OPERATING & MAINTENANCE Supersedes: Form 160.81-O1 (507) Form 160.81-O1 (311)
00562VIP
Issue Date
March 24, 2011
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation, maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
oils, materials under pressure, rotating components, and operating/service personnel. It is expected that this in-
both high and low voltage. Each of these items has the dividual possesses independent training that will en-
potential, if misused or handled improperly, to cause able them to perform their assigned tasks properly and
bodily injury or death. It is the obligation and respon- safely. It is essential that, prior to performing any task
sibility of operating/service personnel to identify and on this equipment, this individual shall have read and
recognize these inherent hazards, protect themselves, understood this document and any referenced mate-
and proceed safely in completing their tasks. Failure rials. This individual shall also be familiar with and
to comply with any of these requirements could result comply with all applicable governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is
not to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers and
controls may not be installed inside the micro panel. No external wiring is allowed to be run through
the micro panel. All wiring must be in accordance with Johnson Controls published specifications
and must be performed only by qualified Johnson Controls personnel. Johnson Controls will not be
responsible for damages/problems resulting from improper connections to the controls or application
of improper control signals. Failure to follow this will void the manufacturer’s warranty and cause
serious damage to property or injury to persons.
2 JOHNSON CONTROLS
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
CHANGE BARS
Changes from the previous version of this document are to technical information only. Any other changes in
are indicated with a line along the left or right hand col- spelling, grammar or formatting are not included.
umn in the area the revision was made. These revisions
ASSOCIATED LITERATURE
DESCRIPTION FORM NO.
SOLID STATE STARTER (MOD “B”) – OPERATION & MAINTENANCE 160.00-O2
INSTALLATION 160.81-N1
OPTIVIEW™ CONTROL CENTER – SERVICE INSTRUCTIONS 160.81-M1
WIRING DIAGRAM – UNIT WITH ELECTRO-MECHANICAL STARTER 160.81-PW1
WIRING DIAGRAM – UNIT WITH MOD “B” SOLID STATE STARTER 160.81-PW2
RENEWAL PARTS – UNIT 160.81-RP1
RENEWAL PARTS – OPTIVIEW™ CONTROL CENTER 160.81-RP3
YR TA TA T0 – A
DESIGN LEVEL
MOTOR CODE
60 Hz 50 Hz
POWER SUPPLY
CF 5CC
– for 60 Hz
CG 5CD
5 for 50 Hz
CH 5CE
CJ 5CF
COMPRESSOR CODE
CK 5CG
T0, T1, T2, T3, T4, T5
CL 5CH
CM 5CI
CN 5CJ
CONDENSER CODE
CP 5CK
TA, TB, TC, TD, TE, TF
CR 5CL
XA, XB, XC, XE, XF, XG
CS 5CM
ZA, ZB, ZC, ZD, ZE, ZF
CT 5CN
CU 5CO
COOLER CODE
CV
TA, TB, TC, TD, TE, TF
XA, XB, XC, XE, XF, XG
ZA, ZB, ZC, ZD, ZE, ZF
MODEL
JOHNSON CONTROLS 3
FORM 160.81-O1 (311)
ISSUE DATE 3/18/2011
4 JOHNSON CONTROLS
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
TABLE OF CONTENTS
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION.......................................... 11
System Operation Description......................................................................................................................... 11
Capacity Control.............................................................................................................................................. 12
Chiller Operation Overview............................................................................................................................. 12
SECTION 2 - OPTIVIEW™ CONTROL CENTER....................................................................................................17
Introduction...................................................................................................................................................... 17
Start/Stop Control............................................................................................................................................ 18
Stop / Reset (O).....................................................................................................................................19
Start (◄ )................................................................................................................................................19
Run ( ■ ).................................................................................................................................................19
Interface Conventions..................................................................................................................................... 19
Overview................................................................................................................................................19
Display Only...........................................................................................................................................19
Programmable........................................................................................................................................19
Navigation..............................................................................................................................................21
Languages..............................................................................................................................................22
Analog Input Ranges..............................................................................................................................22
Home Screen.................................................................................................................................................. 23
System Screen................................................................................................................................................ 25
Evaporator Screen.......................................................................................................................................... 27
