Project: Short Circuit 1 ETAP Page: 1

12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
1/2 Cycle Network

Swing V-Control Load Total


Number of Buses: 1 2 2 5

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 3 0 0 1 0 0 4

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load
Total
Number of Machines: 3 0 0 0 0 3

System Frequency: 50.00 Hz

Unit System: English

Project Filename: Short Circuit

Output Filename: C:\ETAP 1260\Short Circuit\ShortCircuit1.SA2


Project: Short Circuit 1 ETAP Page: 2
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project: Short Circuit 1 ETAP Page: 3
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 SWNG 13.800 13.800 1 100.00 0.00

Bus2 Gen. 13.800 13.800 1 100.00 60.00

Bus3 Load 20.000 20.000 1 100.00 30.00

Bus4 Load 20.000 20.000 1 100.00 30.00

Bus5 Gen. 13.800 13.800 1 100.00 60.00

5 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Project: Short Circuit 1 ETAP Page: 4
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Line/Cable Input Data

Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable Length

ID Library Size Adj. (ft) % Tol. #/Phase T (C) R1 X1 Y1 R0 X0 Y0

Line1 34,4 49212.6 0.0 1 75 0.0914400 0.0609600 0.0609600 0.0914400

Line / Cable resistances are listed at the specified temperatures.


Project: Short Circuit 1 ETAP Page: 5
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift


ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

T1 60.000 13.800 20.000 12.50 45.00 0 0 0 0 0 12.5000 YNd 30.000

T2 50.000 13.800 20.000 12.50 45.00 0 0 0 0 0 12.5000 YNd -30.000

T3 40.000 13.800 20.000 12.50 45.00 0 0 0 0 0 12.5000 YNd -30.000

2-Winding Transformer Grounding Input Data

Grounding

Transformer Rating Conn. Primary Secondary


ID MVA Prim. kV Sec. kV Type Type kV Amp Ohm Type kV Amp Ohm

T1 60.000 13.800 20.000 D/Y Solid

T2 50.000 13.800 20.000 D/Y Solid

T3 40.000 13.800 20.000 D/Y Solid


Project: Short Circuit 1 ETAP Page: 6
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus1 Bus3 0.46 20.83 20.83

T2 2W XFMR Bus2 Bus3 0.56 24.99 25.00


T3 2W XFMR Bus5 Bus4 0.69 31.24 31.25

Line1 Line Bus3 Bus4 112.50 75.00 135.21


Project: Short Circuit 1 ETAP Page: 7
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Synchronous Generator Input Data


Positive Seq. Impedance
Synchronous Generator Rating % Xd" Grounding Zero Seq. Impedanc
ID Type MVA kV RPM X"/R %R Adj. Tol. % Xd' Conn. Type Amp X/R % R0 % X0

Gen1 Turbo 23.529 13.800 1500 1.00 0.200 0.20 0.0 20.00 Wye Solid 1.00 0.200 0.20

Gen 2 Turbo 11.765 13.800 1500 1.00 0.250 0.25 0.0 20.00 Wye Solid 1.00 0.250 0.25

Gen3 Turbo 29.412 13.800 1500 1.00 0.200 0.20 0.0 10.00 Wye Solid 1.00 0.200 0.20

Total Connected Synchronous Generators ( = 3 ): 64.706 MVA


Project: Short Circuit 1 ETAP Page: 8
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus5

Prefault voltage = 13.800 kV = 100.00 % of nominal bus kV ( 13.800 kV)


= 100.00 % of base kV ( 13.800 kV)

Positive & Zero Sequence Impedances


Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus5 Total 0.00 437.592 0.00 100.09 100.10 436.740 436.740 6.76E-001 6.76E-001 6.80E-001 6.80E-001

Bus4 Bus5 19.01 2.545 56.42 68.33 100.00 1.694 0.000 1.14E+002 1.18E+002
Gen3 Bus5 100.00 435.047 100.00 100.00 100.00 435.047 436.740 6.80E-001 6.80E-001 6.80E-001 6.80E-001

# Indicates fault current contribution is from three-winding transformers

* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: Short Circuit 1 ETAP Page: 9
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Short-Circuit Summary Report

1/2 Cycle - 3-Phase, LG, LL, & LLG Fault Currents

Prefault Voltage = 100 % of the Bus Nominal Voltage

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV Real Imag. Mag. Real Imag. Mag. Real Imag. Mag. Real Imag. Mag.

Bus5 13.80 309.392 -309.457 437.592 308.801 -308.843 436.740 267.997 267.941 378.966 -422.103 -113.825 437.181

All fault currents are symmetrical momentary (1/2 Cycle network) values in rms kA

* LLG fault current is the larger of the two faulted line currents
Project: Short Circuit 1 ETAP Page: 10
12.6.0H
Location: LAB DSTL UNSRI Date: 09-14-2019
Contract: 03041181621024 SN:
Engineer: Diaz Dwirahma Yuda Revision: Base
Study Case: SC
Filename: Short Circuit Config.: Normal

Short-Circuit Summary Report

Bus Positive Sequence Imp. (ohm) Negative Sequence Imp. (ohm) Zero Sequence Imp. (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus5 13.800 0.01287 0.01288 0.01821 0.01287 0.01288 0.01821 0.01295 0.01295 0.01831