You are on page 1of 15

Electrical Engineering

https://doi.org/10.1007/s00202-019-00841-6

ORIGINAL PAPER

A protection strategy for inverter-interfaced islanded microgrids


with looped configuration
Hamed Karimi1 · Ghazanfar Shahgholian1 · Bahador Fani1 · Iman Sadeghkhani1 · Majid Moazzami1

Received: 17 November 2018 / Accepted: 24 September 2019


© Springer-Verlag GmbH Germany, part of Springer Nature 2019

Abstract
Development of an efficient protection strategy is one of the main barriers in paving the way for the implementation of
inverter-based microgrids. The limited fault current of voltage-sourced converter (VSC) units as the sole fault feeding sources
in the islanded mode of operation makes the fault detection difficult for conventional overcurrent-based protection system. On
the other hand, bidirectional power flow due to the presence of distributed energy resource units and looped configuration of
microgrids results in miscoordination of the overcurrent relays. To address these problems, this paper proposes a protection
strategy for islanded inverter-interfaced looped microgrids. By monitoring the fault-imposed component of VSC current,
the proposed scheme quantifies the severity of fault condition as the fault detection criterion. To preserve the protection
coordination among available overcurrent relays, the proposed protection scheme adaptively changes the limiting level of
hybrid reference frame limiter of the VSC control system proportional to their distances to the fault point. The proposed
protection scheme is local, and there is no need for any change in the commercially available overcurrent protection relays.
The reliable performance of the proposed protection strategy is assessed on the simulation model of a looped microgrid
network.

Keywords Distributed energy resource (DER) · Fault detection · Looped microgrid · Overcurrent relay · Protection
coordination · Voltage-sourced converter (VSC)

List of symbols k Sampling step


CB Circuit breaker N Number of samples within a moving window
CLF Current limiting factor OCR Overcurrent relay
DER Distributed energy resource OSI Overall severity index
FDI Fault detection index Sbase Nominal power of DER
HRFL Hybrid reference frame limiting Td Time delay of Delta filter
I Relay current Ts Sampling time
IPS Plug setting current t Operating time of relay
pu
ILref RMS value of inductor current reference UF Amplitude of fault component of DER output volt-
i Lref Inductor current reference age
pu
iL  ref
Limited inductor current reference UN Amplitude of normal-running component of DER
io Output current output voltage
pu Vbase Nominal voltage of DER
i o,F Fault component of output current
pu
i o,FI Fault-imposed component of output current vo Output voltage
pu voref Output voltage reference
i o,N Normal-running component of output current
VSC Voltage-sourced converter
i th Current threshold
ξ Fault detection threshold
B Ghazanfar Shahgholian
shahgholian@iaun.ac.ir
1 Department of Electrical Engineering, Najafabad Branch,
Islamic Azad University, Najafabad 85141-43131, Iran

123
Electrical Engineering

1 Introduction distribution network leads to bidirectional power flow. This


issue that is more severe in the looped configuration degrades
The need for paving a way to increase energy security and to the performance of the conventional protection system that
decrease the environmental concerns leads to great attention is designed for radial networks.
to distributed energy resource (DER) units [1–3]. Deple- Up to now, various protection techniques have been pro-
tion of fossil fuels, the increment of greenhouse gas, and posed that can be broadly classified into eight groups: (i)
competitive electricity market result in significant research adaptive protection, (ii) differential protection, (iii) voltage-
on renewable DERs. Since the output power of these units based protection, (iv) symmetrical components-based pro-
is DC or uncontrolled AC, they are interfaced to the host tection, (v) external device-based protection, (vi) distance
network through a power-electronic interface converter com- protection, (vii) DER power management, and (viii) non-
monly acting as a voltage-sourced converter (VSC) [4]. To conventional protection. Figure 1 shows the different meth-
coordinately control of DER units and to increase the relia- ods of these groups.
bility, the microgrid concept has emerged as a set of DERs
and loads [5,6]. A microgrid can operate in both islanded Group I automatically updates the protection system set-
and grid-connected modes of operation. In the former oper- tings. In [10], an adaptive protection scheme is proposed
ating mode, VSC controls the voltage and frequency of the that uses the fault component of current. An adaptive
microgrid while it manages the injected real and reactive overcurrent protection scheme for distribution systems
power of DERs in the latter operating mode [7]. On the other is proposed in [11]. The need for communication infras-
hand, with the development of control and protection algo- tructure and updating the settings during each change in
rithms, the microgrid configuration can be both radial and the microgrid are the main disadvantages of the adaptive
looped/mesh. Flexibility and reliability are the main factors protection schemes.
for adopting the microgrid configuration. Due to existence Group II detects the fault by measuring the differential
of several paths for delivering electric power to the loads, quantities which the main ones are differential cur-
the looped configuration is a proper choice to enhance these rent [12] and differential energy [13,14]. The latter is
features [8]. less sensitive to synchronization error among measure-
One of the main challenges of the microgrid is an effi- ments. Ref. [15] proposes a protection scheme based on
cient protection system that is able to detect and isolate the differential impedance. Ref. [16] shows that differential
faulty section with acceptable speed. The origins of these protection based on the symmetrical components of cur-
challenges are the low fault current and bidirectional cur- rent presents best performance over the differential RMS,
rent flow of inverter- interfaced islanded microgrids. In the power factor angles, symmetrical components of voltage,
absence of the utility grid, the fault current only flows from and total harmonic distortion (THD). Similar to the pre-
the DER units. Due to the low thermal inertia of VSCs, the vious group, the differential protection suffers from the
fault current contribution of inverter- interfaced DERs is typ- need for the communication link that increases the cost
ically limited to 2–3 times the nominal current [9]. The low and reduces the reliability of the protection scheme.
fault current of these microgrids may be insufficient to trigger Group III is based on the voltage measurements. The
the conventional overcurrent relay or increases its operating fault condition is detected using the voltage drop [17–20]
time. On the other hand, the integration of DER units into and voltage THD measurements [21]. In [22], the fault

