IF FIRST REFNET TO FARTHEST INDOOR UNIT ACTUAL PIPING LENGTH IS MORE THAN 40MTRS,

THEN HEADER PIPE BETWEEN REFNET TO REFNET (OR HEADER) FOR THAT LONGEST BRANCH
NEED TO BE SIZE UP AS PER BELOW TABLE -

6.4mm (1/4") >>>> 9.5mm (3/8") 28.6mm(1 1/8") >>>> 31.8mm(1 1/4")
9.5mm (3/8") >>>> 12.7mm(1/2") 34.9mm(1 3/8") >>>> 38.1mm(1 1/2")
12.7mm(1/2") >>>> 15.9mm(5/8") 41.3mm(1 5/8") >>>> 41.3mm(1 5/8")
15.9mm(5/8") >>>> 19.1mm(3/4")
19.1mm(3/4") >>>> 22.2mm(7/8")
22.2mm(7/8") >>>> 25.4mm(1")

IF OUTDOOR UNIT TO FARTHEST INDOOR UNIT EQUIVALENT PIPING LENGTH IS MORE THAN 90MTRS,
THEN SYSTEM MAIN HEADER PIPE NEED TO BE SIZE UP AS PER BELOW TABLE -