer dimension, it is the value when each distance between the base outdoor units is specified to 20mm. 1.5 Meters Beneath the Unit. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. *To be launched soon.

16 17
Indoor Units Indoor Units

4-Way Cassette Type 4-Way Cassette


SET FREE-RCI Technique Features Compact Type
Extremely quite operation
By employing a super-high-stream turbo fan Highly Compact Size
(three-dimensional twisted wing large bore and high • Compared with the standard 4-Way Cassette Type indoor
efficiency), the wind flow of efficiency has been improved unit, the size of the air panel for this product has been
with the under damping slit mounted near the center of the reduced by 250mm (from 950mm to 700mm).
revolving shaft, the abnormal noise which is unique to DC
motors caused by the number of magnetic poles and
revolution speed of the motor, is reduced. Unified panel sizes 700mm
570mm
Panel size are unified to a 950mm square, neat and elegance, and Body
The indoor unit height from

700mm
With broad range of air supply, is suitable to be used in

295mm
well harmonized with decoration. the false ceiling surface can
high ceiling and great space be adjusted from the corner
Compact and thin Air Panel pocket with a wrench.
The height of the unit is just 248mm(less than 2.5HP), so it can The dashed line shows the size of the standard 4-way cassette type.
Corner Pocket
be installed in a small space inside a ceiling. 530
Easy Installation
• Easier Height Adjustment • Installation to Grid Ceiling
The unit height can be adjusted from 4 corner pockets, with This product can be installed to a 570

586
530
the air panel attached to the unit. Height adjustment from grid ceiling with a 600mm x 600mm

570
the corner pockets is suitable for fine adjustment. To keep opening without cutting the grid.
the unit level, avoid significant height adjustment.
586
Model RCI-1.0 FSN1Q RCI-1.5 FSN1Q RCI-2.0 FSN1Q RCI-2.5 FSN1Q RCI-3.0 FSN1Q RCI-4.0 FSN1Q RCI-5.0 FSN1Q RCI-6.0 FSN1Q Otherwise, it might cause water leakage from the drain pan.
Indoor Unit Power Supply AC 1Ph, 220~240V/50Hz , 220V/60HzV/50Hz Grid Ceiling (mm)
KW 2.9 4.4 5.8 7.3 8.7 11.6 14.5 16.5
Normal Cooling Capacity *1 kcal/h 2500 3800 5000 6300 7500 10000 12500 14200 General Specifications
Btu/h 9900 15000 19800 24900 29700 39600 49500 56300 Indoor Unit Type 4-Way Cassette (Compact) Type
KW 2.8 4.3 5.6 7.1 8.4 11.2 14.2 16 Model RCIM-1.0FSN3 RCIM-1.5FSN3 RCIM-2.0FSN3
Normal Cooling Capacity *2 kcal/h 2400 3700 4800 6100 7200 9600 12200 13800 Indoor Unit Power Supply AC 1φ, 220-240V / 50Hz, 230 / 50Hz, 220V / 60Hz
Btu/h 9600 14700 19100 24200 28700 38200 48500 54600 kW 2.9 4.1 5.8
Nominal Cooling Capacity *1) kcal/h 2,500 3,550 5,000
KW 3.3 4.9 6.5 8.5 9.6 13 16.3 18
Btu/h 9,900 14,100 19,800
Normal Heating Capacity kcal/h 2800 4200 5600 7300 8300 11200 14000 15500
kW 2.8 4.0 5.6
Btu/h 11300 16700 22200 29000 32800 44400 55600 61400 Nominal Cooling Capacity *2) kcal/h 2,400 3,400 4,800
“Sound Pressure Level dB 32-30-28 32-30-28 32-30-28 32-30-28 34-32-30 41-36-33 43-38-35 44-40-36 Btu/h 9,600 13,600 19,100
(Overall A Scale) Hi/ Me /Lo” kW 3.2 4.8 6.3
Dimension H X W X D mm 248 X 840 X 840 248 X 840 X 840 248 X 840 X 840 248 X 840 X 840 298 X 840 X 840 298 X 840 X 840 298 X 840 X 840 298 X 840 X 840 Nominal Heating Capacity kcal/h 2,800 4,100 5,400
Net Weight Kg 23 23 24 24 26 29 29 29 Btu/h 10,900 16,400 21,500
Sound Pressure Level
Refrigerant R410A dB 36/34/28 38/35/33 42/39/37
[Overall A Scale] Hi/Me/Lo
Air Flow Rate Hi/ Me/ Lo m3/min 13/12/11 15/13.5/12 16/14/12 20/17/15 26/23/20 32/28/24 34/29/25 37/32/27
Height mm 295 295 295
(cfm)
Motor W 56 56 56 56 56 108 108 108 Width mm 570 570 570
Outer
Connection Dimensions Depth mm 570 570 570
Liquid mm φ 6.35 φ 6.35 φ 6.35 φ 9.53 φ 9.53 φ 9.53 φ 9.53 φ 9.53 Net Weight kg 17 17 17
Gas mm φ 12.7 φ 12.7 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 Refrigerant R410A
Condensate Drain VP 25 (Outer Diameter) O 32 Indoor Fan
Air Flow Rate Hi/Me/Lo m3/min. 13/12/10 15/13.5/12 16/14/12
Approximate Packing Measurement m3 0.22 0.22 0.22 0.22 0.26 0.26 0.26 0.26
Motor W 52 52 52
Adaptable Panel Model P-N23NAQ
Connections Flare-Nut Connection (With Flare Nuts)
Color NEUTRAL WHITE
Dimension H x W x D mm 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 37 X 950 X 950 Liquid Line mm φ6.35 φ6.35 φ6.35
Refrigerant
Net Weight Kg 6 6 6 6 6 6 6 6 Gas Line mm φ12.7 φ12.7 φ15.88
Piping
Approximate Packing Measurement m3 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 Condensate Drain VP25 VP25 VP25
Approximate Packing Measurement m3 0.13 0.13 0.13
NOTES:
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. NOTES:
Cooling Operation Conditions Heating Operation Conditions 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB) Cooling Operation Conditions Heating Operation Conditions
*1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB) Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
*2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB) *1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter *2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1.5 Meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V,
the sound pressure level increases by about 1dB.The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

18 19
Indoor Units Indoor Units

2-Way Cassette Type In-the-ceiling Type


Downsizing and weight reduction simplify handling for
(Low-height)
easier renewal
The length of the 3.0HP type is shortened from 1,320 mm to SET FREE RPIZ Technology Feature
860 mm, the height is also shortened, and the volume is Installation Space Saving
reduced by about 50%.The reduced weight of 30 kg also makes With a height of 192mm may be easily installed inside the low
handling much easier. height residential ceiling.

