207C.6.3 Design Wind Loads
Simplified design wind pressures, p,, for the MWERS of
low-rise simple diaphragm buildings represent the net
pressures (sum of internal and external) to be applied to the
horizontal and vertical projections of building surfaces as
shown in Figure 207C.6-1. For the horizontal pressures
(Zones A, B,C, D), By is the combination of the windward
and leeward net pressures. pg shall be determined by the
following equation:
Ps = AK uPss0 (207C.6-1)
where
a adjustment factor for building height and
‘exposure from Figure 207C.6-1
Ky topographic factor as defined in
Section 207A.8 evaluated at mean roof
height, A
Psao simplified design wind pressure _ for
Exposure B, at h~ 9 m from Figure 207C.6-
1
CHAPTER 2~ Minimum Design Loads 2-115
207.64 Minimum Design Wind Loads
‘The load effects of the design wind pressures from Section
207€.633 shall not be less than a minimum load defined by
assuming the pressures, p,, for zones A and C equal to
+766 Pa, Zones B and D equal to +383 Pa, while assuming
a for Zones E, F, G, and Hare equal to 0.0 Pa.
‘National Structural Code of the Philippines Volume I, 7th Edition, 201524116 CHAPTER 2 — Minimum Design Loads
|. Pressures shown are applied to he horizontal and vertical projections, foreaposure B, at k= 91m. Adj oother exposures and height
with adustnet factor A
2. The load pattems show shall be spied to each comer ofthe uilingin tum asthe reference comer. (See Figure 20741)
3. PorCase Buse @ = 07
Load eases | and 2 must be checked for 25" < @ < 45°, Load case at 25° is provided only for interpolation between 25° and 30°,
5. Plus and minus signs signify pressures acting toward and away from the projected surfaces, respectively
6. Forwof slopes other than those show linear ntepoaton is permite
7. The toa horizontal oad shall ot be less than that determined by assuming py =O in zones Band D.
8. Where zone Eo G fills on aro ovethang on the windward side ofthe building, use Eoy std Goy, forthe pressure onthe horizontal
Projection ofthe overhang. Overhangs on the Lewatd an side edge shal have the basi re pressure ppd
9, Notation:
1: 10% of leas horizontal dimension oF 04h, whichever i salle, but nt less than either 4% of lest horizontal dimension or 0.9 m
2s Mean oot height im meters, excep thi cove height shal be use for oof angles = 10!
(0 Angle of plane of rot from horizon in degrees
Figure 207C.6-1
Main Wind Force Resisting System ~ Method 2.Design Wind Pressure
Enclosed Buildings h << 18 m Walls and Roofs
Association of Structural Engineers af the Philippines, Inc, (ASEP)CHAPTER 2~Minimum Design Loads 2-1
] Zones
Angle | Load | Horizontal Pressures Vertical Pressures Overha
(degrees) | Case | a | B | e | c | u | con | con
ose | 1 | 066 | -034 | 044 04s | -0.55 | 035 087
[10° 1 074 -o48 | -0.55 | 037 “087
15° 1_| oss 0.16 | -079 | 052 | -o55 | 039 | ssn | 087
[20° 1_| os -0.13 | -0.79 | 085 | -055 | -042 | -141_ | -087
25° 1 0.83 0.14 | 037 | 05 | -0.27 | 041 | -068 | -058
2 | 0 0 | 0.14 | -027 | -oo4 | o1s | 0 0
soto4se |_1_| 074 oa | 0.06 | -0.45 039 | 026 | 03
2_| 074 oat | 029 | -0.22 ois | -026 | -03
ows? | |r 036 | 141 | -08 062 | -197 | «isa
10° 1 | 132 [055 | oss | -032 0.86 0.67 -1.54
1s 1_| 148 | -o48 | 098 | 028 092 07 “1.54
20° 1_| 1.62 | -0.43 | 1.08 | -0.23 0.98 0.74 154
a 1_| 14s | 023 | 107 | 0.25 0.89) 072 | 122 | -103
2 |o | o |olo 0.48 032 | 0 o
aotase |__| 132 [09 [1.05 [072 “08 0.68 | -046 | 053
2 | 132 | 09 | 10s | 072 039 -028 | 046 | 053
ows? | 1 | 183 | -095 | 122 | -057 “125 097 | -308_| 2.41
10° 1_| 2.06 | -o86 | 1.37 | -0.49 “134 -104 | 308 | 241
15° 1_| 231 | -076 [153 | 044 | 22 | -144 -109 | 308 | 241
20° 1_| 283 | -o67 | 169 | 037 | 22 | -1.53 116 | 308 | 241
oe 1_| 231 | 037 | 167 | 039 | -1.02 | -139 “13 “1.62
2 | 0 [| o [o | o [039 | 076" 049 | 0 0
sora |__| 206 | a | 164 | 13 | one | 12s -107 | -072 | 083
2 | 206 [iar [164 [113 [079 | 002 04s | -o7 | -083
Figure 207C.6-1
Main Wind Force Resisting System — Method 2 Design Wind Pressure
Enclosed Buildings h < 18 m Walls and Roofs, Simplified Design Wind Pressure, Psy (Pa)
(Exposure B at h= 9.0m with I= 1.0
National Structural Code of the Philippines Volume |, 7th Edition, 20152-418 CHAPTER 2 Minimum Design Loads
bi zone
Wint | oot | | Herz Pasa Wert eee Tay
speed | date, [ae a wfc | > |e [ow] fom
ows Lt [aa tas fs | ae [a 22 [aoe | sas
ie fo fast fam [ive] on | sar 22 [ae [aa
ww fob “096 [anos | 307 22 [ae [ase
LL oat [oar bass [aw | 2 | age | tee | 278
2 oo | 0 [056 “ous [on | 0
ew Tt 301 [236] ue | 02 oa [ass | ai
oer fa stae [2ae [ur | 432 2 [a9 | 608
ft “i [20 [or | 432 “3200 [508
15° 1 148 3 0.86 | -4.32 3 2.14 6.04
sow fe “ia jaan pom [an [ame | 60s
Lt tn am fus | 2 [an}ass | 22 | 33
vo fo fo] 0 [om }aas oa | cor | o
2 4.04 | 2.76 | 3.21 | 2.21 1.55 | -121 135, 0.86 “141
djinga Factor or Bung Helgh aad Exponrs 4
cd Taysare
Height (m)_ B Cc D
0-5 1.0 121 147
a ts
8 10 135 1.61,
5 eo
[ons f os
eee
Enelosed Buildings h = 18 m Walls and Roofs, Simplified Design Wind Pressure, psy (Pa)
Figure 207C.6-1 (continued)
‘Main Wind Force Resisting System ~ Method 2 Design Wind Pressure
(Exposure B at = 9.0 m with f = 1.0
Association of Structural Engineers of the Philippines, Inc. (ASEP)