Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
overcurrent protective relay of Grand Rapids hydro generator compensation highlights the problem in protective relays and
in Manitoba Hydro system [15-16]. in voltage profile during fault condition. In a radial series-
SSR is mostly concern in turbo generators [17] whereas, in compensated power system, the electrical resonance
[18] stated that hydro generator could be possibly exposed to frequency is given by the following formula [21].
a harmful shaft torque as a result of superimposed sub and
=± (5)
super synchronous fault currents following upon a fault in the
series compensated grid. Hence, in order to investigate Where fs is power system nominal frequency
impact of SSR on hydro generators Grand Rapids station in XL is total inductance of the grid
Manitoba Hydro system is considered as an example. Current flowing to the grid circulates to armature winding
In this paper, Manitoba Hydro network with several power of the generator and interacts with turbine-generator rotor as
sources including Grand Rapids hydro generator and a double sub harmonic and super harmonic frequencies. As shown
circuit transmission line with a length of about 500 Km [19] below, the current includes fundamental component (grid
is simulated in PSCAD/EMTDC software. Reactance of frequency) and also another sinusoidal components are
double circuit line is compensated by suitable placement of determined by existing elements in the grid. [21-22].
series capacitance [16]. Impact of SSR on operation of ( )= sin( 1 + 1 ) + − 2 sin( 2 + 2 ) (6)
different types of protective relays such as distance relay with Where: ζ is damping ratio given by (7).
OSB element, out of step protection of generator (pole = (7)
2
slipping), differential and overcurrent relay is analyzed in the
network. Out of step protection of generator is configured to ω2 is damping frequency as follow.
separates the generator from the grid in case of pole slipping 2 = 1− 2 (8)
to maintain stability of the network. It decides to operate or ωn is un-damped natural frequency as follow.
restrict operation according to protection strategy. 1
= (9)
This paper mostly focuses on behavior of OOS generator
protection function during SSR. Hence, an adaptive algorithm Sub synchronous current induced to generator produces
based on sub harmonic measurement and ferroresonance torque on the turbine-generator shaft. Sub synchronous torque
analysis in time domain is proposed for this function. The may coincide with one of the natural frequencies of the rotary
algorithm recognizes occurrence of SSR along with system. It causes oscillation of the shaft at some natural
frequencies. Sub synchronous resonance can Cause
ferroresonance. In case of operation of the function, it either
catastrophic damage to the turbine-generator shaft. SSR is
decides to change the locus of characteristic or blocks trip
generally divided in to transient and steady state described as
operation of the element in OOS conditions. In addition, the
follow.
algorithm distinguishes protection of the generator against Transient SSR occurs due to occurrence of a short circuit in
sub harmonics, which are close to natural frequencies of the a system with series compensation. Transient magnitudes
rotor. Finally, the algorithm is examined in SSR conditions to include sub synchronous frequencies, which depend on
certify the correct operation. elements in the network. Slip frequency fr in generator is
given by (10) [23].
III. THEORETICAL APPROACH OF SSR IN TRANSMISSION LINE = 0− (10)
Theoretical aspect of SSR in AC transmission system is In case this frequency coincides with one of natural
explained in this section. frequencies of the turbine-generator rotor (fn), torque
amplitude is increased much larger with respect to the system
A. Series compensation and SSR phenomenon without compensation.
Loadability of AC transmission line is defined as follow
[20]. Steady state (Self-excitation) SSR is divided in to the
.
= (1) Induction Generator Effect (IGE) and Torsional Interaction
(TI). IGE considers generator as a rigid mass at constant
Series compensation increases capability of power
speed connected to the network. TI considers the turbine-
transmission by adding series capacitors, which decrease total
generator with multi-mass shaft, which interact with the
line impedance as follow.
system disturbances at its natural frequencies.