Fig. 1 Microgrid protection techniques in different groups

123
Electrical Engineering

detection is performed by transferring the voltage signals support vector machines for fault detection and location.
to dq axes and comparing them with the reference volt- In [38], a bi-level multi-agent system-based protection
age. The possibility of mal-operation for voltage drops scheme is proposed to preserve the protection coordi-
caused by the no fault conditions such as a load switch- nation in the presence of DER units. The methods of
ing and no distortion of voltage waveform in the case of this group suffer from the high computational burden and
using enhanced current limiting schemes in VSC control need for training data.
system are the main barriers affecting the development
of this group.
This paper proposes a protection strategy for islanded
Group IV is based on the using symmetrical compo-
microgrids with the looped configuration. The proposed
nents. In [23], the grounding fault and double line fault
scheme relies on the control system and output signals of
types are detected using the zero-sequence and negative-
VSCs and does not impose the extra cost. By monitoring the
sequence components of current, respectively. Inability
VSC current in a moving data window, the fault condition
in detecting three-phase faults and mal-operation due to
is detected by measuring the overall severity of a change
inherent unbalanced nature of the distribution network
in the VSC current to address the low fault detection sen-
are the main disadvantages of this method. Ref. [24]
sitivity of overcurrent relays. To identify the faulty feeder
proposes a faulty feeder location method based on mod-
and to preserve the protection coordination among the avail-
ifying the directional protection based on the phase
able conventional overcurrent relays in the presence of DERs
differences between the positive-sequence fault-imposed
in the looped microgrid, a DER power management-based
components of bus voltage and feeder current.
method (Group VII) is proposed. In this scheme, the injected
Group V employs the external devices to equalize the
fault current of VSCs is changed in such a way that the cur-
fault current level in both grid-connected and islanded
rent flowing through those relays which are closer to the fault
modes of operation for employing the same protection
point will be greater than other relays. To this end, the current
system. Either using the storage devices such as the bat-
limiting level of the hybrid reference frame limiting (HRFL)
tery, supercapacitors, and flywheel, the fault current level
scheme is adaptively changed based on the fault location.
in the islanded mode of operation increases [25–27] or
The main features of the proposed protection strategy are as
using the fault current limiters, the fault current contri-
follows.
bution of the main grid decreases. However, the need for
an accurate algorithm to detect islanding condition and
high cost are the main disadvantages of this group. • It is effective for inverter-interfaced looped microgrids
Group VI proposes to use the distance relays in dis- with limited fault current and bidirectional fault current
tribution networks and to define the protection zones flow.
based on DER location [28]. The impedance differential • It detects the fault condition with proper sensitivity by
and inverse-time low-impedance schemes are proposed monitoring the available measurement of VSC current;
in [16]. In [29], the possibility of employing distance • It is implemented in VSC control system and does not
protection in grid-connected and islanded microgrids is require additional device; and
investigated. Pilot-based distance protection is proposed • It does not require the communication link and can be
in [30] for meshed distribution networks in the presence implemented in microgrids with commercially available
of DER units. However, the effect of fault resistance overcurrent relays.
on the calculated impedance by the relays especially in
distribution networks where the lines are short and the The rest of the paper is organized as follows. Section 2
possibility of high-impedance fault occurrence is high describes the study microgrid and VSC control system.
and need for communication in the pilot-based scheme The main protection challenges of islanded VSC-interfaced
are the main disadvantages of this group. looped microgrids are presented in Sect. 3. Section 4 is
Group VII is based on management of generated power dedicated to the proposed fault detection and protection coor-
of DER unit during fault condition. References [31,32] dination schemes. The simulation results are carried out in
propose to disconnect DERs during the fault condition, Sect. 5 to verify the effectiveness of the proposed protection
but they are not applicable for islanded mode of operation strategy. Finally, the paper is concluded in Sect. 6.
where DER units are the sole power supplies. Also, con-
trol of output current of DGs during the fault condition
is proposed in [33,34]. 2 Looped microgrid test model
Group VIII consists of non-conventional protection
schemes [35]. The protection strategy proposed in [36] is Figure 2 shows the single-line diagram of the four-wire
based on the type-2 fuzzy logic. Reference [37] uses two study microgrid [39]. Using the looped configuration, four