Top-class noise control thanks to compact turbo fan Quite Operation


The three-dimensional twisted wings of the compact turbo Low-profile design allows installation in a small space
inside ceiling Air flow rate can be adjusted by 3 grades, lower noise in lower grade.
fan greatly reduce noise, and electromagnetic disturbance
is minimized by PWM (Pulse Width Modulation) control. A compact turbo fan simplifies the structure and reduces the
Model High Sound Low Sound
Pressure (dB) Pressure (dB)
height to 298 mm, for easy installation. RPIZ-1.0FSN1Q 27 21
Speed-up tap ensures comfortable air conditioning even Broad Range Of External Static Pressure RPIZ-1.5FSN1Q 31 26
Compact Turbo Fan
when installed in the high ceiling 10Pa (or 30Pa), flexibility supports a wide range of installation RPIZ-2.0FSN1Q 34 28
Even rooms with a high ceiling can be comfortably conditions at site e.g. longer ducts and shorter ducts supplied. RPIZ-2.5FSN1Q 35 30
air-conditioned by setting the speed-up tap with the remote 298mm
Ceiling Drain-up Mechanism as Standard Part
controll switch. Satisfies Varied Requests On Installation
Available air inlet as rear or bottom entry, consumers can Drain-up length achieves 900mm which enables convenient drain
Specifications choose relevant air inlet mode according to the practical piping and enlarges the flexibility of installation.
Model RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.0FSN2 RCD-2.5FSN2 RCD-3.0FSN2 RCD-4.0FSN2 RCD-5.0FSN2 installation space.
Indoor Unit Power Supply AC 1φ, 220-240V / 50Hz, 220V / 60Hz
kW 2.9 4.1 5.8 7.3 8.3 11.6 14.5
Nominal Cooling kcal/h 2,500 3,550 5,000 6,300 7,100 10,000 12,500
Capacity *1)
Btu/h 9,900 14,100 19,800 25,000 28,200 39,700 49,600
kW 2.8 4.0 5.6 7.1 8.0 11.2 14.0
Nominal Cooling kcal/h 2,400 3,400 4,800 6,100 6,900 9,600 12,000
Capacity *2)
Btu/h 9,600 13,600 19,100 24,200 27,300 38,200 47,800
Model RPIZ-1.0FSN1Q RPIZ-1.5FSN1Q RPIZ-2.0FSN1Q RPIZ-2.5FSN1Q
kW 3.2 4.8 6.3 8.5 9.0 12.5 16.0
Nominal Heating Indoor Unit Power Supply AC 1Ph, 220~240V/50Hz , 220V/60HzV/50Hz
kcal/h 2,800 4,100 5,400 7,300 7,700 10,700 13,800
Capacity
Btu/h 10,900 16,400 21,500 29,000 30,700 42,600 54,600 KW 2.9 4.4 5.8 7.3
Sound Pressure Level Normal Cooling Capacity *1 kcal/h 2500 3800 5000 6300
dB 34/32/30 35/32/30 38/34/31 40/36/33 43/40/36
(Overall A Scale) Hi/Me/Lo Btu/h 9900 15000 19800 24900
Dimensions H x W x D mm 298 x 860 x 620 298 x 1,420 x 620 KW 2.8 4.3 5.6 7.1
Net Weight kg 27 30 48 Normal Cooling Capacity *2 kcal/h 2400 3700 4800 6100
Refrigerant R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) Btu/h 9600 14700 19100 24200
Air Flow Rate m3/min. 10/9/8 13/11/9 15/13/11 19/16/14 29/24/21 34/29/25 KW 3.3 4.9 6.5 8.5
Hi/Me/Lo (cfm) (353/318/282) (459/388/318) (530/459/388) (671/565/494) (1,024/847/742) (1,201/1,024/883) Normal Heating Capacity kcal/h 2800 4200 5600 7300
Motor W 35 55 35 x 2 55 x 2 Btu/h 11300 16700 22200 29000
Connections Flare-Nut Connection (With Flare Nuts) Sound Pressure Level (Overall A dB 27-24-21 [29-25-22] 31-29-26 [34-31-28] 34-30-28 [36-32-26] 35-33-30 [39-37-33]
Liquid / Gas mm φ6.35 /φ12.7 φ6.35 /φ15.88 φ9.52 /φ15.88 φ9.52 /φ15.88*3) Scale) Hi/ Me/ Lo
Condensate Drain VP25 Dimension H X W X D mm 192 X 900 X 447 192 X 900 X 447 192 X 1170 X 447 192 X 1170 X 447
Approximate Net Weight Kg 21 22 27 27
Packing Measurement m3 0.23 0.37 Refrigerant R410A
Adaptable Panel Model P-N23DNA P-N46DNA Air Flow Rate Hi/ Me/ Lo m3/min (cfm) 8/7/6 [7.5/6.5/5.5] 10/8/7 [9.8/8.5/7.5] 14.5/12.5/10.5 [13.5/11.9/9.5] 16/14/12 [14.8/13.0/11.5]
Color Neutral White External Pressure Pa 10(30) [20(50)] 10(30) [20(50)] 10(30) [20(50)] 10(30) [20(50)]
Dimensions H x W x D mm 30 x 1,100 x 710 30 x 1,660 x 710 Motor W 16 25 40 50
Net Weight kg 6 8 Connection Flare-Nut Connection (with Flare Nuts)
Approximate Liquid mm φ 6.35 φ 6.35 φ 6.35 φ 9.53
Packing Measurement m3 0.10 0.15 Gas mm φ 12.7 φ 12.7 φ 15.88 φ 15.88
Condensate Drain VP 25 (outer Diameter O 32
Approximate Packing Measurement m3 0.15 0.15 0.18 0.18
NOTES:
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
*1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
*2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V,
the sound pressure level increases by about 1dB.The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

20 21
Indoor Units Indoor Units

In-the-ceiling Type In-the-ceiling Type


(Low Static Pressure) (High Air Quantity)
SET FREE-RPI Technique Features Broader range of external static pressure and higher air
Installation Space Saving volume. Flexibly supports a wide range of installation
Less than 270mm in height can be easily fit into the limited conditions on site, e.g. longer ducts.
space in the false ceiling (0.8HP to 2.5HP) • Space Saving Design
With a height of only 280mm (2.0HP to 3.0HP), 385mm
Flexibilty supports a wide range of installation conditions at site (4.0HP to 5.0HP) or 440mm (8HP and 10HP), this unit
• Adjustable Fan Speed
can be installed at false ceiling spaces in almost any
building. The indoor fan motor has three speeds that can be adjusted
to allow for pressure loss in the duct, thus providing a more
Minimum 5mm efficient air flow.
• Quiet Operation
285mm The well balanced centrifugal fan helps in a quiet and
False efficient operation.
Ceiling

