SECTION 7

SYSTEM STATUS MONITORING


Konqsberq K-Pos DP

Introduction
Functions are available for monitoring the status of the K-Pos
DP
operator stations, process stations and IO system.
During normal operation you can:
. View the operational status of the Operator Stations, History
Stations and Process Stations
. View information and status indications for every IO driver,
IO block and IO point configured in the system.

System architecture
A K-Pos DP system consists of one or more operator stations
(OS) and one or more process stations (PS). A history station
(HS) may also be included.
The K-Pos DP control software is implemented in one, two or
three K-Pos DP process stations (DpPSs) (the Main controller PS
group) depending on the redundancy level of the system. The
process stations are implemented in computers located in the
K-Pos DP Controller Cabinet.
The DpPSs in the Main controller group are interconnected via a
dedicated redundancy net (RedNet).
Communication between operator stations, history stations and
process stations is via a single or dual communication net (Net
A and Net B).
Communication with thrusters and sensors is performed by the
IO system, which is an integrated part of the DpPS. If additional
IO is required for sensors or thrusters, additional dedicated IO
process stations can be implemented.

The process stations themselves provide no permanent storage


of programs and data. When a process station starls up, all its
programs and data are loaded from its PS servers, which are
located either on one or more operator stations or in the flash
memory of the PS itself.

july 2008 - Rev 0 3


Konosbero K-Pos DP

Operator stations
The following standard names are used to identiff the operator
stations and history stations in K-Pos DP systems:

OS name OS description
DP-OS1 Main K-Pos DP Operator Station
DP-O52 Main K-Pos DP Operator Station
DP.O53 Main K-Pos DP Operator Station
DP-O54 Fire Backup K-Pos DP Operator Station
DP-O56 Stand-alone Simulator K-Pos DP Operator Station
DP-HSI Main K-Pos DP History Station
cPos-OS1 cPos Operator Station
cPos-OS2 cPos Operator Station
cJoy-OT1 cJoy Operator Terminal
cJoy-OT2 cJoy Operator Tcrminal
wTl cJoy (cWing) Wing Terminal
wT2 cjoy (cWing) Wing Terminal
wT3 cJoy (cWing) Wing Terminal
WT4 cJoy (cWing) Wing Terminal

Process stations
The process stations are implemented in Remote Control Units
(RCU).
The RCU unit contains a real-time single board computer and
lO interflaces in the same unit.

Redundancy
In single systems, the K-Pos DP Controller Cabinet contains a
single DpPS.
In dual systems, the K-Pos DP Controller Cabinet contains two
DpPSs which operate with a master/slave relationship.
Switching between master and slave can be performed manually,
or the switching can be performed automatically by the system.
In triple systems, the K-Pos DP Cabinet contains three DpPSs.
The concept of majority voting is used to detect and isolate
faults in the sensors and in theK-Pos DP system itself.

WinPS
A WinPS is a Process station that runs on an OS computer, as
opposed to a standard PS. AWinPS provides full PS
functionality,
except that it cannot communicate with the IO system.
WinPSs are used for development purposes and in simulators.

July 2008 - Rev 0


Konqsberq K-fos DP

PS names and numbers


The following standard names and numbers are used to identiff
process stations and redundancy groups in K-Pos DP systems.

Redundancy Redundancy type PS description


group
DpMain Single, DpDual or DpTriple Main K-Pos DP Controller PS A
Main K-Pos DP Conholler PS B
Main K-Pos DP Controller PS C
DpM IO1 Single, DpDual or DpTriple Main Input/Output 1

DpM IO2 Single, DpDual or DpTriple Main Input/Output 2


DpM Sim Sinsle Main - Simulator (WinPS)
DpM_Vrm Single Main - Built-in Trainer - Vessel Reference
Model (WinPS)
DpFS Vrm Single Field Simulator - Vessel Reference Model
(WinPS
DnBackup Sinele Backup K-Pos DP Controller PS A
DpB IOI Single Backup Input/Output
DpB IO2 Single Backup Input/Output 2
DpB Sim Sinsle Backup - Simulator (WinPS)
DpB Vrm Sinele Backup - Vessel Reference Model (WinPS)

The Vessel Reference Models run in WinPS and provide


simulator and built-in trainer functions.

IO system
The IO system provides the communication interface for
exchange of IO signals between the field devices (thrusters and
sensors) and the process station.
The main elements of the IO system are:
.IO drivers
IO drivers are responsible for the communication with the
field device. The IO driver provides conversion between field
values and IO raw values.

The following driver types are supported:


- RBUS for discrete analog and digital IO
NetIO for communication between PSs
- Dedicated sensor and interface drivers for serial line
devices such as Artemis, GPS, Fanbeam and HPR
- ComAs for generic serial line IO
. IO blocks
An IO block represents a group of identifiable IO signals from
an IO device in the field. For example:
- For IO cards belonging to the RBUS driver, an IO block
represents an IO card in the IO rack.
- For NetIO communication between process stations, an IO

July 2008 - Rev 0 5


Konasbero K-Pos DP

block may represent all the signals related to a particular


sensor or thruster.
. IO points
IO points are the connection points for IO signals. An
IO point may provide signal conditioning elements for
conversion between the IO raw value on the driver side and
the engineering value on the K-Pos DP system side.