123
Electrical Engineering

Fig. 2 Study looped microgrid

Table 1 Study microgrid


Parameter DER1 DER2 DER3 DER4
parameters
Nominal power (kW) 10 3 12 15
Nominal line-to-line voltage (V) 400 400 400 400
DC bus voltage (V) 800 800 800 800
Fundamental frequency (Hz) 50 50 50 50
Switching frequency (kHz) 5 5 5 5
Filter inductance (mH) 2 0.6 2.4 3
Filter capacitance (μF) 15 50 12.5 10
Real power droop coefficient 2 × 10−4 6.67 × 10−4 1.66 × 10−4 1.33 × 10−4
Reactive power droop coefficient 3.25 × 10−3 10.83 × 10−3 2.7 × 10−3 2.16 × 10−3

electronically interfaced DER (EC-DER) units with various A


t= P + B, (1)
ratings supply three loads in the islanded mode of operation. I
−1
IPS
The real powers of loads 1–3 are 13.5, 4.5, and 17.5 kW while
their reactive powers are 6.5, 2.55, and 0.8 kVAr, respec-
where t is the operating time of the relay. I is the relay
tively. The cable resistance and inductance are 1.268 /km
current and IPS is its plug setting current. A, B, and P are
and 0.422 /km; the length of lines 1–6 are 300, 100, 100,
constant parameters that determine the shape of the charac-
100, 200, 50 m, respectively. The parameters of the DER
teristic curve. In this paper, the adopted characteristic curve
units are presented in Table 1.
of the OCR relays is the extremely inverse type.

2.2 DER control system

2.1 Protection system structure Due to flexibility in the production of high-quality power,
the VSC units have gained great attention among industries
Distribution networks are commonly protected using the as the DER interfaces [41]. In the islanded mode of opera-
overcurrent relays (OCRs). If the feeder current is within the tion, the VSC works in the voltage control mode to regulate
operating region of the relay, the OCR commands to open its the frequency and amplitude of microgrid voltage. Figure 3
associated circuit breaker (CB) after a time delay based on shows the typical control structure of the VSC control sys-
the time-current characteristic curve of the relay. In accor- tem. This system consists of an outer power control loop
dance with the IEC 60255 [40], the characteristic curve of an and the inner voltage and current control loops. The former
OCR relay is expressed as produces the frequency and amplitude of voltage reference

123
Electrical Engineering

Fig. 3 Structure of VSC control


system

i  L, j = CLF j × i L,
ref
voref for inner control loops. The frequency-real power and ref
j ; j = a, b, c, (2)
voltage-reactive power droop characteristics are commonly
used for this purpose [42]. The voltage control loop regulates where
the VSC output voltage vo by producing the inductor current
reference i Lref for the current control loop. Finally, the cur- ⎧

⎨ √ th
i
, IL,
ref > √i th
rent controller produces the reference signal for generating j
CLF j = 2 × IL, j
ref 2 ; j = a, b, c, (3)
the VSC switching signals. To enhance the power sharing ⎪
⎩1,
accuracy and dynamic behavior of the system, the virtual otherwise
impedance control loop is added to the VSC control system
that reduces the voltage reference proportional to the output i  ref ref
L, j is the limited inductor current reference and IL is the
current i o . ref
RMS value of i L . In the cases of using synchronous and
stationary reference frames, an auxiliary controller imple-
mented in natural reference frame works instead of the main
2.3 VSC current limiting VSC control system during an overcurrent condition. Since
no crest clipping occurs and the voltage control loop remains
Due to the low thermal inertia of VSC, its filter inductor closed in all phases, HRFL strategy presents high-quality
current should be limited to prevent damage of semiconduc- waveforms without the occurrence of any overvoltage.
tor switches. High cost and low reliability of the external
device-based limiters have increased the popularity of the
VSC control system-based limiters. These limiters usually 3 Protection challenges of
limit the inductor current reference of VSC using the cur- inverter-interfaced islanded microgrids
rent limiter block of Fig. 3. Three of most common control
system-based current limiters are instantaneous saturation, The conventional OCR-based protection system is designed
latched, and HRFL strategies [9]. Through the crest clip- based on the radial power flow and no presence of load-
ping, the instantaneous saturation limiting strategy prevents side generation units; the protection system operates based
i Lref from increasing beyond the current threshold or maxi- on the amplitude of feeder current and OCRs are coordinated
mum allowable peak current i th . However, poor quality of based on unidirectional power flow. However, there are many
voltage and current waveforms and low accuracy in current differences between a microgrid and the distribution network.
limiting are the main disadvantages of this limiter. The oper- High penetration of DER units, bidirectional power flow, and
ating principle of the latched limiting strategy is to replace the possibility of operation in islanded mode are the main
the i Lref with a pre-defined inductor current reference during ones. Due to the limited current of EC-DER units, their effect
overcurrent conditions. However, the occurrence of overvolt- on the fault current may be neglected in the grid-connected
age in the healthy phase(s) is the main disadvantage of this mode of operation because their currents may be negligible
limiter. To address the problems of these limiters, [9] pro- with respect to fault current contribution of the main grid.
posed the HRFL strategy that limits the i Lref in the natural However, in the islanded mode of operation, the short-circuit
reference frame using a current limiting factor (CLF) as level is low and DER units affect the fault current.