= − (2)
= (1 − ). (3) B. SSR analysis tool
S is the compensation degree, which is changed between 0 In order to analyze SSR several methods have been
and 100% defined as follow. proposed. Frequency scanning and eigenvalue analysis are
= × 100% (4) the most popular tools, which have been practical in this case.
The degree of compensation could be 100% theoretically. It Frequency scanning calculates impedance from behind of
may produce large currents in the presence of small stator winding of generator as a function of frequency.
disturbances or faults. On the other hand, a high level of
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
For dynamic stability studies, eigenvalue analysis is The polygon width Za also determines the maximum
performed by deriving the linearized model of ac system as detectable power swing slip frequency. Considering that even
follow [24]. with rapid power swings, at least two impedance values must
Ỳ= (11) have been established within the power swing polygon.
4
The elements of matrix Y depends upon the system = (17)
. .
quantities and operating conditions necessary to describe the
Occurrence of power swing in effect of SSR with specific
system and the matrix A is a n × n matrix. Eigenvalue of
slip frequency and different ratio of n=EA/EB causes
matrix A is calculated and then torsional frequencies are
operation of the function in corresponding protective zone.
obtained as follow.
| |.2
Out of step function has a decisive role to maintain stability
= (12) of the network during power swing. Hence, adaptation of
2
Where λi is calculated eigenvalue of matrix A characteristic to detect power swing in effect of SSR and
determination of behavior of the relay according to protection
IV. SUB SYNCHRONOUS RESONANCE IN ELECTRICAL strategy seems to be necessary.
PROTECTION
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
B. Ferroresonance detection based on time domain stiffness are entered to the algorithm. Typical values are
analysis given in the flowchart for a 480 MW hydro generator. Then,
The consequences of experiences and simulations of SSR natural frequencies (fn) of the rotor are determined by
phenomena certify occurrence of ferroresonance due to eigenvalue analysis. The algorithm receives pole slipping
increasing voltage magnitude and collision of capacitance setting values and grid quantities like; instantaneous values of
line with saturated area of transformer or reactor core. Hence, voltage, current, and frequency. Sub synchronous frequencies
in order to make a reliable detection of power swing in case in the current waveform of the network are detected in range
of SSR it is preferable to detect ferroresonance of different of 5-50 Hz by means of low pass filter. Then Fast Fourier
types which can be considered in setting modification of Transform (FFT) decomposes the signal in to number of sub
OOS characteristic. harmonics. It represents a replica of fer, which depends on the
In this section, proposed method in [29-30] is used to value and type of elements (R-L-C) in the network. Slip
determine ferroresonance of different types based on time frequency fr induced in the rotor is compared with natural
domain analysis. In order to design a detection tool based on frequencies of the rotor. It distinguishes fr which coincide
a logical circuit, ferroresonant characteristics must be with one of natural frequencies (fn) then alarm massage is
quantified. THD (Total Harmonic Distortion) and ∆f issued by the algorithm.
(frequency difference with respect to rated frequency) are the The algorithm calculates sub harmonic currents as criteria
quantities, which are used as criteria to determine to detect SSR in the network defined as follow [12].
ferroresonance of different types as shown in Table I. Current Sub Harmonic Nominal Ratio
TABLE I
CRITERIA TO DETERMINE FERRORESONANCE MODE ( )= × 100 (18)
Ferroresonance ∆f d∆f T.H.D (%) Harmonic Current Sub Harmonic Fundamental Ratio
type dt spectrum
Fundamental zero Zero > 50 Discrete
Harmonic constant Zero > 50 Discrete ( )= × 100 (19)
Quasi-periodic variable Not zero > 100 Discrete
Chaotic variable Not zero > 100 Continuous Current Total Sub Harmonic Distortion
2 2 2
(5 ) + (6 ) +⋯+ (50 )
Fundamental ferroresonance is detected when frequency of ( )= × 100 (20)
(60 )
waveform remains at nominal value (∆f is zero) and the value
of THD is more than 50%. Harmonic ferroresonance is Setting values of the above criteria depends on required
detected when frequency of waveform is deviated from sensitivity to detect SSR. It also can be determined by
nominal value and remains constant (∆f is not zero); protection scheme. If the value of one of the above criteria
furthermore, the value of THD is also more than 50%. In exceeds setting value and remains stable more than 100 ms or
most cases, fundamental and harmonic ferroresonance more than 10 Operation Per Second (OP/S), SSR is
contain odd harmonics; hence, harmonic spectrum is discrete. considered in the network. OP/S registers successive pickup
Quasi-periodic and chaotic modes are determined when values, which are dropped off in the time below 100 ms. The
∆
is detected. criteria explained in section IV. B, to determine
ferroresonance of different types is used in the algorithm.
