DESCRIPTION OF RELAY PROTEC'HON
BK 60-311 E
BER, Doc., 2985
Enol.: 7452 283 F
7452284 5, 74589966 Reg. 7452
Genorator proteotion for STAL turbines
satel
i
¢
g
i
Edition 1 Size approx. 3-50 MVA
1. Introduction ‘The generator protections described below are for STAL turbines
ra
2, Neutral -point
eartaing
Earth-fault
gurrent
{contra-rotation turbines) with a total generating output within the
range 5-50 MVA, i.e,, mainly industrial turbines, Protections of
this design hes long been standard.
Generators for STAL turbines do not require any more comprehensive
protective arrangements than other generators, The design of contra~
rotation turbines with twin generators directly connected in parallel
implies, however, that the protective gear in some cases will have
a unique disposition.
Generators of this size are normally fitted with longltudina! differen~
tial protection, which in this case is common to both generators. The
‘over-current protection, whose task is then primarily fo oparats
tupon the ocourrence of external faults, is therefore introduced only
‘on the one generator, Tn atldition, an interturn short-cireuit protec~
tion common to both generators is incorporated, and this protection
ig hare mate hoth simple and effective and will also operate upon
phase intorruption.
As the two excitation windings are connected in series, it is possible
to incorporate 2 simple bridge type protection against rotor inter~
turtis of section faults and rotor winding open—olrouits,
‘The protections, which, when operating always effect stopping of
the turbine, give 2 tripping impulse to the turbine trip solenafd oaly.
‘When the emergonoy stop valvo subsequontly closes, = limit switoh
on it will trip the main clrouit-breaker and the field switch,
‘The recommended relay settings can be seen on sheet 6 .
In the case of a stator earth fault, a high earth-fault current mey
cause extensive and severe damage to the stator laminations, especi-
ally if the fault is of long-duration. A general rule is therefore that
in the oase of generators (or motors) that are directly connected t
a network the earth~feult current should be limited to a harmless
value.
im the cage of a very low earth-fault current, a normal earth-fault
signal may be sufticient, but if the current exceeds 10 to 15 A, auto-
matic, selective earth-fanit tripping shoald be arranged. With currents
of the order of 50 to 100 A or more, especially rapid tripping is neces-
sory.
Ta the following text tt has heen assumed, in the case of turbine sets
dixectly connected to a network, that the neutral points of the gena=
rators are not earthed. They may only ke earthed after careful eon-
sideration. Of importance ia this connection is whether other neutral
points are earthed in the nework, how they are earthed, and the size
of the network’s own capacitive earth-fault current.723 eval
ASEA
Information
DESCRIPTION OF RELAY PROTECTION RFR, Dec., 1965 RK 60-311 E 2
3. Diagrams
4. Deseription
4.1 Diagram
7452 283
412
4.12
Reg. 7452
A generating set connected to its own step-up transformer, on the
other hand, should have one generator neutral point earthed throagh
a high resistance. (See sheet 5 )
‘The diagrams enclosed refer to the following cases:
7452 283 ‘The generators connected directly to a network with an
insignificant earth-feult current (and in certain cases
where there is a particularly high earth-fault current,
See under "4, 1.2 Differential protection" below)
7452 264 The generators connected directiy to a network with such
2 high earth-fault current {for example > 10 to 18 A) that
automatic earth-fault tripping is required.
7452 286 The generators connected to their own step-ap transformer
without distribution at the generator voltage.
Diagram 7452 283 comprises the following relay protections:
Over-current protection for the generators.
The time-lag over-current relays 19 are connected’ to the current
transformers 3 5 on the neutral side, They may be inverse time-teg
over-current relays of type RI and RIDI or cefinite time-lag over-
current relays of type RIDA, depending on which type of relays are
‘used in the network,
in the case of an over-current, the relays trip the generator eircuit-
breaker after 3 certain time-lag. If the aver-current is caused by an
overload of a short circuit outside the circuit-breaker, it then ceases
immedistely and the relays will reset instantaneously. The turbine
under n0-load ezn then he easily reconnected to the network. If, on
the other hand, the over-current remains, as will be the case upon a
short circuit within the circuit-breaker, for example in one generator,
the time-lag relay 23:7 provides an irapulse to the trip! solenoid of
the turbine after a further 0,5 sec {epprox.), which also results in
field switeh tripping and demagnetization.