Monitoring functions
The following monitoring functions are available:
. Viewing of status information for the Operator Stations,
History Stations and Process Stations in your system. using
the Equipment - System Status dialog box.
. Viewing of status information for all PSs in the system, using
the Station Explorer dialog box.
. Viewing of overview information for all IO drivers, IO blocks
and IO points, using the [O Manager dialog box.
. Viewing of information for selected IO Points using the Io
Point Browser dialog box. See IO Point Brovvser on page 259.
. Viewing of information displayed for each IO Block, related
to each IO Point and its contents, using the IO Terminal Block
dialog box
. Viewing of information for selected DP PS Serial porls using
the Properties DpPs Serial port dialog box.
-
NI
^*o
Many of the.fbanres provided by these dialog boxes are related
to configuring the system. These feahu'es recpire OS
Con/iguration Mode and/or PS Configtratiorz Mode and
thereJore are not described in this manual. This manual only
describes features thqt qre available in normal operation mode.

Eq u ipment
The Equipment - System Status dialog box shows operational
status information about the Operator Stations, History Stations
and Process Stations in your system.

July 2008 - Rev 0


Konqsberq K-Pos DP

DpailS A OFdr6, fr 4927.88 313h 14.O9.O509:45:10 125414


0di-P1 A Operd@d OK 'l3a2a 8.04 d 06,09105 05:{X5a 12:5111
Oril$ F Oplimil 4930? i14h 14n9trn+4F1? 1?5111
Dplf_Dl B OFrdrmd OK 13aa1 8md mnw05:4354 12:5{14
DpM_Sn A OFrdind c{< 0 3.14h l4€9O509:45:12 12:5t14
OpM_Vrm A OFdrmd OK 0 314h 14{)grtr509:1E12 12:.5q11

This dialog box has five pages:

.PS
. PS Redundancy
. OS/HS
. Event Printer
. Net Status
In each line of each page, the background colour of certain fields
are changed to indicate alarm conditions.

When a system or process alarm condition occurs, the


background
of the field changes colour and starts to flash. It will continue to
flash until the applicable alarm is acknowledged.

PS page
The PS page shows the current status of all process stations
defined in the system.
To display this page, select System+Equipment.

Dd/oin A Operdbnd 192?88 313h 14,Ogn509:46:10 125414


0FM_D1 A OFrdrfrd 94 OK 13424 8.04d mO9O505:43:54 125414
DpMnn B Oplrdimd OX 4931.02 3.14h 14O9O50946:12 12:5411
oplv_D1 B Operational 94 OK 13424 8.04 d 1160S05 05:4151 I 254'1 1
OpM_Sin A Operdrfrnl 0 OX 0 3.14h 14I]9.050946:12 115411
Dpil Vrm A Orerationa/ 0 OK 0 3.14h 14O9O50946:12 12:54.11

July 2008 - Rev 0


Konosbero K-Pos DP

Station
Identification of the PS.
Group name
Displays the name of the redundancy group to which this station
belongs.
(No column title)
Identification of the PS within the redundancy group. For
example: Controller PS A, B or C within the DpMain group.
Status
Shows the current status of the PS:
. Operational PS is operational.
. Booting -
PS is booting (loading configuration).
- PS is rebooting due to an effor.
. Rebooting
-
. Not Communicational PS has repofted a status, but no
communication with the - PS is possible.
. Not Reported PS has not reported any status.
. Halt -
PS has stopped due to an error condition.
-
Spare Time (7o)
The available CPU capacity, expressed as a percentage of total
CPU capacity.
Net State
Indicates the state of the A and B network interfaces:
. OK Both network interfaces are OK.
-
. A-ERROR Error on network interface A.
. B-ERROR - Error on network interface B.
. AB-ERROR- Error on both network interfaces.
-
I/O Status
Shows the status of the IO system for this PS:
. OK No errors reported.
. ERROR Errors reported.
-
Serial Status
Not relevant for K-Pos DP systems.
Other Status:
Shows the status of other sub-systems reported by this station
(typically system self-test and monitoring):
. OK No errors reported.
-
. ERROR Erors reported.
-
Free Memory
Available memory (or largest continuous block) in kB. (Not
applicable for WinPSs.)
Uptime
The accumulated uptime of the station. Shown as a number
followed by a character indicating the period. For example: 3.06
d indicates 3.06 days (m: minutes, h: hours, d: days, y:
years).

July 2008 - Rev 0


Konqsberg K-Pos DP

Started
Time stamp when the PS was started.
Format: daylmonth/year hour: min: sec
Last reported
Time stamp of last communication.
Format: hour:min:sec
The PS page has a shortcut menu. Right-click anywhere on the
page to display the following menu:
Print Image... Print Image.. see Print Image.
station Exphrer... Station Explorer... see Station Explorer.
P5 Info. ,. PS Info... not relevant for K-Pos DP systems during normal
system Everts.. ,
operation.
IO t'lanager.,,
System Events... see Presentation of messages.
IO Point Bro' r'er,..
IO Manager... see 10 Manager.
IO Point Browser... see IO Point Browser.

PS Redundancy page
The PS Redundancy page shows redundancy information for all
process stations.

To display this page, select System---rEquipment and then click


the PS Redundancy page tab.