NOTE:
When bottom air inlet is adopted, sound pressure will increase according to factors
such as the installation mode and the room structure. Model RPI2.0FSNA RPI2.5FSNA RPI3.0FSNA RPI-3.0 FSNQH RPI4.0FSNA RPI5.0FSNA RPI-6.0 FSNQH RPI8.0FSNA RPI10FSNA
Indoor Unit Power Supply AC 1Ph, 220~240V/50Hz , 220V/60HzV/50Hz AC 1Ph, AC 1Ph, 230V/50Hz
RPI-1.0FSNQL RPI-1.5FSNQL RPI-2.0FSNQL RPI-2.5FSNQL RPI-3.0FSNQL RPI-4.0FSNQL RPI-5.0FSNQL RPI-6.0FSNQL RPI-8.0FSNQL RPI-
Model 220V/50Hz
10.0FSNQL
AC 1f, 220 KW 5.8 7.3 8.3 8.7 11.6 14.5 16.5 23.3 29.1
Indoor Unit Power Supply AC 1Ph, 220~240V/ 50Hz , 220V/60HzV/50Hz AC 3f, 380V~415V/50Hz
V/50Hz Normal Cooling Capacity *1 kcal/h 5000 6300 7100 7500 10000 12500 14200 20000 25000
KW 2.9 4.4 5.8 7.3 8.7 11.6 14.5 16.5 23.2 28.6 Btu/h 19800 25000 28200 29700 39700 49600 56300 79400 99200
Normal Cooling Capacity *1 kcal/h 2500 3800 5000 6300 7500 10000 12500 14200 20000 24600 KW 5.6 7.1 8 8.4 11.2 14 16 22.4 28
Btu/h 9900 15000 19800 24900 29700 39600 49500 56300 79200 97600 Normal Cooling Capacity *2 kcal/h 4800 6100 6900 7200 9600 12000 13800 19300 24100
KW 2.8 4.3 5.6 7.1 8.4 11.2 14.2 16 22.4 28 Btu/h 19100 24200 27300 28700 38200 47800 54600 76400 95500
Normal Cooling Capacity *2 kcal/h 2400 3700 4800 6100 7200 9600 12200 13800 19300 24100 KW 6.3 8.5 9 9.6 12.5 16 18 25 31.5
Btu/h 9600 14700 19100 24200 28700 38200 48500 54600 76500 95600 Normal Heating Capacity kcal/h 5400 7300 7700 8300 10700 13800 15500 21500 27100
KW 3.3 4.9 6.5 8.5 9.6 13 16.3 18 25 31.5
Btu/h 21500 29000 30700 32800 42600 54600 61400 85300 107500
Normal Heating Capacity kcal/h 2800 4200 5600 7300 8300 11200 14000 15500 21500 27100
Sound Pressure Level dB 43 44 44 42-39-35 50 52 45-41-37 60 62
Btu/h 11300 16700 22200 29000 32800 44400 55600 61400 85300 107500 (Overall A Scale) Hi/ Me/ Lo
Sound Pressure Level dB 29.5-26-24.5 34-32-30 34-32-30 35-33-31 40-37-33 41.5-39-35 42-39-35 43-39-37 50 52 Dimension H X W X D mm 280 x 1130 280 x 1130 280 x 1130 350 X 900+75 385 x 1190 385 x 1190 350 X 1300+75 440 x 1550 440 x 1550
(Overall A Scale) Hi/ Me/ Lo x 555 x 555 x 555 X 800 x 675 x 675 X 800 x 675 x 675
Dimension H X W X D mm 270 X 650+75 270 X 650+75 270 X 650+75 270 X 900+75 350 x 900+75 350 x 900+75 350 x 1300+75 350 x 1300+75 470 x 1060 x 470 x 1250 x Net Weight Kg 32 34 34 46 63 65 58 81 81
X 720 X 720 X 720 X 720 x 800 x 800 x 800 x 800 1120 1120
Refrigerant R410A
Net Weight Kg 26 26 35 35 46 46 58 58 96 108
Air Flow Rate Hi/ Me/ Lo m3/min 17/15/13 23/21/19.5 28/26/23.5 25/21/17 33/31/28 45/41/37.5 38/25/29 84.95/77.58/70 96/87.5/80
Refrigerant R410A
(cfm)
Air Flow Rate Hi/ Me/ Lo m3/min 8/7/6 13/11/9 15/13/11 16/14/12 25/21/17 27/23/19 37/31/25 38/35/29 58 72
(cfm) External pressure 19 19 19 120(90) 49 49 120(90) 78 78
External Pressure Pa 30 30 30 30 60 60 60 60 100 100 Motor W 110 110 110 120 670 670 280 1500 1500
Motor W 20 40 45 45 100 100 160 180 500 750 Connection
Connection Flare-Nut Connection (with Flare Nuts) Liquid mm φ 6.35 φ 9.52 φ 9.52 φ 9.53 φ 9.52 φ 9.52 φ 9.53 φ 9.52 φ 9.52
Liquid mm φ 6.35 φ 6.35 φ 6.35 φ 9.53 φ 9.53 φ 9.53 φ 9.53 φ 9.53 φ 9.53 φ 9.53 Gas mm φ 12.7 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 19.05 φ 22.2
Gas mm φ 12.7 φ 12.7 φ15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 15.88 φ 19.05 φ 22.2 Condensate Drain VP 25 (outer Diameter O 32
Condensate Drain VP 25 (Outer Diameter) O 32 Approximate Packing m3 0.29 0.29 0.29 0.38 0.59 0.59 0.52 0.83 0.83
Approximate Packing m3 0.21 0.21 0.27 0.27 0.38 0.38 0.52 0.52 0.90 0.90 Measurement
Measurement

NOTES:
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
*1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
*2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

22 23
NEW

Indoor Units Indoor Units

Ceiling Type Wall Type


Motion Sensor Control (Option) User Friendly
The air conditioning capacity is saved automatically depending Easy switching from wireless to wired remote controller by
on a situation and the amount of detected human activity by Dip Switch built-in the receiver part. All alarm code is
adopting the motion sensor kit. In addition, the operation can be displayed when using wireless remote controller by
stopped automatically if the absent situation continues for more combining the flashing times of "Timer", "Filter/Defrosting".
than 30 minutes*1. (All models)
The motion sensor can maintain the comfortable indoor
environment and eliminate the unnecessary operation*2. Compact and Stylish Design
*1): The default setting is “30 minutes”. However, the setting is changeable.
• The unit has been designed with a flat front panel and a slim body. The front panel is easy to clean and should remain relatively
*2): The default setting is “Running Operation”. However, “Automatic Stop” can be selected by High Efficiency and Low Noise by New Fan Runner
dust free.
setting from the remote control switch.
Newly-developed fan runner is adopted. By improving shapes
• For 1.0HP and 1.5HP units, their compact design with 830mm width, allows for flexible and neat installation in narrow spaces.
of fin and air outlet, the fan efficiency is improved and the low noise
For 2.0 to 2.5HP units, unit width is 1,050mm
Detecting Area performance is achieved.
Depth 7m • Front flat panel protects the unit from dust and facilitates maintenance work. For 1.0HP to 2.5HP units, you can easily remove
the front flat panel and wash it with water.
Fan Casing • Koukin Filter: This unique anti-bacterial filter prevents bacterial growth in the air conditioner thus increasing the efficiency of the
Air Outlet
Ceiling Diffuser air conditioner.
New L-Shaped Fin
Height
Detecting Area 2.7m
Specifications
0.8m from Floor Level Model RPK1.0FSNA RPK1.5FSNA RPK2.0FSNA RPK2.5FSNA RPK3.0FSNSM3 RPK4.0FSNSM3
Indoor unit Power Supply AC 1Ph, 220~240V/50Hz , 220V/60HzV/50Hz
1.8m 7.2m KW 2.9 4.1 5.8 7.3 8.3 11.6
Normal Cooling Capacity *1 kcal/h 2500 3550 5000 6300 7100 10000
9m
Btu/h 9900 14100 19800 25000 28200 39700