In the case of a short circuit outside the generators, for example on
the busbars, the over-current protection operates in the normal way,
even if the two generators begin to oscillate in relation to each other.
The over-current relays, of course, only sense the short-circuit
current of their own generator and not any possible oscillations in the
total current from the two generators.
Differentis! protection commen to both generators
‘The differential protection of type RYDHA works in accordance with
the high-impedance principle and bas the following characteristic
properties:
Speed - operating time approx, 15 ms (excluding auxiliary relay).ASEA
DESCRIPTION OF RELAY PROTECTION RFR, Dec., 1965 {RK 60-311 E
448
ald
Information
Reg. 7452
Sensitivity - primary operating current approx, 2-4 % of the total
normal current of the generating set
Stability - ebsolute stability upon the presence of faults outside
the protective zone.
With regard to the design and mode of operation of the protection,
see the specific déscription RK 60-301 E.
The protection 20 is connected to its own current-transformer cores
2 aon the line side and 3 a on the neutral side of each generator.
All nine current-transformer cores must have the same turns-ratic
but need not otherwise be identical. No other relays or instruments
may be connected to these cores, The auxiliary relay built into the
protection provides a direct actuating Impulse to the trip solenoid,
the main circuit-breaker and the field switch.
The three-phase differential protection also operates upon the presence
of earth faults if the earth-fault current exceeds the operating value of
the protection, This value is normally so iow that in networks with a
‘high earth-fault current (for example 50 to 106 A or more) the diffe-
rential protection may be considered as 2 fully satisfactory earth-
fault protection and in addition an extremely rapid one. Ia this case,
no special earth-fault protection as in diagram 7452 284 {see under
4.2 below) is necessary.
Over-voltage protection consisting of a time-lag over-voltage relay 22
‘of type RIB 51 with a time -lag inversely dependent on the rise in
voltage. The relay anc the voltage regulator should be supplied by
separate voltage transformers,
Ef the load disappears, the voltage regulator should intervene and limit
the rise in voltage. Owing to the time-lag, the protection then has no
opportunity to operate. In the ease of a lasting rise in voltage, for
example if a fault in the regulator or excitation system results in
full excitation, ou the other hand, the protection should operate. In the
case of parallel operation with other generators, overexcitation causes
over-current aud the over-current protection will trip the generator
circuit-breaker. At the subsequently rise in voltage the voliags relay
then actuates the stop-valve, whereupon demagnetization takes place.
Interturz short-circuit protection for the stator windings.
This consists of an over-yoltage relay 23:1 fed by 2 voltage trans-
former 9 connected between the two neutral points. Across this trans-
former normally only a low yoltage occurs, mainly consisting of
harmonics which do not affect the relay since the latter is fitted with
aharmonic filter 28:3. In the case of an interturn short circuit in
one phase of the one generator, on the other hand, a voltage is obtained
with the frequency of the fundamental that is so great that the relay
operates and provides an actuating impulse to the turbine trip solenoid
via a time-Lag relay.
Before the two generators are synchronized (running-up) a considerable
voltage may build up between the neutral points. The interturn short~
circuit protection is therefore blocked during starting by an auxiliary
contact on the main circuit-breaker.erie
3
2
ASEA
DESCRIPTION OF RELAY PROTECTION RFR, Dei
4.45
4.1.6
4.17
44,8
Information
RK 60-311 E
21965,
Reg. 7452
Field winding protection against short circuits and interruptions in
the generstor fields.
