You are on page 1of 12

Type M100

Energy Meter

Type M100
Energy Meter

T&D
Protection & Control
Type M100 Energy Meter

Fig 1.: M100

Features Application Functions


• Active and reactive energy M100 applications include; One or two parameters, according
metering to the model ordered, selected from:
• Energy measurement to
• Single phase or three phase IEC 61036 Class 1.0 Import active energy
connection Whtotalimport
• Replacement/upgrade of existing
• Balanced or unbalanced load energy meters Export active energy
Whtotalexport
• One or two line LCD display • Energy metering for building
Import reactive energy
(one line per counter) management or power
management systems using VArhtotalimport
• Pulsed outputs available pulsed outputs
(1 or 2, as an option) Export reactive energy
The M100 is intended for use on VArhtotalexport
• Setting of CT primary value systems where energy monitoring is
required, being capable of Configuration
• Compact design
providing display of one or two It is possible to modify the following
Introduction metering quantities, each of which parameters, using the optional
can be specified for active or external pushbutton:
The M100 energy meter uses
reactive power, and for import or
numerical technology to achieve Current transformer primary value
export measurement. Options also
high accuracy over a wide dynamic
provide pulsed outputs for 1 or 2 Reset of energy meters
measuring range. It measures
measurements. In this application,
energy for single or three phase
the M100 provides a more compact
systems. Housed in a DIN standard
solution than electromagnetic
96mm by 96mm case, the M100 is
devices.
compact, rugged and ideal for
panel mounting in power
distribution and power monitoring
applications.

2
u v
1

3 11

U V 2

Out 1 Out 2 Supply


k l

Load
A
K L

Fig 2.:
Typical diagram - single
phase connection N

Notes: Connect two wire auxiliary supply terminals marked ‘supply’ if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.

u v u v

U V U V 3

2 5 8

Out 1 Out 2 Supply


k l

Load
A
K L

Fig 3.: B
Typical diagram - three phase,
three wire balanced load
C

Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.

u v 1

3 11

2
U V
Out 1 Out 2 Supply
k l

Load
A
K L

Fig 4.:
Typical diagram - three phase, C
four wire balanced load
N

Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.

3
u v u v

1 7
U V U V 3 9

2 5 8

k l Out 1Out 2 Supply

Load
A
K L
k l
B

Figure 5: C
Typical diagram - three phase, K L
three wire unbalanced load
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.

u u u
11

x x x
1 4 7
X X X 3 6 9 11

2 5 8
U U U

k l Out 1 Out 2 Supply

k l
A
K L
k l
B
K L

C
K L

Figure 6: N
Typical diagram - three phase, Load
four wire unbalanced load
Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.
Out 1/Out 2 are volt-free contact pulse outputs, if fitted.

Out

100ms

24V DC R>100R
Power supply
Pulse receptor
Figure 7: 0V
Connections for pulse output

