Professional Documents
Culture Documents
Data
IEC Curve Selected Units
Entry
Ip Setting 0.20 Amps
Tp Setting 0.15 sec
Injected Current 1.3 1 times
Choose the Curve Normal Inverse
1
Current to be Injected 0.26 Amps
Calculated Tripping Time for 1.3 times
3.992 Secs
Current
Data
IEC Curve Selected Units
Entry
IEp Setting 1.00 Amps
TEp Setting 1.00 sec
Injected Current 5 3 times
Choose the Curve Normal Inverse
1
Current to be Injected 5 Amps