A CFffi Y6 Y6 Cotrmdrn ftrx*E oPM


a opaffi Y6 Y6 q n'@ oPM
aDh I Op6d@ M b Dqr# Rr@ oPU
DpM.lOl I OpaM Y.s Y6 q Rrn$4 oPM

Station
Identification of the PS.
Group name
Displays the name of the redundancy group to which this station
belongs.
(No column title)
Identification of the PS within the redundancy group. For
example: Controller PS A, B or C within the DpMain group.
Status
Shows the current status of the PS:
. Operational PS is operational.
. Booting -
PS is booting (loading configuration).
- PS is rebooting due to an elror.
. Rebooting
-

July 2008 - Rev 0


Konosbero K-Pos DP

. Not Communicational PS has reported a status, but no


-
communication with the PS is possible.
. Not Reported PS has not reported any status.
. Halt -
PS has stopped due to an eror condition.
-
Online
Displays whether the PS is online or not. See Redundant $rytems
on page 120.
Master
Displays whether the PS is master or not. See Redundant $)stems
on page 120.
Capability
Displays the Capability status, indicating to what extent the PS is
technically capable of fulfilling its intended purpose:
. OK No errors.
- Error Errors that are common to all PSs in the
. Common
redundancy group.-
. Degraded Errors that related to only this PS in the
redundancy - group.
. lncapable The PS is in a state where it should not be used
-
as the master or online computer.

Running mode
Displays the Running mode:
. Running The PS is communicating and has finished all
-
start-up preparations.
. Starting The PS is communicating, but more startup
preparation - is needed.
. lnactive The PS is not communicating. It may be
initializing- or loading, or not executing at all.
Type
Displays the redundancy type for the redundancy group.
For the DpMain and DpM_IO groups, the following types are
relevant: Single, DPDual and DPTripte.
The PS Redundancy page has a shortcut menu. Right-click
anywhere on the page to display the following menu:

Prini Image... Print Image.. seePrint Imcrge on page 246.


Station Explorer.,. Station Explorer... see Station Explorer on page 247 .
P5 Info.,. PS Info... not relevant for K-Pos DP systems during normal
System Events.,, operation.
IO Manager,,.
System Events... see Presentation of messages on page 90.
IO Point Browser...
I0 Manager... see IO Manager on page 251.
IO Point Browser... see IO Point Browser on page 259.

10 July 2008 - Rev 0


Konqsberg K-Pos DP

OS/HS page
The OS/HS page shows the status of the operator stations and
history stations that are defined in the system.
To display this page, select System-Equipment and then click
the OS/HS page tab.

Station
Identification of the OS or HS.
Status
Shows the current status of the OS or HS:
. Operational OS or HS is operational.
-
. Not Communicational OS or HS has reported a status, but
-
no communication with the OS or HS is possible.
. Not Reported OS or HS has not reporled any status.
. Stopped -
OS or HS is not switched on.
-
Last Reported
Time stamp of last communication.
Format: daylmonth/year hour:min:sec
Net State
Indicates the state of the A and B network interfaces:
. oK Both network interfaces are OK.
-
. A-ERROR Error on network interface A.
. B-ERROR - Error on network interface B.
. AB-ERROR- Error on both network interfaces.
-
The OS/HS page has a shortcut menu. Right-click anywhere on
the page to display the following menu:

Print Image...

Event Printer page


The Event Printer page shows the status of the event printers that
are configured in the system.

July 2008 - Rev 0 11


Konosbero K-Pos DP

To display this page, select System---+Equipment and then click


the Event Printer page tab.

The operator stations in the K-Pos DP system are grouped into


Print Groups - usually either Main or Backup - where each group
has one event printer. Only one of the operator stations (the
Master) within a print group will print alarm messages to the
event printer. If the Master operator station becomes inactive for
any reason, the role of event printer Master passes automatically
to another active Master of the Print Group.
Station
The address ofthe event printer.
Print Group
The name of the group of operator stations that can print to this
printer.
Master
The current master operator station in this print group.
Members
The operator stations that are members of this print group. If an
operator station is not active, its name is shown in parentheses.
Printer Info
Information on the printer status such as Idle or Printing. This
information is provided by the printer interface.
The Event Printer page has a shortcut menu. Right-click
anywhere on the page to display the following menu:

Print Image,,.
l
Net Status
The Net Status page shows the status of the communication
network for all OSs, HSs and PSs in the system.
To display this page, select System+Equipment and then click
the Net Status page tab.

L2 July 2008 - Rev 0


Konqsbetg K:P9S_DP

This page contains a window that is divided into two panes. The
left-hand pane lists all stations in the communication network by
means of icons and names. Clicking any icon or name displays
in
the righrhand pane the status of the communication network as
seen from the receiving station in the lefrhand pane.

If a red A, B or AB is displayed superimposed on an icon, this


indicates that the station has a network communication elror on
net A, B or both.
Sending Station
Identification of the OS, HS or PS sending messages to the
receiving station.
Msg pr. 100 sec
The total number of messages being received every 100 seconds
on both networks.
Lost Msg Net A
The number of lost messages on network A.
Lost Msg Net B
The number of lost messages on network B.
IpAddress
The lnternet Protocol (IP) address of the sending station.
The right-hand pane is static and once information has been
displayed it is not updated. You can update the information
either
by reselecting the Net Status page or by right-clicking anywhere
on the page to display the following shortcut menu:
PrinL Image., ,

Select Print Image to print the content of the current page.