A voltage relay (18 and 24:1) is bridge-connected to the two excitation
windings connected in series. Under normal conditions, the relay,
for reasons of symmetry, receives no voltage at all or only an In-
significant one. In the case of rotor open circuit, or a short circuit
of a part of the winding, the syrumetry is disturbed. The relay then
actuates the turbine trip solenoid via the time-lag relay 24:5,
During runring-up, also the field winding protection is blocked by
#n auxiliary contact on the main cirouit-breaker. The conductors
to the voltage divider 18 are protected upon short circuit by a resis-
tor 16 and a miniature circuit-bresker 17. Both should be placed as
close to the excitation circuit as possible.
Short-cirouiting a part of one of the rotor windings involves unequal
excltation of the twin generators and a reactive compensation current
passing between them. Together with the lond current, this current
Tight cause a thermal overload, which lg prevented by the operation
of the above-mentioned protection.
Earth-fault signal for the excitation circult
Across a capacitor 15, a voltage transformer 14 continuously feeds
an alternating voltage {40 V) into the excitation circuit. Upon the
oceurrence of an earth fault in the latter, the a.c. circuit is closed
and the current relay 24:8 actuates a signal relay with a time-lag.
Normally, a emall current flows through the relay, doponding on the
capacitance to earth of the excitation circuit and the relay current
netting should be safely higher than this current.
The voltage transformer should be jed from the aoxillary low voltage
supply or from another (HV) voltage transformer (220 or 110 V, 50 o/s)
via a mintature ciroutt-breaker with a signal contact.
‘The design of the protection will in principle be the same with an ex-
citation system including a.c. exciter and rectifier as with a d.c.
exciter.
General earth-fault signal
Upon the appearance of an earth fault in the generators or in the not-
work, the neutral-point voltage relay 25 connects in a time-lag signal
relay. As an alternative, the neutral -point voltage relay can be con-
neoted to voliage transformers on the ousbars.
‘The reverse power protection is intended to prevent the generaiors
from motoring when steam -supply is shut off, as there is then a
risk of dangerous overheating of the blading system. Reverse power
protection is, however, only necessary with back-pressure turbines.
In the case of condensing turbines, motoring does not involve ary
Gangercus overheating of the blading system if there is a full vacum.
Vacuum failure will result in direct tripping of the turbine,7D aval
IMI vs
ASEA
Information
DESCRIPTION OF RELAY PROTECTION RFR, Dec., 1965 RK 60-311 E a
Reg. 7452
419
4.2 Diagram
‘TA52 284
4.3 Diagram
7452 286
‘The single-phase power relay 20 should be connected to the current
transformers of one generator and is designed for a sensitivity of
approx, 1% of the rated power, In the case of reverse power, the
main circuit-breaker effects tripping via a time-lag relay 81:1 with
a setting of about 20 seconds.
Each projection is fitted with its own indicating device, which is
visible in the window of the relay case and can be Teset by hand.
Al! protections are provided with a relay testing switch and test bolts.
When the switch is set in its central position, the tripping circuit is
opened. In addition, when switching over to the test position. the relays
are disconnected from the measuring transformers and the current
transformers are short-circuited.
Diagram 7462 284 comprises the same equipment as the shove
7452 233 with the addition of a sensitive and selective earth-fault
protection which disconnects the set upon the occurrence of an earth
fault in the generators.
‘The protection consists of a sensitive earth-fault relay 26 connected
to three current transformer cores 2 of its own ln direct zero
sequence connection. Provided that the neutral points of the STAL
generators are uncarthed, the protection operates oaly upon the
presence of an earth fault on the generators, and not wher faults in
the network ocour. The protection effects tripping via a time-lag
relay 26:3 with a low setting.
When there is an over current (for example upon a short circuit in
the network), differeness between the current transformers may
foed to a spill current through the earth-fault relay. In order to
prevert undesired tripping, the instantaneous break contacts K6-K7
{ihe starting contacts) on the time-lag over-current relays 19 of
type RIDA block the earth-fault protection. In addition, tripping is
made depeadent on the neatral-point voltage relay 28:1, the make
eoatect of which is comiected in series with the earth-fault relay
make contact.