4
Hardware Description Procedure for resetting (b) To change to the next digit
channel 2 hold the setting button until
The M100 is housed in a DIN case ‘E’ is displayed and
with maximum dimensions of 96mm by Press the setting button twice and release. Repeat
96mm by 96mm. hold.
steps 1 and 2 until the
M100 variants are available for single correct CT ratio is set.
phase systems or 3 phase 3 or 4 wire
2*RESET* 5 CT=00000/5
systems, with balanced or unbalanced
loads.
The above display is shown. SET
The front panel contains a 1 or 2 line The display will show the far right 4. When changing the CT primary
alphanumeric liquid crystal display of digit count down from 5 to 0 and settings the last digit set should
16 characters per line, with a then return to the normal working be the far right digit as shown
character size of 4.86mm by 2.96mm. display. The counter should have below.
Measuring circuit connections on the reset to zero. If the setting button is
released before zero count is 5. Once this digit has been set,
rear are by means of individual M4 press the setting button and
screw clamp terminals, auxiliary and reached the counter will not reset.
release when ‘E’ is displayed.
pulsed output connections using M2.5
terminal blocks. A copy of the relevant Procedure for changing the 6. This will enter the new setting
DIN circuit diagram is printed on a CT ratio into the unit. If you finish on any
label on the device. other digit, the unit will default
1. Press the setting button three
back to the original setting.
times and hold until the CT ratio
User Interface is displayed. 7. If the device is left in the CT
If the external pushbutton option has setting mode it will
2. Press the setting button once.
been selected, the configurable automatically change to the
Rolling characters, +, –, b, E
normal working display after
features of the M100 can be accessed should appear in the bottom
30 seconds, defaulting to the
through a menu-driven system. The right hand corner of the display.
latest fully programmed value
menu is arranged as shown below:
3. Hold the setting button in until E (ie. any incomplete changes
Active and reactive energy are is displayed, then release. SET will be lost).
displayed when the device is will appear under the CT ratio
switched on. and an underscore will appear
under the first digit as shown
below.
*123456789 Wh
000001234 varh CT=00000/5
SET
Procedure for resetting
channel 1 (a) To increase the digits by
one, press and hold the
Press the setting button once and hold.
setting button until a ‘+’ is
displayed and release. To
1*RESET* 5 decrease the digits hold the
setting button until a ‘–’ is
displayed and release.
Repeat step (a) until the
The above display is shown. correct reading is
The display will show the far right digit displayed.
count down from 5 to 0 and then
return to the normal working display.
The counter should have reset to zero.
If the setting button is released before
zero count is reached the counter will
not reset.

5
Technical Data AC auxiliary supply Design
• Standard auxiliary voltages (Vx) • Protection
Accuracy 63.5V, 110V, 230V IP52 on front of panel
• Active and reactive energy
• Optional auxiliary voltages • Safety IEC 61010-1
IEC 61036 Class 1.0
Compliant intallation category II
50V to 250V
Voltage input
600V
• Supply voltage range
• Standard rated voltages (Vn)
Pollution degree 2
0.8 to 1.2Vx
63.5V, 110V, 230V, 400V
• Installation category III 300V
• Burden
• Optional rated voltage
Pollution degree 2
<3VA
50V to 440V
• Weight
• Overload 2Vx for 1s
• Voltage measuring range with
0.5kg
Display
separate auxiliary supply
• LCD
0.1 to 1.5Vn Ambient conditions
2 lines JVF (DIN 40 040)
• Self-powered
• Number of digits • Temperature
0.8 to 1.2Vn
9 digits Reference range of operation
• Burden with auxiliary supply
• Height of digits 0°C to +50°C
<0.1VA
4.86mm Rated range of operation
• Burden self-powered
• Width of digits –10°C to +60°C
<3.0VA
2.96mm Storage
• Rated frequency
Relay outputs –40°C to +60°C
50Hz or 60Hz
• Relay contact rating • Humidity
• Frequency range
AC: 250V, 6A, 50Hz up to 95% (without condensing)
45Hz to 65Hz
DC: 24V, 0.25A resistive Mechanical environment
• Overload
• Maximum switching power • EMC
2Vn, 10s
1500VA RFI radiated immunity

Current input • Maximum number of pulses IEC 61000-4-3


• Rated current (In) 4000 per hour 10V/m
1A, 5A • Pulse duration • EFT burst
• Maximum current (Imax) 100ms IEC 61000-4-4 level 4
1.6In 4kV
• Burden • ESD electrostatic discharge
<0.1VA IEC 61000-4-2
• Overload 3In continuously 8kV
50In for 1s

6
Case
The M100 is housed in a 96mm x
96mm x 91mm plastic case in
compliance with UL 94-V0. See
Figure 8.

96mm 5mm 91mm*

Terminal 1

M4 96mm
Terminals

92mm (+0.8, –0)

92mm (+0.8, –0)