123
Electrical Engineering

Fig. 4 Direction of fault current


in study microgrid. a before
opening of CB1 (looped
structure) and b after opening of
CB1 (radial structure)

(a)

(b)

Fig. 5 Monitor of VSC output


current signal in the moving
data window

123
Electrical Engineering

The low fault current in the islanded VSC-interfaced


microgrid makes the fault detection difficult because the
conventional OCRs operate based on the current amplitude;
therefore, a fault condition may not be detected or the fault
clearance time increases. Also, reducing the threshold may
result in nuisance tripping. On the other hand, regarding the
looped structure of study microgrid and presence of several
DER units in the network, the direction of the fault current in
OCRs locations is different and the fault point is fed from both
forward and backward directions. In this condition, the fault
current flowing through the OCRs is not proportional to their
distances to the fault location. Regarding the looped structure
of study microgrid, when the CBs near the fault point isolate
the faulty feeder, the microgrid structure changes to radial
type. It results in a change in fault current direction that this
change leads to protection miscoordination. One of the worst
scenarios is when the fault occurs near the DER unit with the
lower rating. In this case, CBs near the DER units with higher
ratings may wrongly isolate a healthy feeder. As shown in
Fig. 4a, when a fault occurs at line 1, first, CB1 as the closet
CB to the fault point is opened using the associated OCR.
After the operation of CB1, the microgrid structure changes
to radial and the fault current direction changes, as shown in
Fig. 4b. In this condition, depending on the rating and loca-
tion of DERs and OCR settings, the CBs of a healthy line
may be wrongly opened. Fig. 6 Flowchart of the proposed fault detection algorithm

4 Proposed protection scheme where

4.1 Fault detection algorithm Sbase


Ibase = , (5)
Vbase
The limited fault current of EC-DERs leads to one of the
main protection challenges of islanded microgrids. Due to
and Sbase and Vbase are the nominal power and voltage of
the absence of high fault current contribution of the main net-
DER, respectively.
work, the conventional overcurrent protection devices cannot
When a fault occurs, the VSC output current changes with
detect the fault condition or detect this condition without
respect to its pre-fault value. The difference between the
proper speed. Reducing the threshold may result in normal
post-fault and pre-fault values is known as the fault-imposed
load switching wrongly interpreted as a fault event by these
component. It is independent of the pre-fault current and
devices. To address the problem, this paper proposes a fault
keeps the fault signature. Consequently, during a fault con-
detection algorithm that is based on monitoring the transient
dition, the output current signal consists of fault-imposed and
response of DER current. The proposed strategy is inspired
normal-running components as
from [43] that measures the overall severity of an episode
of care. The reason for adopting this algorithm is the differ-
ence in transient response during a fault condition and a load pu pu pu
i o,F (kTs ) = i o,FI (kTs ) + i o,N (kTs ), (6)
switching event. The proposed fault detection strategy is local
and only requires the available output current measurement.
In the first step of the proposed algorithm, the output cur- pu pu pu
where i o,F , i o,FI , and i o,N are the fault, fault-imposed, and
rent of DER is normalized as normal-running components of output current, respectively.
Ts and k are the sampling period and sampling step, respec-
pu io tively. The fault-imposed component can be calculated using
io = , (4) the Delta filter [44] as
Ibase

123
Electrical Engineering

(a) (b)
Fig. 7 a Output current and h calculated for DER1 during an a–b–c–g fault and b output current and OSI calculated for DER3 during an a–g fault

pu pu pu
i o,FI (kTs ) = i o (kTs ) − i o (kTs − Td ), (7)

where Td is the time delay of Delta filter. Figure 5 shows


pu
that absolute values of i o,FI signal samples are monitored
by a moving data window to quickly detect any change in
signal form. To make a trade-off between the accuracy and
speed, the length of the moving window is adopted equal to
a half cycle. To calculate the fault-imposed components, the
time delay of the Delta filter is also considered equal to a
half cycle; thus, each sample is reduced by the associated
sample in the previous half cycle. The overall severity of a
disturbance is calculated as