Specifications Normal Cooling Capacity *2


KW
kcal/h
2.8
2400
4
3400
5.6
4800
7.1
6100
8
6900
11.2
9600
Model RPC-1.5FSN3 RPC-2.0FSN3 RPC-2.5FSN3 RPC-3.0FSN3 RPC-4.0FSN3 RPC-5.0FSN3 RPC-6.0FSN3 Btu/h 9600 13600 19100 24200 27300 38200
Indoor Unit Power Supply AC 1φ, 220-240V / 50Hz, 220V / 60Hz KW 3.2 4.8 6.3 8.5 9 12.5
kW 4.1 5.8 7.3 8.3 11.6 14.5 16.5 Normal Heating Capacity kcal/h 2800 4100 5400 7300 7700 10700
Nominal Cooling
kcal/h 3,550 5,000 6,300 7,100 10,000 12,500 14,200 Btu/h 10900 16400 21500 29000 30700 42600
Capacity *1)
Btu/h 14,100 19,800 25,000 28,200 39,700 49,600 56,300 Sound Pressure level (Overall A dB 45/42/40/38 45/42/40/38 43/40/38/34 45/43/41/37 49/43/40/36 51/49/46/41
kW 4.0 5.6 7.1 8.0 11.2 14.0 16.0 Scale) Hi 2/ Hi/ Me/ Lo
Nominal Cooling
kcal/h 3,400 4,800 6,100 6,900 9,600 12,000 13,800 Cabinet Color White
Capacity *2)
Btu/h 13,600 19,100 24,200 27,300 38,200 47,800 54,600 Dimension H X W X D mm 290 x 830 x 220 290 x 830 x 220 290 x 1050 x 220 290 x 1050 x 220 333 x 11500 x 245
kW 4.8 6.3 8.5 9.0 12.5 16.0 18.0 Net Weight Kg 10 10 12.9 12.9 18
Nominal Heating kcal/h 4,100 5,400 7,300 7,700 10,700 13,800 15,500
Capacity Refrigerant R410A
Btu/h 16,400 21,500 29,000 30,700 42,600 54,600 61,400 Air Flow Rate Hi 2/ Hi/ Me/ Lo m3/min (cfm) 11 11 13.6 16.5 19/17/14/12 22/19/17/15
Sound Pressure Level Motor W 36 36 38 42 40
dB 37/35/31/28 38/35/31/28 38/35/32/29 40/37/33/29 44/42/37/32 48/45/41/35 49/47/42/36
(Overall A Scale) Hi2/Hi/Me/Lo
Connection
Cabinet Color Neutral White
Liquid mm φ 6.35 φ 6.35 φ 6.35 φ 9.52 φ 9.52
Dimensions H x W x D mm 235 x 960 x 690 235 x 1,270 x 690 235 x 1,580 x 690
Gas mm φ 12.7 φ 12.7 φ 12.7 φ 15.88 φ 15.88
Net Weight kg 26 27 35 41
Condensate Drain VP 16
Refrigerant R410A
Approximate Packing Measurement m3 0.1 0.1 0.12 0.12 0.14
Air Flow Rate m3/min. 15/13/11/9 19/16.5/14/11.5 21/18.5/15.5/12.5 30/26.5/22/17 35/31/25.5/20 37/32.5/27/21
Hi2/Hi/Me/Lo (cfm) (530/459/388/318) (671/583/494/406) (742/653/547/441) (1,059/936/777/600) (1,236/1,095/900/706) (1,306/1,148/953/742) Srandard Accessories Wall Mounting Bracket
Motor W 50 80 160
Connections Flare-Nut Connection (With Flare Nuts)
NOTES:
Liquid / Gas mm φ 6.35 /φ12.7 φ 6.35 /φ 15.88 φ 9.52 /φ 15.88 φ 9.52 /φ 15.88 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Condensate Drain VP20 Cooling Operation Conditions Heating Operation Conditions
Approximate Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
m3 0.23 0.31 0.38 *1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
Packing Measurement
*2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
NOTES: 2. The sound pressure level is based on following conditions.
1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. 1.5 Meters Beneath the Unit.
Cooling Operation Conditions Heating Operation Conditions The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
Indoor Air Inlet Temperature: 27˚C DB (80˚F DB) Indoor Air Inlet Temperature: 20˚C DB (68˚F DB)
*1) 19.5˚C WB (67˚F WB) Outdoor Air Inlet Temperature: 7˚C DB (45˚F DB)
*2) 19.0˚C WB (66.2˚F WB) 6˚C WB (43˚F WB)
Outdoor Air Inlet Temperature: 35˚C DB (95˚F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

24 25
All Fresh Air Indoor Unit
Create Comfortable And healthy indoor environment
Indoor Units Create a comfortable and healthy indoor environment by
introducing fresh outdoor air. By heating or cooling fresh outdoor
Floor Type air to almost the same temperature as the room temperature, NOTES:

Floor Concealed Type


fresh ambient air can be adapted and then introduced into indoor 1. The nominal cooling capacity and heating capacity are based on
following conditions: Cooling operation conditions : 330c DB,280c
room. Besides, after filtered, fresh outdoor air in transition WB, piping length: 7.5m, piping lift: 0m Heating operation
seasons can be drawn to indoor room directly with no need of conditions: 00c DB, -2.90c WB, piping length: 7.5m, piping lift: 0m
(Heating capacity is tested when defrosting is not available)
Compact Design heating or cooling operation. While the fresh outdoor air is 2. The sound pressure level is based on the following conditions: 1.5
Special emphasis has been placed on compatibility with introduced, other indoor units don’t bear fresh air load. meter beneath the unit
interior design. The space saving design 630mm in height, The above data was measured in an anechoic chamber so that
Advanced Control reflected sound should not be taken into consideration in the field
220mm in depth, fits into the space below bay windows and 3. An air filter with duct connector efficiency more than 50% needs to
allows the unit to be freely installed without spoiling the Can be interfaced with H-LINKII system, easy electrical wiring be attached to the duct system of the suction side at site.
aesthetics of a room. design and installation. 4. When the resistance of the field-supplied duct is small, it may cause
abnormal stoppage, malfunction, spraying water, etc., due to
Specifications excessive air flow. And the duct which is to be connected to this unit,
Flexible line-up to set-free series shall be insulated for dew protection.
Model
Floor Type Floor Concealed Type NOTES:
1. The nominal cooling and heating capacity
All fresh air indoor units is applicable to SET-FREE outdoor units. 5. All fresh air indoor unit is for processing fresh air load and not for
RPF-1.0FSN2E RPF-1.5FSN2E RPFI-1.0FSNQ RPFI-1.5FSNQ RPFI-2.0FSNQ RPFI-2.5FSNQ stabilizing the room temperature. For adjusting the air conditioning
Indoor unit Power Supply AC 1Ph, 220~240V/50Hz AC 1Ph, 220~240V/50Hz
is the combined capacity of the HITACHI Both SET-FREE indoor units and all fresh air indoor unit can be load of the room, the additional air conditioner is required.
standard split system, and is based on
KW 2.9 4.1 2.9 4.4 5.8 7.3 the JIS standard B8616. used in SET-FREE system. 6. Under cooling mode, when outdoor temperature is lower than 200c,
Normal Cooling Capacity *1 kcal/h 2500 3550 2500 3800 5000 6300 Cooling Operation Conditions the system will automatically shift to ventilation operation; under
Btu/h 9900 14100 9900 15100 19800 25000 Indoor Air Inlet Temperature: Higher external static pressure heating mode, when outdoor temperature is higher than 150c, the
KW 2.8 4 2.8 4.3 5.6 7.1
27˚C DB (80˚F DB) system will automatically shift to ventilation operation; in case inlet
*1)19.5˚C WB (67˚F WB) Better installation flexibility on site, longer ducts can be connected. temperature is below -70c, All fresh air indoor unit will stop
Normal Cooling Capacity *2 kcal/h 2400 3400 2400 3700 4800 6100 *2)19.0˚C WB (66.2˚F WB)
Btu/h 9600 13600 9500 14700 19100 24200 Outdoor Air Inlet Temperature: RPI- RPI- RPI- RPI- RPI- RPI- RPI- RPI-
35˚C DB (95˚F DB) Model RPI-5.0KFNQ RPI-8.0KFNQ
KW 3.2 4.8 3.3 4.9 6.5 8.5 10.0KFNQ 12.0KFNQ 16.0KFNQL 16.0KFNQH 20.0KFNQL 20.0KFNQH 20.0KFNQLF 20.0KFNQHF
Normal Heating Capacity kcal/h 2800 4100 2800 4200 5600 7300 Heating Operation Conditions AC 1φ, 220 AC 1φ, 220 AC 1φ, 220 AC 3φ, 380 AC 3φ, 380 AC 3φ, 380 AC 3φ, 380 AC 3φ, 380 AC 3φ, 380 AC 3φ, 380
Indoor unit Power Supply
Indoor Air Inlet Temperature: V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz V/50Hz
Btu/h 10900 16400 11100 16700 22200 29000 20˚C DB (68˚F DB) KW 14 22.4 28 33.5 45 45 56 56 56 56
Sound Pressure level (Overall dB 35-32-29 38-35-31 35-32-29 38-35-31 39-36-32 42-38-34 Outdoor Air Inlet Temperature:
A Scale) Hi/ Me/ Lo 7˚C DB (45˚F DB) Normal Cooling Capacity *1 kcal/h 12000 19300 24100 28714 38571 38571 48000 48000 48000 48000
Cabinate Color Spring White 6˚C WB (43˚F WB) Btu/h 47800 76400 95500 114379 153643 153643 191200 191200 191200 191200
Piping Length: 7.5 Meters KW 13.7 21.9 24.5 33.5 45 45 56 56 56 56
Dimension H X W X D mm 630X1045X220 630X1045X220 620 X 900 620 X 900 620 X 1170 620 X 1170
Piping Lift: 0 Meter
X 202 X 202 X 202 X 202 Normal Heating capacity kcal/h 11743 18771 21000 28714 38571 38571 48000 48000 48000 48000
2. The sound pressure level is based on
Net Weight Kg 25 28 25 26 31 31 following conditions. Btu/h 46776 74773 83650 114379 153643 153643 191200 191200 191200 191200
Refrigerant R410A 1.5 Meters from the Unit and Sound Pressure level (overall dB 42 44 45 55 57 60 59 63 61 66
Air Flow Rate Hi/ Me/ Lo m3/min 8.5/7/6 10/12/09 07/08/06 08/10/07 14.5/12.5/10.5 16/14/12 1.5 Meters from Floor Level. A scall) Hi2/ Hi/ Me/ Lo
The left data was measured in an Diamension H X W X D mm 370 x 1320 486 x 1270 x 486 x 1270 x 486 x 1270 x 635 x 1950 635 x 1950 735 x 1950 735 x 1950 735 x 1950 735 x 1950
Motor W 20 28 16 25 40 50 anechoic chamber so that reflected x 800 1069 1069 1069 x 805 x 805 x 805 x 805 x 805 x 805
Connection Flare-Nut Connection (with Flare Nuts) sound should be taken into
consideration in the field.
Net Weight Kg 60 97 97 97 196 196 222 222 222 222
Liquid mm φ 6.35 φ 6.35 φ 6.35 φ 6.35 φ 6.35 φ 9.53
Refrigerant R410A R410A R410A
Gas mm φ 12.7 φ 12.7 φ 12.7 φ 12.7 φ 15.88 φ 15.88
Air Flow Rate H i/ Me / Lo m3/hrs. 1080 1680 2100 3000 4000 4000 5000 5000 6000 6000
Condensate Drain φ 18.5OD φ 18.5OD VP 25 (outer Diameter O 32
External Pressure Pa 200 220 220 220 200 300 200 320 200 300
Approximate Packing m3 0.26 0.29 0.19 0.19 0.23 0.23
Measurement Connection
Liquid mm φ 9.53 φ 9.54 φ 9.55 φ 12.7 φ 12.7 φ 12.7 φ 15.88 φ 15.88 φ 15.88 φ 15.88
Gas mm φ 15.88 φ 19.05 φ 22.2 φ 25.4 φ 25.4 φ 25.4 φ 28.6 φ 28.6 φ 28.6 φ 28.6
System Equipment Inlet Fresh Air Temperature m3 Cooling 20 Deg C to 43 Deg C, Cooling 20 Deg C to 43 Deg C, Cooling 20 Deg C to 43 Deg C,
Range Heating -5Deg C to -15 Deg C Heating -5Deg C to -15 Deg C Heating -5Deg C to -15 Deg C