Update 5tatistics
5how only errors Select the Update Statistics command to update the statistical
information for the selected station in the right-hand pane.
Select the Show only errors command to filter the information
displayed in the right-hand pane so that only the stations with lost
messages are displayed.

July 2008 - Rev 0 13


Konqsberq K-Pos DP

Print Image
The Print Image command on the shortcut menu of the PS, PS
Redundancy, OS^IS or Net Status page allows you to print the
content ofthe current page on your printer.
Selecting this command displays the Print dialog box.

Printer

Status: Fleady
Type: Canon GP300-405 PS Ver 1.0
\dhere: Hom ru. F2009
Eommenl PS printer i"-. print to file

Print tange

Number of gopies:

r-' Pages lrom: ii-'- to,


r.
I

Comment

i-" Color print


foK -l carcet I

Select the appropriate printer from the Name drop-down list box.
Use the Properties button to select the printout format.
Comment
The text that you type in the Comment text box is printed in a
separate box on the top right corner ofthe printout.
Color print
Select this check box if a printout in colour is required.

Station Explorer
The Station Explorer provides system status information for all
system components in a selected process station, such as:
. For the basis system: applicable PS system information,
self-tests and environment checks (such as temperature check,
fan alarm).
. For the IO Manager: information on all nodes and subnodes
of allconfigured IO parts.
. For the Network: information on the redundant networks -
Net A and Net B.

74 July 2008 - Rev 0


Konqsberq K-Pos DP

A11 nodesin the process station are represented by graphical


symbols showing their current alarm status.
To display the Station Explorer dialog box:
1 Select System+Equipment.
. TheEquipment - System Status dialog box is displayed.
2 Righrclick on a PS line anywhere on the PS or PS
Redundancy page of the Equipment - System Status dialog
box.
. The following shortcut menu is displayed:

Print knage,,,

5tation Explorer..,
P5 Info. ..
SystBm Events.,.
IO Manager.. .

IO Point Browser. ,.

3 Select Station Explorer....


. Thestation Explorer dialog box is displayed, showing the
PS that you right-clicked in step 2.

.: PS vasion
.1'. Fledndacy
+ i WntchDog t
- i: l0 Man4s ,
+ -j AdflisDrv_1 h
- 1 ComAs
- '.1;
1-RSEF20&1
^ i
:: Serid port 101
:r Seridpodl02
-: Scid pod 103
l Seiai port 104
+ r' i
2_RSER20O1
+ ':) 3-FSEB20[I4I
+ 1; 4 BSER20$1 i
* :; 5-FSEB20O1 I
* -: 6-RSEB200'1 I
+ i: 7_8SE8200.1 I
+ :8-FSEB20[I1 i
'l Fabear0n-2 )
: 6psDrv-33 2,
i GpsOrv-4 2,
:, HprDrv-3 2
:: Netlol ,,
-. NetloSysBed 2,
:. Nme.DN-lo 2
1'NrcaDrv-l'l 2
: NreaDN-12 2
-- Nm.dD&-l3 2
1 NrcaDrv-14 2
a; Nmaory-s A
,1 Nrcaorv-B
i NrcoDrv-7 A ^
ai NreaON-8 z
,1, NmaDrv-9 2
I B8usDriva ;
+ ,-' P34_8MP200.8 E
. .r P35 BMPm0-8 E

July 2008 - Rev 0 15


Konosbero K-Pos DP

4 You can use the drop-down list box to select any other PS
to be displayed.

PS tree structure
The dialog box provides a tree structure showing all the nodes
and subnodes in the PS. The tree structure can be expanded and
collapsed, to display or hide information details. Graphical
symbols are displayed to indicate the alarrn status. Hotspot
symbols provide links to dialog boxes for displaying further
information about the IO system.

Alarm status indicators


The following alarm status indicators may be displayed on the
PS status view pane.

,t' There is an error condition in this equipment node, and the


alarm is not acknowledged. When acknowledged, a red circle is
displayed (see below).

+ri but the alarm is not acknowledged. When acknowledged, a green


circle is displayed (see below).

iF There is an error condition in this equipment node and the alarm


is acknowledged.

. :'': The red arrow indicates that there is either an error or an


unacknowledged alarm in one or more equipment subnodes.

r:-: Node and all sub equipment nodes are OK.

Hotspots
Hotspot symbols provide links to dialog boxes for displaying
further information about the IO system:
jj Displays the Properties dialog box, which shows an overview of
the software and hardware status of the selected PS. This feature
is intended only for Kongsberg Maritime personnel.

Displays the Io Manager dialog box, which shows the status of


the IO drivers and IO blocks for the selected PS. See 10
Manager.

.& Displays the Driver Properties dialog box for the selected IO
driver. This feature is intended only for Kongsberg Maritime
personnel.

16 July 2008 - Rev 0


Konqsberq K-Pqs DP

v Displays a submenu:

. For an IO driver:
5how BBUS lO Image,,.
5how IO Dri'.;er.,,

- Theshow RBUS IO Image command displays a graphical


view of the IO cards.