* includes terminals/panel fixing

Figure 8: Case outline

7
Information Required with Order

M 1
Numeric instrumentation
Panel mounted energy meter

Application
Panel mounted energy meter 1

Connection options
Single phase 1
3 phase 4 wire, balanced 2
3 phase 3 wire, balanced 3
3 phase 3 wire, unbalanced 4
3 phase 4 wire, unbalanced 5

Display options
Wh only 1
VArh only 2
Wh/VArh 3
Wh/Wh 4
VArh/VArh 5

CT secondary
1A 1
5A 5

VT secondary
63.5V B
110V E
230V V
400V 4

Frequency
50 – 60Hz X

Auxiliary rating
63.5 B
110V E
230V V

No. of pulsed outputs


None 0
One 1
Two 2

External reset facility


Not fitted 0
Fitted 1

8
Extra information required with order
CT ratio
VT ratio

Display 1

Display 2

Active energy meter A


Reactive energy meter R

Import energy meter I


Export energy meter E

Lagging VArs as positive +


Lagging VArs as negative –

If pulse outputs are required:

Relay 1 Relay 2
Wh or varh
Import or export
Energy per pulse

Notes on ordering
The standard devices on offer reflect the new normalised European voltage, eg. 230V L-N will work on a 220V or
240V system. Therefore, if for example a 220V unit is requested, a nominal 230V unit will be supplied.
NB. The unit of measurement displayed changes according to the change in CT ratio. The energy per pulse is related
to the displayed value. See Table 1 below for default settings.