In addition, the value of THD increases more than 100%
where chaotic mode contains a continuous harmonic In case of occurrence of power swing due to SSR and
spectrum. As harmonic spectrum is mostly a qualified ferroresonance conditions impedance varies in the network.
characteristic, THD and ∆f are only used in logical circuit to In unstable power swing condition, impedance trajectory may
determine ferroresonance modes. traverse across out of step characteristic of generator
protection. The algorithm designated for OOS characteristic
C. SSR detection algorithm in generator Out Of Step decides to determine behavior of the function in such
protection conditions according to protection strategy. Protection
In this section, an algorithm based on eigenvalue analysis, strategy is also determined based on results of the stability
sub harmonic measurement and analysis of ferroresonance in analysis in the network. In such conditions, the algorithm is
time domain is proposed to control operation of out of step subject to delay after passing impedance trajectory through
protection of generator during SSR. In addition, the algorithm trip angle at the first sleep. In this time, it determines
distinguishes protection of turbine-generator against sub behavior of the characteristic according to protection strategy.
harmonics, which may coincide with natural frequencies of As shown in the flowchart, it is able to recalculate new
the rotor. setting parameters to change dimension of OOS
Fig. 3 shows an example of flowchart of the proposed SSR characteristic. In addition, it determines number of slips in
detection algorithm, which is used in generator protection. In each zone and considers a time delay in trip operation.
order to detect torsional oscillation of generator, mechanical Changing dimension of the characteristic is accomplished
parameters of each section of the rotor like inertia and shaft by calculation of center and radius of the impedance circle as
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
shown in Fig. 3. For instance, in case of passing impedance rest of values of n, which may pass through transformer or
locus through generator with a value of n<1 in impedance transmission line. Hence, the value of Zm must be
diagram the condition is provided for operation of zone1. It is recalculated so zone1 of OOS characteristic can be situated
assumed that protection strategy requires the OOS function out of the impedance locus.
does not operate in power swing with such value of n due to
SSR. On the other hand, the function is required to operate in
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
characteristic out of the circle. form the characteristic, can be modified according to
= −( − ) . (21) situation of impedance circle and discretion of protection
Where C is distance between center of circle and point A strategy. If OOS, ferroresonance and SSR are not detected
Security Factor (SF), is applied to increase stability margin. setting values of the relay are returned to initial values. In
On the contrary, in n>1 state, if the radius (R) of impedance addition to that, in case of increasing the current higher than
circle is greater than the distance between center of circle and Imax the condition of I > Imax is added to retrieve initial setting
point A (C) Zs and ZTr are recalculated by the following values.
formula to locate the characteristic out of the circle. It is clearly identified that, the values of measured sub
+ = ( + )−( − ) . (22) harmonics, ferroresonance of different type detection, in
addition; increasing voltage and current during SSR and
ferroresonance depends on varies conditions. These
conditions includes the values of R-L-C elements, switching
and line and plant outage, which results in changing network
configuration. Furthermore, the status of generator excitation
system (under-over) is crucial to determination of system
impedance situation. Hence, in order to provide an intelligent
protection which adapt the status of the system with
protection requirements automatically, on line monitoring of
the system is required by the algorithm.