N 
 
pu
OSI = 1 − 1 − i o,FI (kTs ) , (8)
k=1
Fig. 8 Output current and h calculated for DER4 of the study microgrid
where OSI is the overall severity index and N is the num- during load 3 switching
ber of samples within a moving window. Unlike the adding
or averaging current samples over a moving data window,
A disturbance is considered as a fault event if h > ξ ,
this multiplicative multi-attribute utility model prevents the
where ξ is the fault detection threshold. Since OSI is calcu-
dilution of the effect of severe fault-imposed samples on the
lated in each phase independently, the faulty phase(s) can be
overall score by the non-severe ones. Also, the increase in
identified based on its value. The flowchart of the proposed
output current does not necessarily lead to a high overall
fault detection algorithm is shown in Fig. 6.
score. During normal operation, OSI = 0 because the fault-
imposed component is zero. However, when a disturbance
occurs, OSI increases depending on the disturbance severity. 4.2 Protection coordination strategy
The fault detection index (FDI) is expressed as
According to Sect. 3, the OCR-based protection system coor-
     
dinately operates if the current flowing through the relay near
pu pu pu
h = max OSI i oa,FI , OSI i ob,FI , OSI i oc,FI . (9) the fault is greater than the current flowing through other
relays. To this end, the injected current of EC-DERs should

123
Electrical Engineering

Fig. 9 Output current


waveforms of all DERs
equipped with conventional
HRFL strategy during an
a–b–c–g fault

Fig. 10 Current flowing


through all CBs of the study
microgrid equipped with
conventional HRFL strategy
during an a–b–c–g fault

pu pu
be proportional to their distances to the fault point; the shorter where UN and UF are the amplitudes of normalized
distance to the fault point, the higher injected fault current to normal-running and fault components of DER output volt-
the network. Due to the need for limiting the VSC current for age, respectively. It should be mentioned that all voltage and
preventing damage to its semiconductor switches, [39] mod- current signals of the DER control system are normalized
ifies the latched limit strategy using a voltage-based droop based on the nominal power and voltage of each DER. If
characteristic. The proposed protection system is based on the current reference exceeds its threshold in one phase, the
the modification of HRFL strategy using a voltage term to associated CLF is adaptively calculated using (10). The pres-
pu pu
simultaneously satisfy both current limiting and protection ence of voltage term UN − UF results in limiting level of
coordination requirements. the DER injected current is adaptively determined based on
The modified current limiting factor is expressed as its distance to the fault point. Consequently, those EC-DERs
that are closer to the fault point more contribute to the fault
current than others.
⎧ 0.5




1

⎨ U pu − U pu
N, j F, j i th 5 Performance evaluation
CLF j = √ , IL,
ref > √ ; j = a, b, c,

⎪ ×
ref,pu j
2

⎪ 2 I L, j

⎩1,
This section is dedicated to evaluating the effectiveness of the
otherwise proposed protection scheme. The islanded looped microgrid
(10) of Fig. 2 is simulated using MATLAB/Simulink and ETAP.

123
Electrical Engineering

(a) (b)
Fig. 11 Characteristic curve of OCRs of study microgrid equipped with conventional HRFL strategy during an a–b–c–g fault. a Characteristic
curve of OCR associated with CB1 during fault and b Characteristic curve of OCRs associated with CB2, CB7, and CB8 after opening of CB1

The former software presents the time domain results while 5.1.2 Case 2: single-phase-to-ground fault
the latter software presents the characteristic curves of OCRs.
Both fault detection and protection coordination functions This case study is dedicated to evaluating the performance of
of the proposed scheme are evaluated through several case the proposed fault detection strategy during an asymmetri-
studies. The length of moving data window and time delay cal fault. A single-phase-to-ground fault (a–g) with the fault
of Delta filter is 10 ms, the sampling time is 1 ms, and the resistance of 2  is simulated in line 4. Figure 7b shows the
current and fault detection thresholds are adopted equal to DER1 output current and OSI for three phases. OSI in phase
3 pu and 0.06 pu, respectively. All disturbances are simulated a increases to 0.284 pu and exceeds its threshold while OSI
at t = 4 s. in healthy phases b and c does not. Thus, this condition is
correctly classified as an a–g fault event. The fault detection
time is about 4 ms. It verifies the proper sensitivity and speed
5.1 Fault detection performance of the proposed fault detection scheme.