- The Show IO Driver command displays the Driver


Properties dialog box for the selected IO driver. This
feature is intended only for Kongsberg Maritime personnel.
. For an IO block (IO card):
Show IO Block., ,

Propertier,,,

- Theshow IO Block command displays the IO Terminaal


Btock dialog box, which shows information about the
selected IO block and its IO points.
TheProperties command displays the Properties dialog box
for the selected IO card. This feature is intended only for
Kongsberg Maritime personnel.
. For a serial port:
I

L-I:l"jt'*:': _
- TheProperties command displays the Properties dialog box
for the selected serial port.

Displays theIo Terminal Block dialog box, which shows


information about the selected IO block and its [O points.

Acknowledging PS system alarms


To acknowledge a PS system alarm:
I Righrclick on the appropriate node in the tree structure of
the Station Explorer dialog box.
. The following shortcut menu is displayed:
System Evenls for Node. ,,
System EvenLs for Node and Subnodes...
System Events for P5,,,

2 Select the appropriate command from the shortcut menu.


. TheEvent List window is displayed, containing the
relevant alarms:

- System Events for Node displays alarms for the selected


IO node.

July 2008 - Rev 0 L7


Konosbero K-Pos DP

- System Events for Node and Subnode displays alarms


for the selected IO node and all subnodes.
- System Events for PS displays all alarms for the
selected PS.
3 Acknowledge the alarm.

IO Manager
The Io Manager dialog box displays an overview of the IO
system, showing the IO drivers and IO blocks for a selected
station.
To display the Io Manager dialog box, either:
I Select System+Equipment.
. TheEquipment - System Status dialog box is displayed.
2 Righrclick on a PS line anywhere on the PS or PS
Redundancy page of the Equipment - System Status dialog
box.
. The following shortcut menu is displayed:
Print Image, ,,

stalion Explorer,, ,

P5 Info,.,
Syslem Events,..
IO Manager...
IO Point Browser, ,,

3 Select IO Manager.
. Thelo Nlanager dialog box is displayed.
or:
1 Start the Station Explorer
2 Select the required PS from the drop-down list.
3 Click on the IO Manager icon ( P).
The Io Manager dialog box has three pages, which give an
overview of the IO Interface system:
. TheIO Configurator page, in expandable tree view, presents
the IO drivers, IO objects and IO blocks for the selected PS.
. TheIO Statistics page gives an overview of the connected
terminals and modules. This feature is intended only for
Kongsberg Maritime personnel.
. TheIO Library page presents the contents of the IO typical
library. This feature is intended only for Kongsberg Maritime
personnel.

18 July 2008 - Rev 0


Konqsberq K-Pos DP

IO Configurator
Use the drop-down box to select the PS for which you will
display the IO drivers and IO blocks.
In the expandable tree view, the symbols are as follows:
1st level, lists the IO driver types (J ;
2nd level, lists the IO drivers (l ;
3rd level, lists the IO blocks in alphabetic order ( Ga;
If you click on an IO driver name, the corresponding Driver
Properties dialog box is displayed.
If you click on an IO block name, the corresponding IO Terminal
Block dialog box is displayed.

RBUS IO Image
The RBUS IO Image provides a graphical view of the status of
the RBUS IO cards. This is intended as an aid to fault-findins
in the IO system.
To display the RBUS IO Image:
I Start the Station Explorer
2 Select the required PS from the drop-down list.
3 Expand the IO Manager to locate the RBUSDriver.
4 Click on the sub-menu symbol 1*? ; and select the Show
RBUS IO Image command from the sub-menu.

The RBUS IO Image can be displayed either in the Overview


level or the Detailed level:
. When the Overview level is selected, the display corresponds
to the physical layout of the IO cards as you see them in the
IO cabinet.
. When the Detailed level is selected, more detailed card and
rack information is displayed. The Detailed level is intended
primarily for Kongsberg Maritime personnel.

Overview level
Example RBUS IO Images at the Overview level for an
RCU-based PS is shown below.

July 2008 - Rev 0 19


Konosbero K-Pos DP

I DpOrMaintYindow:trEUS - DpPsOl
ffifi i33 fr Dopso v
OPC
r{ru WL 6
ra
t<
l=
l< I,
=
n
lr
I
l=
IN
!
\) E
\)
to..r'.r lc cc c,
lo IC
lr
lo l& D
I
D
I

I I

E &

A' v

The alarm status indicators are the same as for the Station
Explorer.
lf you click on an IO card, the Io Terminal Block dialog box is
displayed showing information about the selected IO card and its
IO channels..
If you right-click on an IO card, a shoftcut menu is displayed:

System Events for Node...


System Events for Node and Subnodes...

. TheShow IO Block command displays the IO Terminal Block


dialog box, showing information about the selected IO card
and its IO channels
. Ifthe IO card has an error condition, you can select the System
Events for Node or System Events for Node and Subnodes
command to display the Event List window containing the
relevant alarms.
The tool bar of the RBUS IO Image window provides the
following functions:
tllla
t!ttt
tttaa Displays the Overview level of the RBUS IO Image.

0[0
0[0 Displays the Detailed level of the RBUS IO Image.

fr Shows "out-of-rack" cards. Not relevant during normal


operation.

FFF.ot- .3 Use this drop-down list box to select any other PS to be


displayed.

20 July 2008 - Rev 0


Konqsberq K-Pos DP

IO Appears when an IO card is clicked.

Hides/shows the IO Terminal Block dialog box for the selected


IO card.