Total Heat Exchanger Model


Indoor unit Power Supply
RPI-12.0KFNQ
AC 3φ, 380 V/50Hz
RPI-16.0KFNQL
AC 3φ, 380 V/50Hz
RPI-16.0KFNQH
AC 3φ, 380 V/50Hz
RPI-20.0KFNQL
AC 3φ, 380 V/50Hz
RPI-20.0KFNQH
AC 3φ, 380 V/50Hz
RPI-20.0KFNQLF
AC 3φ, 380 V/50Hz
RPI-20.0KFNQHF
AC 3φ, 380 V/50Hz
Specifications KW 33.5 45 45 56 56 56 56
NOTES: Normal Cooling Capacity *1 kcal/h 28714 38571 38571 48000 48000 48000 48000
Model KPI-2521 KPI-5021 KPI-8021 KPI-10021 *1. Use it under the following Btu/h 114379 153643 153643 191200 191200 191200 191200
Indoor Unit Power Supply AC 1 , 220-240V / 50Hz, 220V / 60Hz conditions. KPI-8021: 29Pa or
KW 33.5 45 45 56 56 56 56
more, KPI-10021: 49Pa or more
Air Flow Rate 50Hz m3/h 250/250/165 500/500/350 800/800/670 1,000/1,000/870 *2. The sound pressure level is Normal Heating capacity kcal/h 28714 38571 38571 48000 48000 48000 48000
Hi/Me/Lo 60Hz m3/h 250/250/150 500/500/300 800/800/660 1,000/1,000/720 based on following conditions. Btu/h 114379 153643 153643 191200 191200 191200 191200
External Pressure *1) 50Hz Pa 65/40/20 150/60/30 140/100/70 160/100/80 1.5 Meter beneath the unit and
Sound Pressure level (overall A dB 55 57 60 59 63 61 66
this data was measured in an scall) Hi2/ Hi/ Me/ Lo
Hi/Me/Lo 60Hz Pa 100/50/20 200/60/20 230/120/80 200/110/60 anechoic chamber so that
Sound Pressure Level reflected sound should be taken Diamension H X W X D mm 486 x 1270 x 1069 635 x 1950 x 805 635 x 1950 x 805 735 x 1950 x 805 735 x 1950 x 805 735 x 1950 x 805 735 x 1950 x 805
(Overall A Scale) at 50Hz dB 26.5-27.5/25-26/21-22 32.5-33.5/30-31/23.5-24.5 33.5-34.5/32-33/30-31 36-37/34-35/31.5-32.5 into consideration in the field. Net Weight Kg 97 196 196 222 222 222 222
1.5m from the unit *3. The sound pressure level is
under *2) *3) Refrigerant R410A R410A
60Hz dB 28.5/25.5/21 32.5/28.5/23 35/31/29 36/34/30 based on the total heat
Air Flow Rate H i/ Me / Lo m3/hrs. 3000 4000 4000 5000 5000 6000 6000
Hi/Me/Lo exchange mode. In case of the
bypass ventilation mode, the External Pressure Pa 220 200 300 200 320 200 300
Dimensions H x W x D mm 275 x 735 x 780 317 x 1,016 x 888 398 x 1,004 x 1,164 398 x 1,231 x 1,164
sound pressure level is incrased Connection
Net Weight kg 21 33 61 72 by approximately 1dB(A).
Liquid mm φ 12.7 φ12.7 φ 12.7 φ 15.88 φ 15.88 φ 15.88 φ 15.88
Approximate Packing Gas mm φ 25.4 φ25.4 φ 25.4 φ 28.6 φ 28.6 φ 28.6 φ 28.6
Measurement m 3
0.26 0.46 0.70 0.84
Inlet Fresh Air Temperature Range m3 Cooling 20 Deg C to 43 Deg C , Heating -5Deg C to -15 Deg C

26 27
Optional Parts Remote Controllers
Indoor Units
The newly-adopted LED-backlit LCD provides enhanced 4 type of menus are offered for flexible use as follows:
Remote Control Switch
4-Way Cassette Type legibility. Large, clear character display is realized by Full Menu: Contains “Schedule”, “Elevating Grill”, etc. for users.
HP 1.0 ~ 6.0 PC-ARF Dot Matrix LCD. Help Menu: Contains information provided by
this remote control switch for users such as
Fresh Air Intake Kit *1 OACI-160K2 Compatible with the H-LINK II The newly-adopted directional key provides optimized “About Indication”, “Contact Information”, etc.
T-Pipe Connection Kit *2 TKCI-160K operation. The manual operation is facilitated by reducing Test Run Menu: This menu provides the functions
Duct Adapter *3 PD-75A ( 75) number of switch buttons from 13 to 9. installation of this remote control switch.
Check Menu: This menu provides the functions for service
“Schedule Timer” provides the timer operations for “Run/Stop” and maintain
and “Temperature Setting”. The weekly management is
Receiver Kit for Wireless Control available by using this function. In addition “Holiday Setting”
RCI RCD RPC RPI RPF(I) RPK and “Schedule ON/OFF”setting are available.

Model PC-ALHN PC-ALHD PC-ALHP1 PC-ALHZ PC-ALHZF

NOTES: The PC-AR has a design that matches the interior. A "self-diagnosis function" checks for problems on printed
*1. It is necessary to use the Fresh Air Intake Kit to connect the fresh air intake duct to the unit. Remote Control Switch
boards in indoor andoutdoor units.
*2. Used when two air intakes (φ100 x 2) of the Fresh Air Intake Kit are changed to one air intake (φ150 x 1). The new large LCD display permits users to see the
*3. Used when fresh air intake duct are connected to the indoor unit directly. PC-AR operating conditions and settings. Equipped with energy-saving functions such as a preset
*4. Used when both of the Fresh Air Intake Kit and Filter Box are used. Compatible with the H-LINK II temperature range limiting function for preventing
*5. The electronic expansion valve kit (optional part EV-1.5N1) should be used with indoor unit wall type The timer can be set at half-hour intervals up to 72 hours. excessive cooling/heating and a preset temperature
without expansion valve together. automatic reset function, as well as an operation locking
All the functions can be selected by remote control switches. mechanism and the capability to prevent users from
The PC-AR monitors the operating conditions in the forgetting to turn off the system.
Piping Connection Kit Strainer Kit system and an alarm is issued if a problem occurs. (Function selection setting is required)

Outdoor Unit HP Outdoor Unit Model Piping Set Product Name Model
Number
Strainer Kit MEF-NP1500A
20-24 2 MC-20SNK 1
26-32 2 MC-30SNK 1 One-touch handy operation, no wiring work required.
34-54 3 MC-30SNK 2
Wireless
Remote Control Switch Two or more units can be operated simultaneously by remote control.
* Receiver kit is required.
Multi-kits PC-LH3A PC-LH3B
Compatible with the H-LINK II
Multi-kit for 2 Pipe Heat Pump Operation
< Line Branch > (First Branch)

Outdoor Unit HP Model


8 to10 E- 102SNK
Half-size The main function of this easy-to-use remote control "2 remote control" or "group control" (up to 16 max.) can
12 to 16 E-162SNK system is temperature setting. be used.
Remote Control Switch
18 to 24 E-242SNK Operation modes can be switched over If a problem occurs, an alarm code immediately shows the
26 to 54 E-302SNK PC-ARH (when function selection setting is made). details of the problem.
NOTE: After the second branch, please refer to the technical manual. Compatible with the H-LINK II
Suitable for facilities used by various people, such as hotels.

Control System : Applicable : Not Applicable


RCI-FSN3 RCI- RCD-FSN2 RPIZ- RPI- RPI-FSNA RPC-FSN3 RPK-FSNA RPK- RPF- RPFI- KPI RCIM- 7 Day Timer By using PSC-A1T with PSC-5S, PSC-A64S or PC-AR Two types of weekly schedule (A and B) can be set,
FSN1Q FSN1Q FSNQL(H) FSNSM3 FSN2E FSNQ FSN3 controllers, the air conditioners controlled by them can be and can easily be changed for summer and winter.
PC-AR(*1) × ˜ ˜ ˜ ˜ ˜ × ˜ × ˜ ˜ ˜ × PSC-A1T operated according to a schedule.
Settings are all digitally displayed, allowing operations
Compatible with the H-LINK II The timer can be set at 7-day intervals, and operation/stop and settings to be checked easily.
PC-ARF ˜ (*5)
˜ ˜ ˜ ˜ ˜ ˜ (*5)
˜ ˜ (*5)
˜ ˜ ˜ ˜ (*5)
can be set 3 times daily.
PC-LH3A × ˜ ˜ ˜ ˜ ˜ × ˜ × ˜ ˜ × ×
The power failure backup function prevents the timer
Remote control can be prohibited in accordance with the from being stopped by a power failure lasting up to 2
PC-LH3B ˜ × × × × × ˜ × ˜ × × × ˜ OFF time (when used with PSC-5S, PSC-A64S and PC-AR). weeks.
PC-ARH(*2) ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ × ˜