5.1.1 Case 1: three-phase-to-ground fault

This case study evaluates the performance of the proposed


fault detection strategy in the case of symmetrical faults. A 5.1.3 Case 3: three-phase load switching
three-phase- to-ground fault with fault resistance of 0.5  is
simulated in line 1. Figure 7a shows the simulation results The objective of this scenario is to investigate the perfor-
for this scenario. h increases to 0.263 pu and the fault is prop- mance of the proposed scheme in the case of load switching.
erly detected. Thus, this condition is correctly interpreted as a To this end, the switch S is closed at t = 4 s and load 3 as
fault event by the proposed scheme. The fault detection time the largest load of the study microgrid is energized. Figure 8
is about 3 ms. As shown in Fig. 7a, during semi steady-state shows the output current and h for DER4. h increases to
condition after fault occurrence, the fault-imposed compo- 0.049 pu but does not exceed the threshold ξ . Thus, the pro-
nent backs to zero because there is no difference between the posed fault detection strategy does not mal-operate during a
current samples in two consecutive half cycles. load switching event.

123
Electrical Engineering

Fig. 12 Output current


waveforms of all DERs
equipped with modified HRFL
strategy during an a–b–c–g fault

Fig. 13 Current flowing through


all CBs of the study microgrid
equipped with modified HRFL
strategy during an a–b–c–g fault

5.2 Protection coordination performance than other CBs currents. However, as shown in Fig. 10, the
current flowing through CB7 and CB8 is greater than CB2
5.2.1 Conventional HRFL strategy current. Figure 11b shows that the OCR associated with CB7
and CB8 operates 0.196 s after operation of CB1 associated
As mentioned in Sect. 2.3, the currents of EC-DERs are lim- relay while this time delay for OCR associated with CB2 is
ited at i th by HRFL strategy regardless of their distances to 0.233 s. Thus, CB7 and CB8 are opened and the faulty sec-
the fault point. Figure 9 shows the output current of all DERs tion is not isolated. It verifies that the conventional HRFL
in the case of a symmetrical fault at line 1. The currents of strategy does not preserve the protection coordination.
VSCs are properly limited at three times their rated currents
during the fault condition. Figure 10 shows the current flow- 5.2.2 Modified HRFL strategy
ing through CBs of the study network in this scenario in per
unit; all CB currents are normalized using the Sbase = 40 kVA To verify the effectiveness of the proposed protection strat-
and Vbase = 400 V. When the fault occurs at t = 4 s, the egy, all EC-DERs of the study microgrid are equipped with
CB1 current increases to 3.27 pu peak (122.2 A RMS) that the modified HRFL strategy. Figure 12 shows the output cur-
is greater than other CBs currents. According to the charac- rent of all DERs during a simulated symmetrical fault in
teristic curve of the associated relay shown in Fig. 11a, this line 1. The limiting level of DER current is different after the
relay operates at t = 4.271 s. When CB1 is opened, it is opening of CB1; the current of DER2 as the closet source to
expected that CB2 operates to isolate the faulty section. To the fault point is limited at 3 pu while DER4 as the farthest
this end, the current flowing through CB2 should be greater source to the fault point is limited at 2.5 pu. As shown in

123
Electrical Engineering

(a) (b)
Fig. 14 Characteristic curve of OCRs of study microgrid equipped with modified HRFL strategy during an a–b–c–g fault. a Characteristic curve
of OCR associated with CB1 during fault and b Characteristic curve of OCRs associated with CB2, CB7, and CB8 after opening of CB1

Fig. 15 Output current


waveforms of all DERs
equipped with modified HRFL
strategy during an a–b fault

Fig. 13, first, CB1 is opened because its current is greater ates 0.278 s after the opening of CB1, as shown in Fig. 14b.
than other CBs currents. Based on the characteristic curve of Consequently, the proposed protection strategy preserves the
Fig. 14a, the associated OCR of CB1 operates at t = 4.291 s. protection coordination among OCRs of the study microgrid.
When CB1 is opened, the current flowing through CB2 is The objective of the next scenario is investigating the per-
greater than other CBs currents and its associated OCR oper- formance of the proposed protection strategy in the case of

123
Electrical Engineering

Fig. 16 Current flowing through


all CBs of the study microgrid
equipped with modified HRFL
strategy during an a–b fault

(a) (b)
Fig. 17 Characteristic curve of OCRs of study microgrid equipped with modified HRFL strategy during an a–b fault. a Characteristic curve of
OCR associated with CB1 during fault and b Characteristic curve of OCRs associated with CB2, CB7, and CB8 after opening of CB1

asymmetrical faults. To this end, a line-to-line fault is sim- 6 Conclusion


ulated at line 1. Figure 15 shows the output current of all
EC-DERs. The proposed strategy adaptively determines the The increased reliability and reduced greenhouse gases
limiting level of the injected current of DERs based on their emission have led to increasing attention to the EC-DERs
distances to the fault point. As shown in Fig. 16, the greatest interfaced looped microgrids. The motivation of this paper
current passes through CB1 and its associated OCR operates was to develop an effective protection strategy for this type
at t = 4.303 s based on characteristic curve of Fig. 17a. of microgrids in the islanded mode of operation. To address
When CB1 is opened and configuration of the study micro- the low fault detection sensitivity of conventional overcurrent
grid changes to radial, the greatest current passes through relays, the proposed scheme quantifies the overall severity of
CB2 and its associated OCR operates at t = 4.586 s, as the fault condition as the fault detection criterion. The fault
shown in Fig. 17b. detection algorithm only requires the output current signal
of DER and can distinguish a fault condition from a load
switching event. The problem of protection miscoordination