Detailed level
Example RBUS IO Image at Detailed level for an RCU-based
PS is shown below.

Rack positions containing PSs and power supply units are not
shown on the Detailed level.
The information provided on the Detailed level is intended
primarily for Kongsberg Maritime personnel.

IO Terminal Block
The IO Terminal Block dialog box displays information about a
selected IO block and its IO points. This is intended as an aid to
fault finding in the IO system.
To display this dialog box, either:
I Start the Station Explorer
2 Select the required PS from the drop-down list.
3 Expand the appropriate driver to locate the required IO
block.
4 Either click on the block icon (r E ;, o. click on the sub-menu

July 2008 - Rev 0 2L


Konosbero K-Pos DP

symbol ( f'o.r) and select the Show IO Block command from


the sub-menu.
or:
I Start the IO Manager
2 On the IO Configurator page, select the required PS from
the drop-down list.
3 Expand the appropriate driver to locate the required IO
block.
4 Click on the IO block name.
The content of this dialog varies according to the IO driver.

Note For IO cards belonging to the RBUS driver, a block is


the same as an IO card, and a point is the same as an IO
channel.

1- l0 Manags ,
- I FBUSDiu :
. tr P31-RI,IP2I}B E
ar l0 Eils

Tasi iP3i-AMPboii"*---'--'.-
oesoigion lPos34

Tak: i );

Pariil PraarE(caa toa Cddthho


ScCc
sign#dd*ff ftrS. cld# AMrnd (nO 10 00
+/- 10 Vd -10.m
Lq ffi*oliE ol itu chamai Ofl ;ffiord
:ngindhg acalc mx. IIrc.M
:nginBhg rcalc d. 0.00
inqinsiB d
Hffi 0.00 %
# tila r..r.
rfurotpde 3
)ord 1r Silsd 0 00
)ord 1: EEnedro 0 00
,oiil 1 S6sd 0.00
)od 2: ErBhearq 0.00
,oid3: Sffi :OoOm
)od 3: E.Eneilhg 2m0.00
;sord M
:ngF6Ed M

a1r:.,,1. i
._,,, I
Close

Station Explorer
The upper-left area displays the selected IO block, filtered from
the expandable tree strucrlrre of the Station Explorer, and
displays

22 July 2008 - Rev 0


Konqsberq K-Pos DP

the driver, alarm status and the block tag of the selected IO
block.
Tag
Displays the name of the selected IO block.
Description
Displays descriptive text for the selected IO block.
Task
Shows the scan rate for the selected IO block:
.Task1-Normal
.Task2-Quick
.Task3-Rapid

Not relevant for K-Pos DP systems.


Upper-right list box
The upper-right list box displays the IO block properties
represented by parameters and values. When you point at a
parameter, a tool-tip is displayed, providing more explanatory
text.
IO Points
This area displays information about the IO points lor the
selected IO block.
Direction
The direction of the data flow:

'! output data flow


'J Input data flow
IO tag
The name of the IO signal.
point parameter symbol)
Clicking this symbol displays the IO Point Parameters section
in the lower part of the dialog box.
Status
The stafus of the sensor value:
.OK
. Error
. SIM
Sensor value
The sensor value and its units.

(signal conditioning elements)

dd Sy-Uols representing the signal conditioning elements


used, in order of execution.

July 2008 - Rev 0 23


Konqsbero K-Pos DP

Note
Llhen the clrrsor is positioned over one of the bitmaps
representing an IO signal conditioning element, the narne and
parameters of the element are displayed in a lool-tip window.

Eng. value
The engineering value and its units.
(Eng. status)
The status of the engineering value:
.OK
. Error
. SIM
Connection
For signals that are to be transfered between process stations,
this field displays the name of the NetIO tag that corresponds to
this tO point.
Note
If 1,ott click a cell in the Connection column, the Connect/
Disconnect Terminul dialog box is displayedfor the selected IO
point. This dialog box has no functiott during normal operation.

Details
Clicking the Details button displays or removes the IO point
Parameters and Eng. Signal Conditioning sections in the lower
part of the dialog box.

Shortcut menu
If you right-click on any displayed IO point tag, the following
shortcut menu is displayed:

5et l''lanr,ral Valu*.,.


5el Error 0r,rerride
5el Sirnulator tlli
5et I* Frint in I'larmal f,.lsdr
5et All IO Pr:irrts in ltjsrfial lulrrdts

I* Tag., ,

Connertions, ,,
truto Csmert
,4ulo {ornect *ll
5ignal forditioning

Create I0 Fnint Typical,


5elert Ifi Paint Typiral,,

Reslze folumns

24 July 2008 - Rev 0


Kongsberg K-Pos DP

Resize Columns
Resizes the columns displayed in the IO Points area to fit the
content of the columns.

Signal Conditioning elements


Signal conditioning elements are used in the IO points of an IO
block to parameterize the input/output process signals and to
scale the signals.

All signal conditioning elements are bidirectional, and may be


used both on input and output signals, but some elements are
meaningful on input signals only.
The symbols are displayed between the Sensor value and Eng.
value columns in the IO Points area.