Sensitivity Screen............................................................................................................................................ 31
Condenser Screen.......................................................................................................................................... 32
Refrigerant Level Control Screen.................................................................................................................... 34
Compressor Screen........................................................................................................................................ 36
Hot Gas Bypass Screen.................................................................................................................................. 39
Oil Separator Screen....................................................................................................................................... 40
Electro-Mechanical Starter Screen.................................................................................................................. 42
Mod “B” Solid State Starter Screen................................................................................................................. 44
Ground Fault Protection Screen...................................................................................................................... 46
Setpoints Screen............................................................................................................................................. 48
Setup Screen................................................................................................................................................... 51
Schedule Screen............................................................................................................................................. 54
User Screen.................................................................................................................................................... 56
Comms Screen................................................................................................................................................ 58
Printer Screen................................................................................................................................................. 60
Sales Order Screen......................................................................................................................................... 61
Operations Screen.......................................................................................................................................... 63
History Screen................................................................................................................................................. 65
History Details Screen..................................................................................................................................... 67
Security Log Screen........................................................................................................................................ 68
Security Log Details Screen............................................................................................................................ 70
Custom View Screen....................................................................................................................................... 71
Custom Setup Screen..................................................................................................................................... 72
Trending Screen.............................................................................................................................................. 73
Trend Setup Screen........................................................................................................................................ 75
Advanced Trend Setup Screen....................................................................................................................... 77
Trend Common Slots Screen......................................................................................................................... 79
Master Slot Numbers List For Use With Trend Feature......................................................................... 80
JOHNSON CONTROLS 5
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
6 JOHNSON CONTROLS
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 7
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
8 JOHNSON CONTROLS
FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
LIST OF FIGURES
FIGURE 1 - MODEL YR CHILLER�������������������������������������������������������������������������������������������������������������������������� 11
FIGURE 2 - REFRIGERATION FLOW THROUGH ROTARY SCREW CHILLER��������������������������������������������������� 12
FIGURE 3 - OPTIVIEW™ CONTROL CENTER�����������������������������������������������������������������������������������������������������17
FIGURE 4 - HOME SCREEN����������������������������������������������������������������������������������������������������������������������������������23
FIGURE 5 - SYSTEM SCREEN������������������������������������������������������������������������������������������������������������������������������25
FIGURE 6 - EVAPORATOR SCREEN��������������������������������������������������������������������������������������������������������������������27
FIGURE 7 - SENSITIVITY SCREEN�����������������������������������������������������������������������������������������������������������������������31
FIGURE 8 - CONDENSER SCREEN����������������������������������������������������������������������������������������������������������������������32
FIGURE 9 - REFRIGERANT LEVEL CONTROL SCREEN������������������������������������������������������������������������������������34
FIGURE 10 - COMPRESSOR SCREEN�����������������������������������������������������������������������������������������������������������������36
FIGURE 11 - HOT GAS BYPASS SCREEN������������������������������������������������������������������������������������������������������������39