A3R A3R
ASROS
A A A A
250 [uF] V V 83 [uF] V V
G1AG... n1_right
C-ASDOR 0.00005 [uF] A3RA4D1 A3RA4D2
G2A ASDOR
A A
REMOTE
ASDORVC2
TABLE II
VALUES OF INERTIA, STIFFNESS AND NATURAL FREQUENCIES OF 480 MW
Table II shows rotor mechanical specifications like inertia HYDRO GENERATOR
and time constant of hydro generator in Grand Rapids station
Inertia Value (s) Stiffness Value Fn (Hz) Mode
[16]. Furthermore, in [31] an example of simulation of a (pu. T/rad)
hydro generator with torsional shaft model is implemented by JT1 0.0830 KT1-2 18.0858 51.94 5
the values of rotor inertia and time constant nearly the same JT2 0.1451 KT2-3 33.1075 43.15 4
as the information given in [16]. JT3 0.7864 KT3-4 51.3650 33.31 3
JT4 0.7945 KT4-Gen 68.0483 0.00 0
JGen 0.7859 KGen-Exc 2.117 20.86 1
JExc 0.0284 24.97 2
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
grid par.
Rotor shaft comprises a 4-section turbine, generator and
Voltage
exciter. Electrical resonance frequency (fer) generated by the 1.3M
1.0M 0.1035M
elements of the network due to a short circuit produces a sub 0.8M
0.5M
-0.2378M
-0.3413M
synchronous frequency in generator in Grand Rapids station. 0.3M
Min -0.8820M
(V)
0.0
It may coincide with one of natural frequencies of hydro -0.3M
-0.5M
Max 1.0119M
1.0k -0.5197k
0 Min -2.7163k
(A)
0.0
-1 -1.0k Max 3.6240k
T1 T2 T3 T4 Gen Exc
1 -2.0k
mod 4
-3.0k
0
t (s) 1.100 1.150 1.200 1.250 1.300 1.350 1.400 1.450 1.500 1.550 1.073
-1 1.531
T1 T2 T3 T4 Gen Exc
0.458
1
mod 3
0
(b)
-1
Fig. 7. Grid parameters in short circuit. (a) Non-compensation, (b) Series
T1 T2 T3 T4 Gen Exc compensation.
2
mod 0
1
Fig. 8 shows frequency spectrum of stator current of hydro
0 generator. It consists of sub frequency 27 Hz with amplitude
T1 T2 T3 T4 Gen Exc
1
of about 50% with respect to fundamental. This is fer which is
mod 1
0
with one of natural frequencies (Fig.6, mode 3) of rotor shaft
-1
T1 T2 T3 T4 Gen Exc in Grand Rapids station.
Fig. 6. Torsional modes of Hydro generator in Grand Rapids station. 4 Sub harmonic of current in Hydro generator
x 10
-1.0k
Max 1.7104k shows electrical parameters of hydro generator. Oscillation of
-2.0k
active power causes torsional strength to hydro generator
-3.0k
t (s) 1.100 1.150 1.200 1.250 1.300 1.350 1.400 1.450 1.500 1.550 1.073 shaft. Direction of magnitude of torque on the shaft between
1.531
0.458 section 1 and 2 of turbine, in addition mechanical
(a) displacement of section 1 with respect to generator change
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
-5.0k
magnitude of voltage and current; in addition, oscillation of
Max 13.7917k
-10.0k power in the network as described below.
-15.0k Overcurrent relay measures rms value of fundamental to
80.00k
IMA protect generator and transformer in Grand Rapids station.