Effect of CT primary rating on energy per pulse for 5A secondary

Table 1

9
ALSTOM T&D Protection & Control Business contact addresses

PCB Head Office Australia and Pacific Islands


International Contact Centre ALSTOM AUSTRALIA Ltd
ALSTOM T&D P&C On line 24 hours a day Protection & Control Division
Le Sextant Tel: +44 (0)1785 25 00 70 PO Box 22, 25 Princes Road
3, avenue André Malraux Fax: +44 (0)1785 27 24 51 Regents Park, NSW 2143 Sydney
92300 Levallois-Perret - FRANCE www.tde.alstom.com/p-c/en/contcent.htm AUSTRALIA
Tel: +33 (0)1 41 49 20 00 Tel: +61 29 645 0777
Fax: +33 (0)1 41 49 24 85 South East Europe Fax: +61 29 743 8488
protection.control@tde.alstom.com ALSTOM AUSTRIA AG pcb-map.australia@tde.alstom.com
Hietzinger Kai 169
A1130-Vienna - AUSTRIA
Western Europe Tel: +43 1 87893 726 North and South America
and Africa Fax: +43 1 87893 750
pcb-gee.austria@tde.alstom.com USA, Panama and Caribbean
United Kingdom and Northen Europe
ALSTOM T&D BITRONICS Inc.
ALSTOM T&D P&C Ltd Central Europe
261 Brodhead Road
St Leonards Works - Stafford ALSTOM T&D SA
Bethlehem, PA
ST17 4LX - UNITED KINGDOM uI. Strzegomska 23/27
18017-8698 - USA
Tel: +44 (0)1785 223251 58-160 Swiebodzice - POLAND
Tel: +1 610 865 2444
Fax: +44 (0)1785 212232 Tel: +48 74 854 84 10
Fax: +1 610 865 0340
pcb-wea.uk@tde.alstom.com Fax: +48 74 854 85 48
pcb-gee.poland@tde.alstom.com
France, Belgium and Luxembourg, Canada
Mediterranean and Africa ALSTOM CANADA Inc.
ALSTOM T&D P&C SA Middle East Asia and Pacific 845 Harrington Court
Avenue de Figuières Burlington
34975 Lattes Cedex - FRANCE Middle East Asia Ontario L7N 3P3 - CANADA
ALSTOM T&D P&C Ltd Tel: +1 905 333 3667
Tel: +33 (0)4 67 20 54 54
12th Floor, Cresent Tower Fax: +1 905 333 0840
Fax: +33 (0)4 67 20 54 99
Buhaira Corniche - PO Box 25448 pcb-nsa.canada@tde.alstom.com
pcb-wea.france@tde.alstom.com
Sharjah - UNITED ARAB EMIRATES
Tel: +971 6 556 3971
Italy Fax: +971 6 556 1082 Mexico
ALSTOM FIR S.p.A pcb-map.uae@tde.alstom.com ALSTOM T&D SA DE CV
Viale Giulio Cesare, 29
Alce Blanco 13-A
24124 -Bergamo - ITALY India and South Asia
Naucalpan de Juarez
Tel: +39 035 5791611 ALSTOM INDIA Ltd
CP 53370 Mexico City - MEXICO
Fax: +39 035 5791662 Protection & Control Division
pcb-wea.italy@tde.alstom.com 19/1 GST Road Pallavaram Works Tel: +52 5 358 27 22
Chennai (Madras) 600 043 - INDIA Fax: +52 5 358 83 93
Spain and Portugal Tel: +91 44 236 8621 pcb-nsa.mexico@tde.alstom.com
ALSTOM T&D, S.A. Fax: +9144 236 7276
Paseo de la Castellana, 257 pcb-map.india@tde.alstom.com Central and South America
28046 Madrid - SPAIN
Tel: +34 91 334 59 43 South East Asia ALSTOM INTERNATIONAL (PERU)
Fax: +34 91 334 59 42 ALSTOM T&D P&C Ltd Edificio Las Naciones
pcb-wea.spain@tde.alstom.com 31 Kaki Bukit Road 3 Avenida Central 643 - Piso 1
#02-05, Techlink San Isidro - Lima 27 - PERU
South Africa Singapore 417818 - SINGAPORE Tel: +51 1 221 7954 /1208
ALSTOM MEASUREMENTS Tel: +65 843 3130 Fax: +51 1 221 1209
PO Box 24 Fax: +65 846 1796 pcb-nsa.peru@tde.alstom.com
Primrose 1416 pcb-map.singapore@tde.alstom.com
Gauteng, SOUTH AFRICA Brazil
Tel: +27 11 820 5111 China and North East Asia ALSTOM T&D Ltd
Fax: +27 11 820 5323 ALSTOM T&D P&C Protecção e Control
alstomm@iafrica.com Room 910-912, 9th floor Avenida Interlagos 4211
New Kowloon plaza CEP-04661-300 São Paulo
38 Tai kok Tsui road São Paulo - BRAZIL
Germany
Kowloon, Hong Kong - CHINA Tel: +55 (0)11 3491 70 00
and Eastern Europe
Tel: +852 2833 6265 Fax: +55 (0)11 3491 73 00
Germany and Switzerland Fax: +852 2834 5279 pcb-nsa.brazil@tde.alstom.com
Russian Speaking Countries pcb-map.china@tde.alstom.com
ALSTOM ENERGIETECHNIK GmbH ALSTOM T&D Shanghai South America
Bereich Schutz- und Power Automation Co. Ltd ALSTOM ARGENTINA SA
Schaltanlagenleittechnik 1/B Building - No. 499 Kangyi Road Protección y Control
Lyoner Straße 44-48 Pudong Kangqiao Av. Leandro N. Alem 896 - Piso 5
D 60528 Frankfurt/Main - GERMANY Industrial Development Zone 1001 Buenos Aires - ARGENTINA
Tel: +49 69 66 32 33 33 Shanghai 201315 - CHINA T el: +54 11 4891 9600 / 9666
Fax: +49 69 66 32 25 48 Tel : + 86 (21) 5812 8822 Fax: +54 11 4311 1040
pcb-gee.germany@tde.alstom.com Fax : + 86 (21) 5812 8833 pcb-nsa.argentina@tde.alstom.com

10
Notes:

Your contact:

11
© 2002 ALSTOM - 010201 Flash Espace
Publication: M100/EN BR/Ef

T R A N S M I S S I O N & D I S T R I B U T I O N Protection & Control, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 27 24 51

ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure
should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

You might also like