PSC-A1T(*3) ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ × ˜

PSC-A64S(*4) ˜(*6) ˜(*6) ˜(*6) ˜(*6) By connecting to the H-LINK, up to 64 remote control An external input terminal is provided as standard.
˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜
Central Station
groups and 160 indoor units can be controlled. External signals enable thefollowing functions:
PSC-128WX,PSC-AS2048WXB ˜ (*6)
˜ ˜ ˜ ˜ ˜ ˜ (*6)
˜ ˜ (*6)
˜ ˜ ˜ ˜ (*6)

PSC-A64S   Up to 8 units can be connected to the H-LINK. central operation/stop, demand control,
PSC-A16S ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ emergency stop, central operation output,
Compatible with the H-LINK II In addition to basic controls such as settings for and central alarm output.
PSC-5K,10K,15K for PC-AR ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ operation/stop, the operation mode and temperature,
Up to 160 indoor units
the air quantity and auto louver can be set. Can be used in combination with the One-touch Controller.
PCC-1A ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ Up to 64 remote control groups If a problem occurs, an alarm code immediately shows
THM-R2A ˜ ˜ ˜ ˜ ˜ ˜ ˜ ˜ × ˜ ˜ × ˜ the details of the problem.

Centralized Only performs operation/stop control per remote An external input terminal is provided as
control group. standard. External signals enable the
ON/OFF Controller following functions:
By connecting to the H-LINK, up to 16 remote control central operation/stop, emergency stop,
PSC-A16RS groups and 160 indoor units can be controlled. central operation output, central alarm output
Compatible with the H-LINK II Up to 8 units can be connected to the H-LINK.
Up to 160 indoor units Can be used in combination with the Central Station.
* Make sure to use it with a remote control switch. Indoor units cannot be used without a remote control switch.
Up to 16 remote control groups
* There are restrictions on remote group registration. Please contact our sales staff for more information.

28 29
Network Systems Compare with H-LINK System
Item H-LINK H-LINK II

H-LINK II Max. Number of Refrigerant Group / System 16 64


Address Setting Range of Indoor Units / Refrigerant Group 0 to 15 0 to 63
Hitachi's proprietary high-performance transmission Regardless of Multi-Split System for Buildings or Max. Number of Indoor Unit / System 128 160
system for connecting control wires between indoor and Packaged System for Commercial Use Total Number of Devices in the same H-LINK 145 200
outdoorunits, and between a centralized control system and Max. Wiring Length
By providing a common control function and wiring Total 1,000m (5,000m)*
indoor/outdoor units, across two or more refrigerant systems.
method, a multi-split air conditioning system for buildings * : In case 4 units of PSC-5HR are used.
Flexible Wiring Routes
and a packaged air conditioning system for commercial
Absolutely no restrictions on the order of wiring, the wiring route use are simultaneously used in the same system, and so
and the number of branches. Simply connect to the adjacent are the EHP air conditioning systems. Just connect all the

Mixture of H-LINK and H-LINK II


units or the terminal block of a centralized control system. systems with twin core cables by crossover connection.
The H-LINK transmission system for connection between Adapters or other appliances are not required.
outdoor and indoor units provides an extended system
The models supporting H-LINK II can be mixed with the models supporting H-LINK in the same system without any adaptor.
configuration and improved functions without sacrificing
workability and the flexibility. Outdoor Unit 1(One) H-LINK (II) System
Control System Device
Indoor Unit Outdoor Units (Number of Ref. Groups) Indoor Units

H-LINK II 64 160
H-LINK II
Example H-LINK II/ H-LINK Mixed 16 * 128
H-LINK II 16 128
H-LINK
H-LINK II/ H-LINK Mixed 16 128

: H-LINK II Control Wiring


* : A maximum 16 refrigerant groups can be connected in one H-LINK system under the following conditions.
・Outdoor unit corresponding to H-LINK
・Outdoor unit corresponding to H-LINK II connected with the indoor unit corresponding to H-LINK
Outdoor Unit (Max. 64 Refrigerant System)* More than 17 indoor units can be connected with the 1 outdoor unit depending on the outdoor unit capacity. In that case, 2 ref. groups are required for 1 outdoor unit.

Indoor Unit (Max. 160 Units)* System Configuration


SET-FREE FSN(1) Series SET-FREE FSXN1 and FSXNH Series
Outdoor Unit
H-LINK H-LINK II

* : The above example shows the case that


central control device, indoor units and Indoor Unit
remote control switch are all corresponding H-LINK II H-LINK H-LINK II H-LINK II H-LINK H-LINK II
or or
to H-LINK II system. H-LINK H-LINK

Remote Control Switch


H-LINK H-LINK II H-LINK II H-LINK H-LINK II H-LINK II

Setting Range of Refrigerant Group*1) 0 to 15 0 to 15


Setting Range of Address*1) 0 to 15 0 to 15 0 to 15 0 to 15 0 to 15 0 to 63
Automatic Reset of Setting Temperature*2)
Operation Lock*2)
CS-NET BMS Limitation of Setting Temperature Range*3)
ON / OFF Timer Setting (72Hr.)*2)
Different Operation Mode Indication*3)
Indoor Unit Hot-Start Indication*3)
Change of Indoor Unit Ref. Group No. and Address*2)
Central Station Central Station Centralized ON/OFF 7 Day Timer Outdoor Unit Comp. Pre-heating Indication / Cancel*2)
PSC-5S
Controller Emergency Operation from Remote Control Switch*4)
PSC-A1T
PSC-A64S PSC-A16RS HARC70-P1 HC-A64BNP
*1): The range of ref. group setting and address setting is 0 to 15 when H-LINK corresponding central controller is used.
*2): These functions can be set by wired remote control switch (PC-AR) only.
*3): These functions can be set by wired remote control switch (PC-AR) and half size remote control switch (PC-ARH) only.
*4): This function is not available depending on the outdoor unit type.

30 31
Network Systems Interface
CS-NET You can select the air conditioner control interface depending on your needs to create a comfortable space.