123
Electrical Engineering

of available overcurrent relays with the same characteris- 12. Sortomme E, Venkata SS, Mitra J (2010) Microgrid protection
tics is addressed using the proposed protection coordination using communication-assisted digital relays. IEEE Trans Power
Deliv 25:2789–2796
strategy that is implemented in the DER control system. By 13. Kar S, Samantaray SR (2014) Time-frequency transform-based
modifying the limiting level of HRFL strategy, the injected differential scheme for microgrid protection. IET Gener Transm
current of each DER is adaptively changed proportional to Distrib 8:310–320
its distance to the fault point. It results in the current of 14. Samantaray SR, Joos G, Kamwa I Differential energy based micro-
grid protection against fault conditions. In: IEEE PES innovative
relays closer to the fault point is greater than that of other smart grid technologies (ISGT), pp 1–7
relays and consequently, the commercially available OCRs 15. Huang W, Nengling T, Zheng X, Fan C, Yang X, Kirby BJ (2014)
can coordinately operate. The developed coordination strat- An impedance protection scheme for feeders of active distribution
egy does not require the physical communication link and networks. IEEE Trans Power Deliv 29:1591–1602
16. Casagrande E, Woon WL, Zeineldin HH, Svetinovic D (2014) A
additional devices. Simulation results obtained from several differential sequence component protection scheme for microgrids
case studies verify the effectiveness of the proposed pro- with inverter-based distributed generators. IEEE Trans Smart Grid
tection scheme. Developing a thresholdless fault detection 5:29–37
algorithm and modifying other sections of VSC control sys- 17. Hou C, Hu X Differential energy based microgrid protection against
fault conditions. In: International conference on electrical engineer-
tem such as droop control and virtual impedance loop for ing, pp 1–7
coordination preservation can be considered as future works. 18. Loix T, Wijnhoven T, Deconinck G Protection of microgrids
with a high penetration of inverter-coupled energy sources. In:
CIGRE/IEEE PES joint symposium integration of wide-scale
renewable resources into the power delivery system, pp 1–6
19. Wang X, Li Y, Yu Y Research on the relay protection system for a
References small laboratory-scale microgrid system. In: 6th IEEE conference
on industrial electronics and applications, pp 2712–2716
1. Sangwongwanich A, Yang Y, Sera D, Soltani H, Blaabjerg F (2018) 20. Al-Nasseri H, Redfern MA, Li F A voltage based protection
Analysis and modeling of interharmonics from grid-connected for micro-grids containing power electronic converters. In: IEEE
photovoltaic systems. IEEE Transactions on Power Electronics power engineering society general meeting
accepted for publication 21. Al-Nasseri H, Redfern MA Harmonics content based protection
2. Mishra PP, Bhende CN (2018) Islanding detection using sparse S- scheme for micro-grids dominated by solid state converters. In:
transform in distributed generation systems. Electr Eng 100:2397– 12th international middle-east power system conference, pp 50–56
2406 22. Redfern MA, AL-Nasseri H Protection of micro-grids dominated
3. Sadeghkhani I, Golshan MEH, Mehrizi-Sani A, Guerrero JM, by distributed generation using solid state converters. In: IET 9th
Ketabi A (2018) Transient monitoring function-based fault detec- international conference on developments in power system protec-
tion for inverter-interfaced microgrids. IEEE Trans Smart Grid tion (DPSP 2008), pp 670–674
9:2097–2107 23. Nikkhajoei H, Lasseter R (2006) Microgrid fault protection based
4. Ma K, Chen W, Liserre M, Blaabjerg F (2015) Power controllability on symmetrical and differential current components, Technical
of a three-phase converter with an unbalanced AC source. IEEE Report, Public Interest Energy Research, California Energy Com-
Trans Power Electron 30:1591–1604 mission
5. Olivares DE, Mehrizi-Sani A, Etemadi AH, Cañizares CA, Iravani 24. Zhang F, Mu L (2018) A fault detection method of microgrids with
R, Kazerani M, Hajimiragha AH, Gomis-Bellmunt O, Saeedi- grid-connected inverter interfaced distributed generators based on
fard M, Palma-Behnke R, Jiménez-Estévez GA, Hatziargyriou the PQ control strategy, IEEE Transactions on Smart Grid (accepted
ND (2014) Trends in microgrid control. IEEE Trans Smart Grid for publication, 2018)
5:1905–1919 25. Jayawarna N, Jones C, Barnes M, Jenkins N Operating microgrid
6. Govindugari Venkata S, Ganesh V, Madichetty S (2018) Appli- energy storage control during network faults. In: IEEE international
cation of bacteria foraging algorithm for modular multilevel conference on system of systems engineering
converter-based microgrid with effect of wind power. Electr Eng 26. van Overbeeke F Fault current source to ensure the fault level in
100:2023–2036 inverter-dominated networks. In: 20th international conference and
7. Kolluri RR, Mareels I, Alpcan T, Brazil M, de Hoog J, Thomas DA exhibition on electricity distribution—Part 1, pp 1–4
(2017) Power sharing in angle droop controlled microgrids. IEEE 27. Jayawarna N, Jenkins N, Barnes M, Lorentzou M, Papthanassiou
Trans Power Syst 32:4743–4751 S, Hatziagyriou N Safety analysis of a microgrid. In: international
8. Liu X, Shahidehpour M, Li Z, Liu X, Cao Y, Tian W (2017) Pro- conference on future power systems
tection scheme for loop-based microgrids. IEEE Trans Smart Grid 28. Mirsaeidi S, Dong X, Said DM (2018) Towards hybrid AC/DC
8:1340–1349 microgrids: critical analysis and classification of protection strate-
9. Sadeghkhani I, Golshan MEH, Guerrero JM, Mehrizi-Sani A gies. Renew Sustain Energy Rev 90:97–103
(2017) A current limiting strategy to improve fault ride-through 29. Voima S, Kauhaniemi K Using distance protection in smart grid
of inverter interfaced autonomous microgrids. IEEE Trans Smart environment. In: IEEE PES innovative smart grid technologies,
Grid 8:2138–2148 Europe
10. Han Y, Hu X, Zhang D Study of adaptive fault current algorithm for 30. Tsimtsios AM, Korres GN, Nikolaidis VC (2019) A pilot-based
microgrid dominated by inverter based distributed generators. In: distance protection scheme for meshed distribution systems with
2nd international symposium on power electronics for distributed distributed generation. Int J Electr Power Energy Syst 105:454–469
generation systems, pp 852–854 31. Ebrahimpour M, Vahidi B, Hosseinian SH (2013) A hybrid
11. Coffele F, Booth C, Dyśko A (2015) An adaptive overcurrent pro- superconducting fault current controller for DG networks and
tection scheme for distribution networks. IEEE Trans Power Deliv microgrids. IEEE Trans Appl Supercond 23:5604306–5604306
30:561–568