28.4412k
60.00k
49.7636k
Fig. 10a shows the secondary value of current measured by
40.00k
20.00k 21.3224k the relay during short circuit in 230 kV side in Silver station
0.00 Min -70.4337k where series capacitors are out of service. The straight red
(A)
-20.00k
Max 70.5721k
-40.00k line indicates relay setting value. The relay does not operate
-60.00k
-80.00k because the measured current is below pickup setting of the
1.0k
Active Power relay. In series compensation (Fig. 10b), current increases up
0.8k 0.4933k
0.6k 0.6458k
to pick up value of the relay. As the current amplitude has
0.4k
0.2k
0.1525k increasing manner, trip condition of the relay is fulfilled after
(MW)
20 24.076 0.40
(Degree)
Max 1.015
10 Min -19.887 0.20
0 Max 30.628 0.00
0.60
-2.0 Max 6.093 0.40 Max 1.253
-4.0 0.20
-6.0 0.00
Mech. position mass 1 wrt gen Pick up 0: Low
60
-22.084
-0.439 Trip 0: Low
21.645
(Degree)
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
ohm. Impedance locus enters in to zones 1 and 2 and hydro generator. Similarly, the diagram comprises reactance
remains stable in zone 1 so that trip signal is issued. On (X) and resistance (R) axis based on ohm. Referring to Fig. 2,
the other hand, the impedance locus passes only through OOS characteristic comprises warn and trip angle in the right
OSB elements; hence, OSB signal is issued so that and left side of the polygon. Impedance circles pass through
operation of the relay can be blocked in case of short warn angle, which alert out of step condition. Trip signal is
circuit fault
R5 OSBalong with occurrence
X5 OSBof SSR in the network. issued when the impedance locus passes through trip angle in
R6 OSB X6 OSB an unstable out of step condition after specified number of
SILVERPROTECTION_1 : LINE IMPEDANCE
RZ2 XZ2
RZ1
X Coordinate XZ1
Y Coordinate
slips. Diameter and location of the impedance circles depends
Rab Xab on the ratio of n = . Fig. 12b, shows the calculated ratio
Rbc Xbc
Rca Xca of n between Grand Rapids and the network. The values of n
R5m OSB X5m OSB
+y decrease and are often smaller than 1 in the time after 6.5 s;
400 R6m OSB X6m OSB
RZ2m XZ2m
hence, hydro generator is mostly under excited during SSR.
GRANDRAPIDSPROTECTION : XY Plot
300
R6 OSB X6 OSB
X Coordinate
R5 OSB Y Coordinate
X5 OSB
200
Rab (ohm) Xab (ohm)
Rbc (ohm) Xbc (ohm)
100
Rca (ohm) Xca (ohm)
-x +x 200 RZ2 +yXZ2
0
RZ1 XZ1
-100 POLI1X POLI1Y
150 POLI3X POLI3Y
-200 POLI2Y POLI2X
POLI4Y POLI4X
-300 100 POLI5X POLI5Y
-400
-y 50
-300 -200 -100 0 100 200 300
Aperture Width 11.709... -x +x
0
0.000s 15.000s Position 3.290
(a) -50
SILVERPROTECTION_1 : Graphs
OSB -100
-y
-150
-200 -100 0 100 200 300
Z1 Pickup Aperture Width 11.197183...
0.000s 15.000s Position 0.000
(a)
GRAND RAPIDS PROTECTION
Z1Trip n=EGen/EGrid
1.20
1.10 1.058
1.00 0.934
0.90 -0.124
0.80
0.70 Min 0.467
Z2 Pickup 0.60 Max 1.091
0.50
0.40
t (s) 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 5.0
9.4
Z2Trip 4.4
(b)
Fig. 12. Pole slipping relay. (a) Protective zone and impedance loci, (b) Ratio
x
of n and number of slips during SSR.