The signal conditioning includes elements for:


. Scaling
. Inversion
. Filtering
. Fail-safevalue
. Compensation for wire resistance.
The available signal conditioning elements are as follows:

Description
Icon Element name Analogue Digital Input Output

v Scale X x x Sensor scale maximum

Sensor scale minimum

Sensor unit

Engineering scale maximum

Eneineering scale minimum


Ensineerins unit

# Multi Scale X X x Number of points


(For each point) Sensor point
(For each point) Engineering Point
Sensor unit
Eneineering unit
Wire resistance
PT IOO X x Sensor unit
-=l
Ensineering unit

Engineering unit X X X Eneineering scale maximum


_ry
Engineering scale minimum

Engineering unit

July 2008 - Rev 0 25


Konosbero K-Pos DP

xx Fail-safe X X Fail-safe value


Frceze (check box):

Checked: Last usable value

Not checked: Fail-safe value

Filter X x Filter time (seconds)


'# Limit chcck X X x Gain

Bias
Use negative input value

F Invert x X X None

ft Fail-safe X X Fail-safe value

Freezc (check box):

Checked: Last usable value

Not checkcd: Fail-safe value

F Filter x x On delay (seconds)

Off delav (seconds)

IO Point Browser
The IO Point Browser allows you to search for lO points for
a selected PS, and to display information about them. This is
intended as an aid to faultfinding in the [O system.

IO Point Browser dialog box


To display the IO Point Brorvser dialog box:
I Select System+Equipment.
. TheEquipment - System Status dialog box is displayed.
2 Right-click on a PS line anywhere on the PS or PS
Redundancy page of the Equipment - System Status dialog
box.
. The following shorlcut menu is displayed:

Print Image.,,

Station Explorer,,,
P5 Info,,,
System Events,,,
IO lvlanager,.,
IO Point Browser,,,

3 Select IO Point Browser.


. TheIO Point Browser dialog box is displayed.

26 July 2008 - Rev 0


Konqsberq K-Pos DP

5tat6n

D;F'ol ---* :,
Ta9
Br#se Citaia:
ith;i---- -- -
pPs01 Il-fr7-REA0Y-lOO OK 1 1 OK
- Matchgase
pPsfi I}R7,R{JN_IN_|OD OK I 1 OK Mdlchghoh t.g
- Malch inlial iag segmat

l0 5tat6
'7 t0 0K
t l0 MaMl
7 l0 Passive
v lO Eilor
, l0 Fdilsale
V l0Enoroveride

f-8r-r- byto I.s I


-
-. s-:l:f::,:
-9,:ry::!r*u:1*l=-
:

...----'
Lbs6

Station
Use this drop-down list box to select either all PSs, or the PS
within which you want to browse.
Tag
Browse Criteria
Use this text box to enter the browse criteria. Wildcard
characters
can be used.
Match case
Use this check box to make the Browse Criteria case sensitive.
Match whole tag
Use this check box if the Browse Criteria text is the entire name
of the required IO point.
Match initial tag segment
Use this check box if the Browse Criteria text is the beginning of
the name of the required IO points.

lO Status
Use these check boxes to restrict the search to IO points which
have the specified status:
.IOOK
. IO Manual
' IO Passive
. IO Error
' IO FailSafe
. IO Error Override

July 2008 - Rev 0 27


Konosbero K-Pos DP

Browse by IO Tag
Use this command button to search for IO points whose name
satisfies the specified Browse Criteria.
Browse by Module Tag
Not relevant for K-Pos DP systems.
Details
Clicking the Details button displays or removes the IO Point
Parameters and Eng. Signal Conditioning sections in the lower
part of the dialog box.
Browse results
The upper-left area displays information about the IO points
that satisfu the search criteria. This is the same information as
displayed on the IO Terminal Block dialog (see 10 Terminal
Block), with one additional column:
. PS The name of the PS that contains the IO point.

Shortcut menu
If you right-click on any IO point tag displayed in the browser
window, the following shortcut menu is displayed:

5et I','lanr"sl ?alue,, ,

'1el- LfilI t)\!etrlde


5et 5imulator olf
Set iO Prinl irr f'lr,rmal l'I.Jde
set All IO FBiftt' in t'l*rrn:l l'4ode

IO T69,,,
fBnfiedirlnE,.,
Aul-n inmefl
Aulr tlr:meri All

5ignal Cr:rdilioning,

(reate IO Pnint Typiral,


SelErf IO Psint Typical, ,

Resize Columns
Show l() Jlocl(, , ,

Resize Columns
Resizes the columns displayed in the IO Point Browser dialog box
to fit the content of the columns.
Show IO Block
Allows you to view configuration information for the selected
IO
Block by displaying the corresponding Io Terminal Block dialog
box.

28 July 2008 - Rev 0


Konqsberq K-Pos DP

Properties - DpPs Serial port


The Properties-DpPs Serial port dialog box shows the properties
and configuration ofa selected serial port.
To display the Properties DpPs Serial port dialog box:
-
1 Start the Station

2 Select the required PS from the drop-down list.


3 Expand IO Manager, ComAs and the required serial line to
locate the required serial port (in the example below Serial
port 101).
Stdtion Explorer

lope*ot
,l:, Basis System
i:: l0 Manager
+ rl: ArtemisDr'-1 h
- {:: ComAs h,
- r:, 1_BSEF200-4 i
'::1.r EEEEEII
5erial port 102 =
1.r Serial port
.l03 v
,"; Serial port 104 v
+ :l 2_FEEB?00-4 i
+ ,-; 3-HSEE200'4 i
+ {: 4_BSEH200-4 i
+ ;1: 5 FSEH200-4 i
+ '.-: 6-HEEF200'4 i
+ r-:r /-ft!tftl[U-{ i
+ ;1:: 8-Fi5EH200-4 i
+ ;i FanbeamDrv-Z fi
+ ,l: GpsDrv-3G a
+ 1., GpsDrv-4 k
+ :1: HFrDrv_3 2
+ l' Netlol h,

4 Click on the sub menu icon ( E ;


. A shortcut menu is displayed.