123
Electrical Engineering

32. Varma RK, Rahman SA, Atodaria V, Mohan S, Vanderheide T 39. Oureilidis KO, Demoulias CS (2016) A fault clearing method
(2016) Technique for fast detection of short circuit current in PV in converter-dominated microgrids with conventional protection
distributed generator. IEEE Power Energy Technol Syst J 3:155– means. IEEE Trans Power Electron 31:4628–4640
165 40. IEC standard for single input energizing quantity measuring relays
33. Yazdanpanahi H, Li YW, Xu W (2012) A new control strategy to with dependent or independent time, IEC standard 60255 (2009)
mitigate the impact of inverter-based DGs on protection system. 41. Zamani MA, Yazdani A, Sidhu TS (2012) A communication-
IEEE Trans Smart Grid 3:1427–1436 assisted protection strategy for inverter-based medium-voltage
34. Fani B, Bisheh H, Sadeghkhani I (2018) Protection coordination microgrids. IEEE Trans Smart Grid 3:2088–2099
scheme for distribution networks with high penetration of photo- 42. Chandorkar MC, Divan DM, Adapa R (1993) Control of parallel
voltaic generators. IET Gener Trans Distrib 12:1802–1814 connected inverters in standalone AC supply systems. IEEE Trans
35. Beheshtaein S, Cuzner R, Savaghebi M, Guerrero JM (2019) Ind Appl 29:136–143
Review on microgrids protection. IET Gener Trans Distrib 13:743– 43. Alemi F, Walters SRB (2006) A mathematical theory for identifying
759 and measuring severity of episodes of care. Qual Manag Health
36. Bukhari SBA, Haider R, Zaman MSU, Oh Y-S, Cho G-J, Kim C-H Care 15:72–82
(2018) An interval type-2 fuzzy logic based strategy for microgrid 44. Benmouy G, Roberts J (1999) Superimposed quantities: their true
protection. Int J Electr Power Energy Syst 98:209–218 nature and application in relays. Schweitzer engineering laborato-
37. Beheshtaein S, Cuzner R, Savaghebi M, Golestan S, Guerrero ries, Inc., Pullman
JM (2019) Fault location in microgrids: a communication-based
high-frequency impedance approach. IET Gener Transm Distrib
13:1229–1237
Publisher’s Note Springer Nature remains neutral with regard to juris-
38. Abbaspour E, Fani B, Heydarian-Forushani E (2019) A bi-level
dictional claims in published maps and institutional affiliations.
multi agent based protection scheme for distribution networks with
distributed generation. Int J Electr Power Energy Syst 112:209–220

123

You might also like