FIGURE 12 - OIL SEPARATOR SCREEN��������������������������������������������������������������������������������������������������������������40
FIGURE 13 - ELECTRO-MECHANICAL STARTER SCREEN��������������������������������������������������������������������������������42
FIGURE 14 - MOD “B” SOLID STATE STARTER SCREEN�����������������������������������������������������������������������������������44
FIGURE 15 - GROUND FAULT PROTECTION SCREEN��������������������������������������������������������������������������������������46
FIGURE 16 - SETPOINTS SCREEN����������������������������������������������������������������������������������������������������������������������48
FIGURE 17 - SETUP SCREEN�������������������������������������������������������������������������������������������������������������������������������51
FIGURE 18 - SCHEDULE SCREEN�����������������������������������������������������������������������������������������������������������������������54
FIGURE 19 - USER SCREEN���������������������������������������������������������������������������������������������������������������������������������56
FIGURE 20 - COMMS SCREEN�����������������������������������������������������������������������������������������������������������������������������58
FIGURE 21 - PRINTER SCREEN���������������������������������������������������������������������������������������������������������������������������60
FIGURE 22 - SALES ORDER SCREEN�����������������������������������������������������������������������������������������������������������������61
FIGURE 23 - OPERATIONS SCREEN�������������������������������������������������������������������������������������������������������������������63
FIGURE 24 - HISTORY SCREEN���������������������������������������������������������������������������������������������������������������������������65
FIGURE 25 - HISTORY DETAILS SCREEN�����������������������������������������������������������������������������������������������������������67
FIGURE 26 - SECURITY LOG SCREEN����������������������������������������������������������������������������������������������������������������68
FIGURE 27 - SECURITY LOG DETAILS SCREEN������������������������������������������������������������������������������������������������70
FIGURE 28 - CUSTOM VIEW SCREEN�����������������������������������������������������������������������������������������������������������������71
FIGURE 29 - CUSTOM SETUP SCREEN��������������������������������������������������������������������������������������������������������������72
FIGURE 30 - TREND SCREEN������������������������������������������������������������������������������������������������������������������������������73
FIGURE 31 - TREND SETUP SCREEN�����������������������������������������������������������������������������������������������������������������75
FIGURE 32 - ADVANCED TREND SETUP SCREEN���������������������������������������������������������������������������������������������77
FIGURE 33 - TREND COMMON SLOTS SCREEN������������������������������������������������������������������������������������������������79
FIGURE 34 - PRINTERS�����������������������������������������������������������������������������������������������������������������������������������������96
FIGURE 35 - SAMPLE PRINTOUT (STATUS)������������������������������������������������������������������������������������������������������100
FIGURE 36 - SAMPLE PRINTOUT (SETPOINT REPORT)����������������������������������������������������������������������������������101
FIGURE 37 - SAMPLE PRINTOUT (SCHEDULE)������������������������������������������������������������������������������������������������103
FIGURE 38 - SAMPLE PRINTOUT (SALES ORDER)������������������������������������������������������������������������������������������104
FIGURE 39 - SAMPLE PRINTOUT (HISTORY)����������������������������������������������������������������������������������������������������105
FIGURE 40 - SAMPLE PRINTOUT (SECURITY LOG REPORT)�������������������������������������������������������������������������106
FIGURE 41 - SAMPLE PRINTOUT (TREND DATA NEW OR EXISTING POINTS)��������������������������������������������� 107
FIGURE 42 - SAMPLE PRINTOUT (CUSTOM SCREEN REPORT)��������������������������������������������������������������������107
JOHNSON CONTROLS 9
FORM 160.81-O1 (311)
ISSUE DATE 3/18/2011
10 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE 3/24/2011
SOLID STATE
STARTER OIL
SEPARATOR
CONTROL
CENTER
00562VIP
JOHNSON CONTROLS 11
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
The major components of a chiller are selected to han- pistons (slide valve) which is fed through its ports by
dle the refrigerant, which would be evaporated at full pressurized compressor oil. The flow of the oil is con-
load design conditions. However, most systems will be trolled by the equalizing solenoid valve which modu-
called upon to deliver full load capacity for only a rela- lates to load and unload the slide valve that increases
tively small part of the time the unit is in operation. or decreases the amount of refrigerant flowing to the
compressor, thus controlling the chiller capacity.
CAPACITY CONTROL
CHILLER OPERATION OVERVIEW
The major components of a chiller are selected for full
load capacities; therefore capacity must be controlled In the following description, reference is made to pro-
to maintain a constant chilled liquid temperature leav- cedures that should be performed only by a Service
ing the cooler. A slide valve arrangement located on the Technician. Instructions for these procedures are in
rotary screw compressor compensates for various load OptiView Control Center Service Instructions (Form
conditions. The slide valve arrangement is controlled 160.81-M1 and require SERVICE access level.
by the OptiView™ Control Center and unit controls
that sense the building load conditions. The control The chiller will be permitted to start only if there are no
center sends signals to the solenoid valve that loads and Safety or Cycling shutdown conditions in effect.