5 Select Properties on this shortcut menu.


. TheProperties-DpPs Serial port dialog box is displayed.

The information provided on the Properties DpPs Serial


-
port dialog box is intended primarily for Kongsberg Maritime
personnel.

July 2OOA - Rev O


Konosbero K-Pos DP

SerPort page

oK I cancerl I

Enable configuration
When selected, the configuration shown is enabled.
Baud rate
Shows the baud rate (1 10,300,600, 1200,2400,4800,9600,
19200,38400 baud).
Parity
Shows the parity (No, Even, Odd).
Number of data bits
Shows the number of data bits (5, 6, 7, 8 bit).
Number of stop bits
Shows the number of stop bits (1,2 bi|.
Protocol
Protocols available; Ecma24, Kos100, End of File, End of
Record, Raw, Xon/Xoff, Siemens 3946L, 3946H, 3946RL,
3946RH, Measurex, UniTelWay, SMC, Polled raw, End of
Record/Raw, Kos 150, Inter Frame Gap, Time sync.
EOR char. input
Shows the End of Record character input in hexadecimal.
EOR char. output
Shows the End of Record character output in hexadecimal.
I{W handshake
Shows the Hardware handshake (No, RTS@Send,
RTS@Receive) - (RTS is short for Request To Send).

30 July 2008 - Rev 0


Konqsberq K-Pos DP

HW selection
Shows the Hardware selection (Default, RS232, RS422, RS485).
Auto disable interrupts
To automatically disable intemrpts, select this check box and
click the oK or Apply button.
Max. interrupt rate receive
Shows the highest recorded receive intemrpt rate for this serial
port (since startup or reset).
Max. interrupt rate exception
Shows the highest recorded exception intemrpt rate for this
serial
port (srnce startup or reset).

Int status page


Properties - DpPsOl: Serial port l0l

set disabled serial port f


max. interrupt rale

due to high erception rate

lal cancd I uopt, I

The Int. status page of the Properties DpPs Serial port dialog
-
for the ComAs driver displays the intemrpt status of a selected
serial port.
Reset disabled serial port
To reset a disabled serial port, select this check box and click
the OK or Apply button.
Reset max. interrupt rate
To reset the displayed values for Max. receive interrupt rate and
Max. exception interrupt rate, select this check box and click
the OK or Apply button.
Disabled due to high receive rate
Indicates whether the selected port is disabled due to high
receive
rate (0: enabled, 1 : disabled).
Disabled due to high exception rate
Indicates whether the selected port is disabled due to high
exception rate (0: enabled, I : disabled).

July 2008 - Rev 0 31


Konosbero K-Pos DP

Receive interrupt rate


Shows the current receive intemrpt rate for this serial port.
Exception interrupt rate
Shows the current exception intemrpt rate for this serial port.
Max. receive interrupt rate
Shows the highest recorded receive intemrpt rate for this serial
port (since startup or reset).
Max. exception interrupt rate
Shows the highest recorded exception intemrpt rate for this
serial port (since starfup or reset).

Resetting a disabled serial line


A serial port may be automatically disabled by the system to
protect the K-Pos DP controller computer system from high
traffic caused by an excessively high number of intemrpts.
lf an automatic disable of intermpt has been performed when
reading serial line data from, for example, a position-reference
system, a timeout alarm is issued. The message includes the
relevant driver tag.
This section describes how to manually reset a disabled serial
line so that the process station can continue reading input on that
serial line. This procedure can be performed without restarting
the controller computer.
1 In the Dynamic Alarm Page of the Event List window,
right-click the relevant message.
. A shoftcut menu is displayed.
2 Select Station Explorer on this shortcut menu.
. Thestation Explorer dialog box for the serial line that has
an error is displayed.

I
Dp=ro2

: I i., l0 Manager !
'+lffiffia
: f. Tpl_Fb
FANEI .@
,-*, l0 points

3 Click the Driver Properties hotspot (the indicator to the right


of FanbeamDrv_2 in this example).
. TheDriver Properties dialog box is displayed.

32 July 2008 - Rev 0


Konqsberq K-Pos DP

' Driver Properties - DpPsO2: FanbeamDrv 2

Drter I Driver
config. i D,iu"r status I Driveroperation j

Tag:

Description: I

Type:

Version:

l tt I c",*"t I ipe,.,
- I

4 Click the Driver operation page tab.


. TheDriver operation tabbed page is displayed.

' Driver Properties - DpPsO2: FanbeamDrv

Dri,er I Driverconfig. j Driverstatus DilveroPeration


I

f jll crya | *rerr I

5 Select the Reset disabled serial port check box.


6 Click the oK button.
. The serial line is reset.

July 2008 - Rev 0 33