You are on page 1of 1

Amps X 100 Bus1 (Nom. kV=4.16, Plot Ref. kV=4.

16)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

CB3
500 500

300 R FM4 300


800/5

Bus1
4.16 kV
100 100

50 50

30 30

Finish Mill 4
∆ 6.12 s
10 10

5 5
Seconds

Seconds
3 FM4 - P 3
OC1
CT Ratio 800:5
IEC Standard Inverse Time SIT/A
Finish Mill 4-100% Pickup = 512 A
1 1865 KW Time Dial = 1.7 1
12s Ramp Inst = 2000 A
Time Delay = 0.18 s
.5 .5

.3 .3

.1 .1

.05 .05

.03 .03

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Bus1 (Nom. kV=4.16, Plot Ref. kV=4.16) ETAP Star 16.2.0C

Star2

Project: Date: 08-29-2019


Location: SN: CONTRLGEAR
Contract: Rev: Base
Engineer: Fault: Phase
Filename: D:\EPMG\2019\RCBMI\BTG\Finish Mill 4\Finish Mill 4.OTI