TEST REPORT 21601486-OYC

Date 14 NOV 2016 Page 1 of 3


Singapore Laboratory Services Pte Ltd
64 Tuas South Ave 2 Singapore 637525
Phone +65 6686 3375 Fax +65 6686 3230

SUBJECT:

Testing of geocomposite material

TESTED FOR:

Geocom Engineering
35 Pioneer Road North,
PCI Building, Ground Floor,
Singapore 628475

Attn: Mr Benny Neo

SAMPLE SUBMISSION DATE:

31 Oct 2016

DATE OF TEST:

11 Nov 2016

METHOD OF TEST:

ASTM D4716 : 08 (Reapproved 2013) Standard test method for Determining the (In plane) Flow Rate per
Unit Width and Hydraulic Transmissivity of a Geosynthetic Using a Constant Head.

Sample length : 100mm x 300mm


Vertical pressure : 10kPa 100kPa and 200 kPa
Hydraulic gradient : 1.0
No. of tested specimen : 1 per direction

DESCRIPTION OF SAMPLE:

One piece of geocomposite drainage material identified as “Geocom Geonet” was received.
Thickness: 5mm

Terms and conditions:


1. The result in this report applies to the sample as received from the client at the time of its testing. The result is not intended to be representative of other similar items. This test report may not be used to indicate or imply that Singapore Laboratory
Services endorse the test sample mentioned in the report.
2. Singapore Laboratory Services assumes no responsibility for the accuracy of information and/or details of the samples as supplied by the client.
3. This report shall not be reproduced wholly or in parts and no reference shall be made by the client to Singapore Laboratory Services without the written consent of Singapore Laboratory Services.
4. This report may not be used in any publicity material without the written permission of Singapore Laboratory Services.
5. The tests were carried out at Singapore Laboratory Services unless otherwise stated.

Singapore Laboratory Services is an ISO / IEC 17025 accredited laboratory.


TEST REPORT 21601486-OYC
Date 14 NOV 2016 Page 2 of 3
Singapore Laboratory Services Pte Ltd
64 Tuas South Ave 2 Singapore 637525
Phone +65 6686 3375 Fax +65 6686 3230

TEST RESULTS:

Table 1 - Flow capacity, refer to figure 1


Geocom Geonet

In-plane flow capacity per unit width, q stress/gradient #

Model Type q 10/1.0 (l/msec) q 100/1.0 (l/msec) q 200/1.0 (l/msec)

Geocom Geonet 0.42 0.37 0.27


# Calculated based on 20°C water

Ong Yeo Chuan Lee Shen Sun, Jimmy


Testing Officer Vice President

Terms and conditions:


1) The result in this report applies to the sample as received from the client at the time of its testing. The result is not intended to be representative of other similar items. This test report may not be used to indicate or imply that Singapore
Laboratory Services endorse the test sample mentioned in the report.
2) Singapore Laboratory Services assumes no responsibility for the accuracy of information and/or details of the samples as supplied by the client.
3) This report shall not be reproduced wholly or in parts and no reference shall be made by the client to Singapore Laboratory Services without the written consent of Singapore Laboratory Services.
4) This report may not be used in any publicity material without the written permission of Singapore Laboratory Services.
5) The tests were carried out at Singapore Laboratory Services unless otherwise stated.
TEST REPORT 21601486-OYC
Date 14 NOV 2016 Page 3 of 3
Singapore Laboratory Services Pte Ltd
64 Tuas South Ave 2 Singapore 637525
Phone +65 6686 3375 Fax +65 6686 3230

Terms and conditions:


1) The result in this report applies to the sample as received from the client at the time of its testing. The result is not intended to be representative of other similar items. This test report may not be used to indicate or imply that Singapore
Laboratory Services endorse the test sample mentioned in the report.
2) Singapore Laboratory Services assumes no responsibility for the accuracy of information and/or details of the samples as supplied by the client.
3) This report shall not be reproduced wholly or in parts and no reference shall be made by the client to Singapore Laboratory Services without the written consent of Singapore Laboratory Services.
4) This report may not be used in any publicity material without the written permission of Singapore Laboratory Services.
5) The tests were carried out at Singapore Laboratory Services unless otherwise stated.

You might also like