Professional Documents
Culture Documents
Lectura Microgrids PDF
Lectura Microgrids PDF
Tine L. VANDOORN,
Juan C. VÁSQUEZ,
Jeroen DE KOONING,
Josep M. GUERRERO, and
Lieven VANDEVELDE
T
Image licensed by Ingram Publishing
Secondary Control
Microgrid Control: Overview
Concerning grid control, islanded mi- Primary Control
crogrids have specific characteristics
that differ significantly from those of Communications
the traditional power system. First,
in conventional grids, when an unbal-
ance occurs between the generated Local Local Local
power of the sources and the electri- Control Control Control
cal power consumption, the power is
instantly balanced by the rotating iner-
tia in the system, resulting in a change
of frequency. This principle forms the Microgrid
basics of the conventional primary
control, i.e., the active power/grid FIGURE 1 – MicroGrid communications, local and centralized controllers.
constant-power band) to more ex- In the measurements, an I dc /V g droop equals - 0.04 A/V and the droop of the
treme voltages [Figure 5(b)]. controller is included, analogous to Vg /Vdc droop controller equals 1 V/V.
Table 1 and Figure 6 show some the P/V g droop controller, with I dc The DG units are operated as
measurement results of the VBD con- the dc-side current, I dc,nom = 2 A, current sources, and the effect of
troller. The measured DG unit ter- Vdc,nom = 200 V, Vg,nom = 160 V, the a changing load and dc current are
minal voltage of case 7 is depicted droop of the I dc /Vg droop controller measured. When comparing cases
in Figure 6(a), and the accuracy of
the voltage tracking is illustrated in
Figure 6(b). The microgrid test setup
consists of two DG units connected to 200
a load. The load consists of either a 150
13 or 27 X. The inverters of the DG 100
50
units have been realized by using a
Vg (V )
0
printed circuit board (PCB) that was
–50
developed in Ghent University. The
–100
switches consist of insulated-gate –150
bipolar transistors (IGBTs) with a –200
maximum collector–emitter voltage 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
t (s)
of 1200 V and a collector current of
(a)
40 A. The dc side of the inverter, i.e.,
160
the energy source, is emulated as a
150
dc current source by means of the
140
Sorensen SGI6000/17C source. The
130
Vg (V )