0.0 2.5 5.0 7.5 10.0 12.5 15.0
D. Differential relay
(b) Transformers in Silver station are protected by differential
Fig. 11. Distance relay with OSB element. (a) Protective zones and
impedance loci, (b) Operation of the relay.
protection. The relay has been examined in fault conditions;
hence, reliability of the protection has been certified. The
C. Out of step protection relay is re-examined in fault conditions where series
capacitors are in service. As was mentioned in advance, an
As was discussed in advance, out of step protection function external three phase fault occurs in 230 kV side of
protects generator and transformer against power swing transformer in Silver station. Fig. 13a shows the values of
condition, which cause mechanical and thermal damages. As Idiff (differential current) and Ibias (biasing current) with
was shown in section V, hydro generator in Grand Rapids respect to the time. The relay goes to mal operation
station is exposed to out of step condition during SSR. Fig. successively due to switch off transient state [30] after fault
12a shows polygon characteristic of out of step protection of elimination and drops off after 1 s. At the time of 6.5 s, along
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
with increasing slip frequency (Fig. 9a) Idiff is increased and A. Explanation of the algorithm
the relay picks up again so that successive operation of The adaptive algorithm in OOS protection comprises rotor
protection is obtained for a period of about 2s. Fig. 13b natural frequency calculation, SSR, out of step and
shows two-slope characteristic of differential protection and ferroresonance detection; in addition, OOS setting
current loci based on Idiff indicated on y axis and Ibias modification. The algorithm is implemented by
indicated on x axis. Due to external fault in series PSCAD/EMTDC software explained as follow.
compensation, Idiff increases up to 200% with respect to In order to determine natural frequencies (fn) of hydro
Ibias in both above-mentioned states. generator and detection of generator oscillation, Matlab
SILVERPROTECTION_1,Differential : Graphs
IDiffL1
interface is used in PSCAD. The values of inertia constant
3.00
0.222 and stiffness of the shaft are defined to calculate eigenvalues
2.50 0.213
2.00 -0.009
by the algorithm. Electrical resonance frequency (fer) of the
1.50 Min 0.000 network is measured from the current which pass through a
(A)
Max 2.610
1.00 low pass filter. Sub synchronous harmonics with the values
0.50
higher than 30% are evaluated to find slip frequency (fr)
0.00
IBiasL1
induced in the generator shaft. If fr coincides with one of the
1.40
1.20
0.111 natural frequencies of the shaft an alarm message is generated
0.107
1.00 -0.005
to operate desired action (shut down or trip the generator)
0.80 Min 0.000 according to protection strategy. The values of ISHNR,
(A)
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
Amplitude %
They are increased up to 65%, 52%, and 325% respectively
200
for duration more than 100 ms. Threshold values for these
parameters are determined by protection scheme. In this
example, the values are high enough to consider as SSR 150 ISHNR = 65%
condition in the specified time. As was shown in Fig. 7b,
ISHFR = 52%
increasing the magnitude of voltage up to 1 MV causes 100
saturation of transformer core. Capacitance line of the system
traverses across nonlinear area of saturated curve of 50
transformer and results in occurrence of ferroresonance.
Fig. 14b shows the measured ferroresonance detection
0
quantities, which are listed in table I. the value of ∆f is ISHNR ISHFR ISTHD
increased up to 5 Hz then suppressed gradually. Follow (a)
SILVERPROTECTION_1 : Graphs
variation of ∆f, d∆f/dt is also increased up to 18 Hz/S
deltaf
showing frequency changes with respect to the time. The 6.0
0.072
value of THD is increased up to 3000 % in short time and 5.0 0.003
suppressed to a value of 70 % in sustained state. According 4.0 -0.069
to threshold values of criteria to detect ferroresonance of Min 0.002
3.0
(HZ)
Max 5.122
different types in table I, fundamental ferroresonance is 2.0
detected in fault inception time. Then all types of
1.0
ferroresonance are detected after fault elimination for
0.0
duration of about 0.5 s, whereas fundamental type is still
ddeltaf/dt
detected after this time. Protection strategy is responsible to 20.0
0.000
17.5
select the ferroresonance type in which setting modification is 0.000
15.0
implemented. 12.5
0.000
Min 0.000
SSR and ferroresonance are detected in the time of fault
(HZ/S)
10.0
Max 18.951
inception. However, impedance loci traverse across OOS 7.5
characteristic of generator protection in Grand Rapids station 5.0
in effect of power oscillation in the time of 5 s after short 2.5
0.0
circuit in Silver station. As was shown in Fig. 12b the value THDmax
of n = EGen/EGrid < 1 is mostly eminent hence, impedance 3.5k
0.0367k
circle passes through zone1 of the characteristic. 3.0k 0.1582k
Fig. 14c shows modified polygon characteristic which was 2.5k 0.1215k
2.0k Min 0.0005k
illustrated in Fig. 12a. It is shown that impedance loci
(%)
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
R6 OSB
GRANDRAPIDSPROTECTION : XY Plot
X6 OSB
synchronous resonance in series compensated systems'', Proceedings
R5 OSB
X Coordinate X5 OSB
Y Coordinate
of the IEEE Int. Conf. on Power Electronics and Drive Systems,
Rab (ohm) Xab (ohm) 1999. PEDS '99, Vol. 2, pp. 683 – 687.