unloads the slide valve with the use of compressor oil When a Local or Remote start signal is applied, the
under hydraulic pressure. A cylinder located in the inlet “Start Sequence Initiated” period begins. The duration
end of the compressor houses a spring loaded shaft and of this period depends on whether or not the Refriger-
LD04976
12 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE 3/24/2011
ant Level Control feature is enabled. If the Refriger- After the first 3 minutes of System Run and for the
ant Level Control feature is disabled, the duration is 30 remainder of System Run, if the Differential Discharge
seconds. If the Refrigerant Level Control is enabled, Oil Pressure decreases to following threshold for 2
the duration is programmable over the range of 30 to continuous seconds, a safety shutdown is performed 1
300 seconds with the Valve Preset Time setpoint. The and “Oil – Low Differential Discharge Oil Pressure”
Variable Orifice must be positioned to the 75% closed is displayed: [(evap press/10) +20] PSID with soft-
position prior to starting the compressor motor. Since ware version C.OPT.05.09.303 and later or less than
it is in the fully open position while the chiller is shut- [(evap pressure/10) +15] PSID with software version
down, the valve is driven to the 75% closed position C.OPT.05.08.303 and earlier.
during the “Start Sequence Initiated” period. Due to
variances in Orifice actuator timing and valve position After the first 3 minutes and for the remainder of Sys-
requirements for the different chiller/compressor com- tem Run, the Minimum Load Control feature prevents
binations, the “Start Sequence Initiated” period dura- the slide valve from unloading to a point that will not
tion must be adjusted to allow the Orifice to reach the allow sufficient oil transfer to the Oil Separator. The
75% closed position prior to starting the compressor slide valve position at which insufficient oil transfer
motor. “Start Sequence Initiated” is displayed on the occurs is based on compressor motor current. The op-
Display System Status Line along with a countdown erating point at which the low separator oil level oc-
timer indicating time remaining while the period is in curs, can be found by manually unloading the slide
effect. valve while observing the system conditions. Once
established, the minimum allowed slide valve posi-
During the first 15 seconds of the “Start Sequence tion is that which will maintain the compressor motor
Initiated” period, early vintage chillers performed the current above the programmed Minimum Load FLA
pressure transducer auto-zeroing. Beginning with soft- (15% to 70%) setpoint. When the slide valve unloads
ware versions C.OPT.05.09.303 (and later), the auto- to the point the motor current decreases to the setpoint
zeroing feature is no longer used. If applicable, refer to value, no more unload pulses will be applied. If it un-
description of this feature, as used in previous software loads to the point where the motor current is less than
versions, in OptiView Control Center Service Instruc- the setpoint, a 1 second load pulse is applied every 3
tions (Form 160.81-M1). seconds until the motor current is more than or equal
to the Minimum Load FLA setpoint value. While the
The Chilled Liquid Flow Switch position is checked slide valve unloading is being inhibited, “MINIMUM
5 seconds before the end of the “Start Sequence Initi- LOAD – LOAD LIMIT” is displayed on the System
ated” period. If not closed, a cycling shutdown is per- Details Line of the Display.
formed.
Later in 2007, new production chillers are equipped
At the completion of the start sequence, the Oil Sup- with an oil level sensor in the Oil Separator. The Low
ply Solenoid Valve is energized (opened), “SYSTEM Separator Oil LED on the OIL SEPERATOR screen
RUN” is displayed and the start signal is applied to the indicates the oil level status. With sufficient level, it is
compressor motor starter. extinguished. With insufficient level, it is illuminated.
When the Condenser Pump Delay setpoint (0 to 90 After the chiller has been running for at least 3 minutes,
seconds) [software version C.MLM.05.06.xxx (and if the level sensor opens for 30 continuous seconds,
later) or C.OPT.05.06.xxx (and later)] has elapsed, a safety shutdown is performed and “Oil Separator –
condenser pump contacts TB2-150/151 close to start Low Level” is displayed. The chiller can be restarted
the condenser pump. after the COMPRESSOR switch is placed in the Stop-
Reset (O) position and sufficient oil has been added to
During the first 2 minutes of System Run, a HOLD allow the Sensor to see sufficient level and provide a
output is applied to the slide valve. During the third closed circuit to the Microboard.
minute, if the oil pressure is less than or equal to
((1.1 x evaporator pressure) + 15 PSID), a load out- After the chiller has been running for more than 3 min-
put is applied to the slide valve until the oil pressure utes, the slide valve is loaded and unloaded to control
is more than or equal to ((1.1 x evaporator pressure) the Leaving Chilled Liquid Temperature to the Leav-
+ 18 PSID). Also during the first 3 minutes of “Sys- ing Chilled Liquid Temperature setpoint (as explained
tem Run”, the Variable Orifice position is maintained later, there is no unloading in Ice Storage mode). The
at the 75% closed position and controlled thereafter as SENSITIVITY setpoints can be adjusted by a Service
described below.