If, instead of RIDA, tirme-lag overcurrent retays of type RI or RIDL,
which lack an instantancous starting contact, are used, two instan-
taneous current relays must be introduced for the purpose af block-
ing. A svecial diagiam (7452 285) will be supplied upon request.
Diagrem 7452 286 refers to generators connected directly to their
‘own step-up transformer and differs from 7452 283 in the following
respects:
‘The general earth-faull signal has been replaced by a aeutrat-point
voltage relay 29:1, which provides a tripping impulse via a ime-lag
relsy 29:5 upon the occurrence of zn earth fault on the low-voltage
side, und protects approx. 95 % of the generator winding. The neutral
point voltage relay connected to the voltage transformer 11 is Fitted with
a harmonic filter 29:3 to climinate the effects of the harmonic voltages
occuring at the generalor neutral point.
If an earth fault ocours on the high-voltage side of the transformer,
a neutral-point voltage transmitted eapacitively is obtained on the
low-voltere side. One generator neutral point is therefore earthed
across a high-resistance which limits the transmitted voltage to a
nln lace thar the nnawntine cntita af thm maaten) nine wedfcoe prebaxeASEA Information
DESCRIPTION OF RELAY PROTECTION | RFR, Dec., 1965__RK 60-311 E
Reg. 7452
The selection of the resistor is dependent on the size of the whole
set and on whether the high-voltage side network is directly earthed
or not. With a max. 50 MVA transformer, a resistor for approx. 5A
at fall neutral-point voltage is sufficient. Furthermore, tha resistor
prevents the occurrence of dangerous over-voltages if an earth fault
should occur on the low-volizge side,
In addition, the generator differential protection is replaced by 2
transformer differential protection (20 a and b) of type RYDSA.
common to both the generators and the transformer. The outstand-
ing characteristics of this protection axe: shart operating time
(approx. 25 ms) and effective restraint against undesired operation
Upon the occurrence of external faults and other disturbances. For
farther information, see the specific description 7454 112 E or cata
logue RK 62 E. The protection is connected to taree current trans~
formers 2 a on the high-voltage side and to three current transform-
ers 3 on the neutral side of each generator. The tripping pulse is ob~
tained directly from tripping relays built into the protection.
5, Relay settings ‘The following settings can normally be recommended.
5.1 Diagram
7452 283, Point Relay No. Quantity Setting
Ad. 19 Current 1.4 to 2.5 times the rated current
of each generator
Time longer than for the over-current
protection of the outgoing lines
23:7 ‘Time approx, 0,5 sec.
4.1.2 20 Voltage fixed setting
410 82 Voltage 20-26 % shove the normal sorvico
voltage of the generator
Time 4-6 sec.
4.14 281 Voltage 1-1. times the lowest velue on
the seale
23:5 Time approx. 1 sec.
ALS 241 Voltage 8-10 %
24:8 Time approx. 1.8 sec.
4.1.8 2h Current 0.91-0.018 A
47 85 Voltage 15-20 % of the full neutral-point
voltage
418 90 Power approx. 1 % of the rated power
Si:l ‘Time approx, 20 sec.
5.2 Diagram As above with the addition of
‘a2 284 42 26 Current lowest scale value
28:3 Time approx. 0.5 sec.
6.9 Diagram Ac above with the addition of
1452 286 4.3 2a Current approx. 20 % of the rated current
29:1 Voltage lowest scale value, normally approx.
5% of the full neutral -point voltage
29:5 Time aparox, 1 sec.—
= ionwss 090)
= RAY THLE AY
EEE SS OL | worpmyand weyaausy
pee pbaiag ip Si
tig «5
ayo oye BrraBiaue wo gona parasre
Bos
Woee COAL
ya eee Revabscus yop BEDonc ya oy,
ue
joaboa
‘709 oi
Fe
e
z for
¢ a 5
=
ia cota —
"ext
082 ELhL ae cee Rabe om gat PY 8
7 ¥ z 7