Rbc (ohm) Xbc (ohm) [5] N. Yousif; M. Al-Dabbagh, ''Time-frequency distribution application
Rca (ohm) Xca (ohm) for sub-synchronous resonance analysis in power systems'',
RZ2 XZ2 International Power Engineering Conference, 2005, Vol. 2, pp.771 -
150 +y
RZ1 XZ1
775
POLI1X POLI1Y
POLI3X POLI3Y
[6] H. A. Mohammad pour; E. Santi, ''Sub-synchronous resonance
POLI2Y POLI2X analysis in DFIG-based wind farms: Definitions and problem
100 identification — Part I'', IEEE Energy Conversion Congress and
POLI4Y POLI4X
POLI5X POLI5Y Exposition (ECCE), 2014, pp. 812 – 819.
[7] H. A. Mohammad pour; E. Santi, ''Optimal adaptive sub-
50
synchronous resonance damping controller for a series-compensated
doubly-fed induction generator-based wind farm'', IET Renewable
Power Generation'', 2015, Vol. 9, Issue: 6, pp. 669 – 681.
[8] R. Gagnon, P. Viarouge, G. Sybille, E Tourkhani "Identification of
-x +x Ferroresonance as the Cause of SVC Instability in a Degraded Series
0
Compensated Network" IEEE Power Engineering Society Winter
Meeting 2000, vol.2, pp. 1377 - 1382
[9] D.A. Woodford "Solving the Ferroresonance Problem when
-50 Compensating a Dc Converter Station with a Series Capacitor",
IEEE Transactions on Power Systems, Vol. 11, No. 3, August 1996
[10] G. Zweigle; D. Finney; R. Moxley, ''Adding shaft angle
-y
measurement to generator protection and monitoring'', 66th Annual
-100
-200 -150 -100 -50 0 50 100 150 200 Conference for Protective Relay Engineers, A&M uni. Texas, 2013,
Aperture Width 0.7042253... pp. 549 – 556.
0.000s 15.000s Position 11.275
[11] M. Hedayati, '' Design Of Sub synchronous Resonance Protection
And Reduction Of Torsional Interaction In Power Systems'',
(c) Proceedings of the 6th WSEAS International Conference on Power
Fig. 14. Examination of SSR detection algorithm in OOS characteristic. (a) Systems, Lisbon, Portugal, September 22-24, 2006, pp. 54-58.
SSR detection, (b) ferroresonance detection, (c) modification of Zm setting. [12] M. Peterson, R. Midence, J. Perez, "Application of sub harmonic
protection relay" 11th International Conference on DPSP 2012.