JOHNSON CONTROLS 13
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Technician to reduce over/under-shoot of the Chilled Ice Storage mode is an operating mode within Brine
Liquid setpoint and adapt the control to the local oper- mode that allows the chiller to make ice at a faster than
ating conditions. normal rate by inhibiting unload pulses to the slide
valve. Load pulses are applied until the Leaving Chilled
The following Load Limiting conditions will over- Liquid Temperature Cycling Offset-Shutdown thresh-
ride the normal Leaving Chilled Liquid Temperature old is reached, whereupon the chiller shuts down. No
control. The message displayed for each condition is in unload pulses or hold outputs are applied to the slide
parenthesis. Refer to DISPLAY MESSAGES section valve unless any of the following load limit conditions
of this book for details of each limit. exist:
• Low Evaporator Pressure (“Warning – Evaporator – • Low Evaporator Pressure
Low Pressure Limit”)
• High Condenser Pressure
• High Condenser Pressure (“Warning – Condenser –
High Pressure Limit”) • High Motor Current
• High Motor current (“Motor-High Current Limit”) • Low Discharge Superheat
• Low Discharge Superheat (“Warning – Low Dis- The chiller will automatically restart when the Ice Stor-
charge Superheat Limit”) age Restart threshold is exceeded. Ice Storage mode
is turned ON from the EVAPORATOR screen. After it
• High Discharge Pressure (“Warning – Discharge – is turned ON, Ice Storage mode is automatically acti-
High Pressure Limit”) vated (inhibits unload pulses) and deactivated (allows
The slide valve can be manually controlled by a Ser- unload pulses) by the value programmed for the Leaving
vice Technician from the COMPRESSOR screen using Chilled Liquid Temperature setpoint. Values less than
the Keypad keys. or equal to 32.0ºF activates Ice Storage mode. Setpoint
values more than 32.0ºF deactivate Ice Storage mode.
To provide oil cooling, liquid refrigerant is injected into
the compressor during high Discharge Temperature An LED on the EVAPORATOR screen illuminates
conditions. When the Discharge Temperature increases when Ice Storage mode is active. This allows the chill-
to the programmed Liquid Injection setpoint threshold, er to be switched in and out of Ice Storage mode by a
a solenoid valve is opened, injecting liquid refrigerant Local or Remote change of this setpoint. This feature
into the compressor. This setpoint is programmable by allows the chiller to make ice in the nighttime hours
a Service Technician over the range of 130 to 165°F. and perform air-conditioning duty during the daytime
(fixed at 165°F in software version C.MLM.05.03. hours simply by changing the Leaving Chilled Liquid
xxx) When the Discharge Temperature decreases to Temperature setpoint. When Ice Storage is turned ON,
10°F below this setpoint, the solenoid valve is closed. there are two different Restart setpoints employed: One
is programmed and will be in effect when the Leaving
To prevent overcooling the building or process, the chill- Chilled Liquid Temperature setpoint is less than or equal
er will shutdown and display “LEAVING CHILLED to 32.0ºF (Ice Storage mode active), the other is pro-
LIQUID – LOW TEMPERATURE” when the Leaving grammed and will be in effect when the setpoint is more
Chilled Liquid Temperature decreases to less than the than 32.0ºF (Ice Storage mode not active). Each Restart
programmed Leaving Chilled Liquid Temperature setpoint can be programmed to a different value.
Cycling Offset-Shutdown setpoint. After it has shut-
down, the chiller is prevented from restarting until the Since liquid refrigerant is transferred from the Con-
Leaving Chilled Liquid Temperature has increased to denser to the Evaporator via the Condenser-Evaporator
more than the programmed Leaving Chilled Liquid pressure differential, a large differential can create an
Temperature Cycling Offset-Restart setpoint. This excess refrigerant level in the evaporator. A small dif-
prevents short cycling the chiller. ferential can result in insufficient level in the Evapora-
tor. To maintain an appropriate refrigerant level in the
The chiller can cool WATER or a BRINE solution. Evaporator under all conditions, the chiller is equipped
Water can be cooled over a range of 38.0º to 70.0ºF. with a Variable Orifice. To maintain an appropriate
If Smart Freeze protection (explained below) is en- refrigerant level in the evaporator under all conditions,
abled, the range is 36.0º to 70.0ºF. Brine solution can a Variable Orifice is located in the refrigerant line be-
be cooled over a range of 20.0º to 70.0ºF. tween the condenser and evaporator.
