with the Water Regulations is a minimum of 750mm from ground level to the top of the pipe barrel, and a maximum of 1350mm, unless in a duct. Where pipes are located below a road the depth should increase to 900mm and be ducted. Where water pipes are laid in a service strip close to other services, the National Joint Utilities guidance documents recommends that the depth of the water service is at 900mm throughout to coordinate with the depth of the other services, and enable services to cross each other. The minimum distance between the water pipe work and other sevices is recommended as being 350mm.