VIII. CONCLUSIONS Birmingham, UK, pp. 1-6
[13] N. Perera, K. Narendra, D. Fedirchuk, R. Midence, V. Sood
Series compensation increases Loadability of transmission "Performance evaluation of sub harmonic protection relay using
line. However, it may lead in sub synchronous resonance in practical waveforms" IEEE, EPEC conf.2012, pp51-56.
the network. It causes power oscillation, occurrence of [14] S. Rezaei, "Behavior of protective relays during Sub Synchronous
Resonance', 17th IEEE International Conference on Environment
ferroresonance, increasing voltage and current and and Electrical Engineering, 2017, & 1th IEEE Industrial and
consequently mal operation of protective relays. As Commercial Power Systems Europe (EEEIC / I&CPS Europe),
accidentally line and plant outage may exacerbate the system Year: 2017, pp. 1 – 5
condition, mal operation of protective relays may not be [15] S. Rezaei, "Impact of Sub Synchronous Resonance on operation of
protective relays and prevention method", IEEE/IAS 53rd Industrial
permissible in such conditions according to protection and Commercial Power Systems Technical Conference (I&CPS),
strategy. Out of step protection of the generator is affected 2017, Niagara Falls. ON. Canada. pp. 1-9.
due to SSR. An adaptive algorithm based on sub harmonic [16] S. Rezaei, "An adaptive algorithm based on sub harmonic and time
and time domain analysis of ferroresonance is designed to domain analysis to prevent mal operation of overcurrent relay during
Sub Synchronous Resonance', IEEE transactions on industrial and
manage operation of OOS protection function according to application society, Year: 2018, early access article.
protection strategy. It increases stability and availability of [17] A. A. Maksoud Shaltout, "Sub synchronous Resonance in Large
the generation unit and electrical network. In addition to that, Turbo-Generators Connected to Series Capacitor Compensated
distance relay with OSB element is subjected to such mal Power Systems" Ph.D. dissertation, University of Saskatchewan,
Saskatchewan, Canada, 1981.
operations during SSR. Hence, designation of an adaptive [18] J. Bladh, '' Hydropower generator and power system interaction'',
algorithm for distance relay will be presented as a future Digital Comprehensive Summaries of Uppsala Dissertations from
work. the Faculty of Science and Technology, Uppsala University, 2012.
[19] EMTP works version 2.0.2, examples, 'Ferro-Demo', Data case
given by D.A.N Jacobson
REFERENCES [20] H. Dag, B. Ozturk, A. Ozyurek, "application of series and shunt
[1] J.W. Ballance, S. Goldberg, "Sub synchronous Resonance in Series compensation to Turkish national power transmission system to
Compensated Transmission Lines", IEEE Trans, on Power improve system loadability", ELECO.99, international conference
Apparatus and systems, Vol PAS-92. Sept/Oct.1973. pp.1649-1658. on electrical and electronic engineering, pp. 243-247.
[2] M. Varghese; F. F. Wu; P. Varaiya, ''Bifurcations associated with [21] G. Naresh Babu, V. Sudhagar "Damping of Subsynchronous
sub-synchronous resonance'', IEEE Transactions on Power Systems, Resonance in an Series Compensated System using PSCAD"
1998, Vol.: 13, Issue: 1, pp. 139 – 144. IJAREEIE, Vol. 3, Special Issue 1, February 2014, pp. 103-107.
[3] S. Gupta; A. Moharana; R. K. Varma, ''Frequency scanning study of [22] P. M Anderson, B. L Agrawal, J. E Van ness "Sub synchronous
sub-synchronous resonance in power systems'', 26th IEEE Canadian Resonance in Power systems", IEEE PES book, 1926, pp. 9.
Conference on Electrical and Computer Engineering (CCECE), [23] Andres E. Leon, Jorge A. Solsona "Sub Synchronous Interaction
2013, pp. 1 – 6. Damping Control for DFIG Wind Turbines" IEEE transactions on
[4] B. S. Nagabhushana; Chandrasekharaiah; L. L. Lai; D. Vujatovic, power system, Year: 2015, Volume: 30, Issue: 1, pp. 419 – 428
''Neural network approach to identification and control of sub-
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2019.2936388, IEEE
Transactions on Industry Applications
0093-9994 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.