Connection Method to
CS-NET is Hitachi's control network system for the SET-FREE FS series, SET-FREE FSNM and UTOPIA ranges. HC-A64BNP (for BACnet )
R

Upper System • Connection by IEEE802.3 Compliance (100BASE-TX/10BASE-T) to BACnet Network R

The flexibility of the SET-FREE system allows the internal data to be easily accessed and controlled by the user, Quantity of Connection • Up to 64 Indoor Units per BACnet Adaptor
R

with features including temperature, mode and fan speed setting and groupings.
• RUN/STOP • Available / Not Available for Operation by
Control Item at • Operation Mode Setting Remote control Switch
Upper System • Temperature Setting • Filter Sign Reset
BACnet *1 • Fan Speed Setting
Building
R

Central Station DX Connecting the HC-A64BNP to an H-LINK • RUN/STOP State Notification • Indoor Suction Temperature Notification
Management Management Software Central Station
(communication line between machines) Monitoring Item at • Alarm Signal Notification • Alarm Code Notification
PSC-AS2048WXB
System P.C. (Field supply) (CD-ROM) PSC-A64S allows control of up to 64 indoor units. Upper System • Operation Mode State Notification • Communication Abnormality Notification
PSC-5S *3 • Fan Speed State Notification • Filter Sign
Up to eight HC-A64BNP can be connected to
*2 the same H-LINK.
LONWORKS R

H-LINK II or
Open Network H-LINK
Systems Connection Method to • Connection by SNVT (Standard Network Variable Type) to
HARC70-P1 (for LONWORKS )
R

Upper System LONWORKS Network


R

LAN (Ethernet)
PSC-A128WX Centralized Quantity of Connection • 8 Remote Control Groups (Max. 120 indoor Units)
7 Day Timer
ON/OFF Control Item at • On/Off Order • Temperature Setting
HARC70-P1 Controller Upper System • Operation Mode Setting • All On/Off Order
Central Station EZ
or HC- Monitoring Item at • On/Off State & Alarm • Temperature Setting
A64BNP Upper System • Operation Mode State • Individual Thermostat State
By using the HARC70-P1 adapter for LONWORKS
R

PSC-A1T
to connect air conditioners to the total building
PSC-A16RS control system, air conditioners can be centrally
HARC-BX
controlled.
PSC-A64GT H-LINK II or
H-LINK
H-LINK*4 H-LINK II or H-LINK II or
HARC-BX E (Standard)
H-LINK H-LINK
HARC-BX (for LONWORKS )
R

Connection Method to • Connection by SNVT (Standard Network Variable Type) to


Upper System LONWORKS Network
R

Outdoor Units H-LINK II or Quantity of Connection • 64 Indoor Units


H-LINK • On/Off Order • Temperature Setting
Control Item at
Upper System • Operation Mode Setting • All On/Off Order

Monitoring Item at • On/Off State & Alarm • Temperature Setting


Upper System • Operation Mode State • Individual Thermostat State

H-LINK II or HARC-BX E (Option A)


SET-FREE FSXNK SET-FREE FSNMA
H-LINK Connection Method to • Connection by SNVT (Standard Network Variable Type) to
Upper System LONWORKS Network
R

Quantity of Connection • 64 Indoor Units


Indoor Units A HARC-BX can connect to multiple H-LINK
Control Item at • On/Off Order • Temperature Setting • Fan Speed Setting
with H-LINK transmission terminal to 8 PCB.
Upper System • Operation Mode Setting • All On/Off Order • R.C.Sw Permission/Prohibition

Points for control and monitor have been increased Monitoring Item at • On/Off State & Alarm
RCI RPI RPK RPFI
Upper System • Inlet Air Temperature
to meet more points. (Points for control and
RCD RPC RPF KPI *3 monitor is 8 times larger than HARC70P-1.) HARC-BX E (Option B)
Connection Method to • Connection by SNVT (Standard Network Variable Type) to
Upper System LONWORKS Network
R

You can select the number of controls, monitor,


Remote Controllers and what to control in the indoor unit from three Quantity of Connection • 32 Indoor Units
choices (Standard, Option A and Option B) as • On/Off Order • Fan Speed Setting • All On/Off Order
*1: BACnet is a registered trademark of ASHRAE.
R

Control Item at
*2: LONWORKS is a registered trademark of
R
needed. Upper System
• Operation Mode Setting • R.C.Sw Permission • Louver Position Setting
Echelon Corp. • Temperature Setting /Prohibition
*3: Compatible H-LINK
• On/Off State & Alarm • Temperature Setting • Inlet Air Temperature
PC-LH3A *4: Though connection with H-LINK II is available, Monitoring Item at
Upper System • Operation Mode State • Louver Position • Outlet Air Temperature
PC-ARF PC-AR PC-LH3B Receiver Kit PC-ARH the resulting performance is equivalent to that
of the H-LINK specifications. • Fan Speed Setting • Alarm Code • Outdoor Air Temperature

32 33
Network Systems
Central Station

Central Station EZ
PSC-A64GT
Eazy control with 8.5 inch color touch panel
Its down-to-detail control functionalities,
Specification for Management Computer
such as Weekly Scheduling, Accumulated Work Hours, etc., help you save energy.
Up to 64 remote-controlled groups and up to 160 indoor units can be connected to the single air-conditioning system. Central Station DX OS Windows XP (English version 32 bit)

PSC-A128WX + PSC-AS2048WXB CPU CPU Intel Core TM 2Duo 1.8GHz or more


Memory 2GB or more
Functions
Free Space in Minimum 5GB for each H-LINK + 0.3GB for each additional REFGN Cycle.
• Run/Stop/Abnormality • Operation Mode
Hard Disk Drive (Further additional 16GB or more is required for Check-Unit data collection.)
• Setting Temperature • Setting Fan Speed • Setting Louver
Monitor Function Display Resolution 1,280 x 1,024
• RCS Operation Prohibited Setting • Filter Sign • Alarm Code
• Accumulated Operating Time Drive CD-ROM Drive (for upon installation only)
IEEE 802.3 (10BASE-T/100BASE-TX) (With wake-on-LAN function*2)
• Run/Stop* • Operation Mode • Temperature Setting
Control Function Interface USB
• Fan Speed • Louver • RCS Operation Prohibited • Filter Sign Reset
RS-232C (*2)
*: groups
“All Groups Run/Stop” command signal exception function for selected
is available by “Exception of Run/Stop Ope.” function. *1: Use the management computer exclusively to this system.
*2: LAN with wake on LAN function or RS-232 Interface is required for UPS.
*3: Management computer is assumed to be always ON. It is strongly recommended to use
computer for server or industrial use and/or to create hard disk mirror.
Specification for Management Computer *4: Durable period for management computer may differ from that of air conditioners.
Update periodically and discuss updating procedure in advance.
Communication Unit Units of Adopting for H-LINK II
Communication Line Non-Polar 2-Wire
Communication Method Half-Duplex Communication Functions
Synchro System Asynchronous (start-stop synchronous communication) Managing maximum 2,048 groups of • Run/Stop • RC (Remote Control Switch) Operation Prohibition
Communication Speed 9,600bps air-conditioners. Up to 2560 units of indoor Energy Saving • Shifting Set Temperature (For Cool/Dry to Fan and Stop during Heating)

Wiring Length 1,000m (Total Length) units can be controlled and monitored with Function • Switching Mode (Cool/Dry to Fan and Stop during Heating)

Outdoor Unit Indoor Unit Central Controller Total Unit Number just one computer. • Outdoor Unit Capacity Control
Connecting (Only if supported) (0, 40, 50, 60, 70, 80, 90, 100%)
H-LINK II 64 160 8 200 Advanced functions but easy control for huge
Unit Number* air-conditioning system.
H-LINK 16 128 8 145 Facility Control • Run/Stop • Operation Mode (Cool/Heat)
Control • Emergency Stop (Only for Indoor Units Supporting this function)
: Connecting unit quantity indicates the maximum unit numbers which is possible to connect in the same H-LINK (Control Wiring). and
*
Monitor Function • Run/Stop • Operation Mode (Cool/Heat)
(Level Signal Only) Monitor
• Alarm State

34 35