14 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE 3/24/2011
A liquid level sensor, located in the condenser, detects The offset is added to the programmed Level Control
the refrigerant level. The refrigerant level in the con- setpoint and is displayed as EFFECTIVE REFRIGER-
denser is expressed as 0% (minimum) to 100% (maxi- ANT LEVEL SETPOINT (over the range of 20% to
mum). While the chiller is shutdown, an open signal is 80%) on both the CONDENSER screen and the RE- 1
applied to the actuator, driving the Orifice to the fully FRIGERANT LEVEL CONTROL screen. This is the
open position. When the chiller is started, a close sig- setpoint used to control the level control.
nal is applied to the Orifice actuator for the duration of
the “Start Sequence Initiated” period. This positions it The Orifice can be manually operated from the key-
to approximately the 75% closed position prior to start- pad, using this screen. The Refrigerant Level Control
ing the compressor motor, which occurs at the end of must be enabled by a Service Technician. A complete
the “Start Sequence Initiated” period. description of the Refrigerant level Control operation
are contained in OptiView Control Center Service In-
To allow for actuator timing variances and assure the structions (Form 160.81-M1).
valve is positioned at the 75% closed position, the du-
ration of the “Start Sequence Initiated” period is pro An optional Hot Gas Bypass system allows the chiller
grammable over the range of 30 to 300 seconds with to remain running during extreme light load conditions
the Valve Preset Time setpoint. This position is held by diverting hot refrigerant gas directly from the Oil
for the first 3 minutes of “System Run”. After the first Separator to the Evaporator, bypassing the Condenser.
3 minutes, if the actual level is greater than or less than A solenoid valve, located in the bypass line, is opened
the setpoint, a linearly increasing or decreasing ramp is and closed under Program control to turn the hot gas
applied to the Level setpoint. This ramp causes the set- ON and OFF. When the chiller is shutdown, the Hot
point to increase or decrease (as appropriate) from the Gas Bypass is turned OFF. Each time the chiller is
actual position to the programmed setpoint over a de- started, it remains OFF for the first 3 minutes of chiller
fined period. With software version C.OPT.05.08.303 operation. Thereafter, it is controlled per the differen-
(and earlier), this period is 15 minutes. With software tial between the Return Chilled Liquid Temperature
version C.OPT.05.09.303 (and later), this period is pro- and the Leaving Chilled Liquid Temperature setpoint.
grammable over a range of 3 to 15 minutes using the This differential is programmed as the Hot Gas ON and
RAMP-UP TIME setpoint. Hot Gas OFF setpoints by a Service Technician. If the
chiller is equipped with the Hot Gas feature, operation
During the remainder of chiller run, the actuator is must be enabled by a Service Technician. A complete
modulated to maintain the programmed Level setpoint description of the Hot Gas Bypass system is contained
(20 to 80%). This setpoint and others that affect this in OptiView Control Center Service Instructions (Form
operation are programmed by the Service Technician 160.81-M1).
on the REFRIGERANT LEVEL CONTROL screen. In
software version C.OPT.05.09.303 (and later), an off- To prevent an overcurrent condition when starting the
set is added to the Level Control setpoint during Low compressor, the slide valve should be in the unloaded
Discharge Superheat events. This offset is displayed position. While the unload signal is being applied,
on the REFRIGERANT LEVEL CONTROL screen as “Slide Valve Unloading Before Shutdown” is dis-
REFRIGERANT LEVEL SETPOINT OFFSET. This played. To assist the slide valve in returning to the un-
offset is calculated, over the range of 0% to (80% mi- loaded position, an unload signal is applied to it while
nus programmed Level setpoint), as follows: the compressor is still running prior to shutting down
on the following shutdowns:
• When the chiller is not running, the offset is 0%.
• MULTIUNIT CYCLING - CONTACTS OPEN
• T
he offset remains at 0% during the level control
valve preset and during the ramp after chiller start. • SYSTEM CYCLING - CONTACTS OPEN
• W
hen Discharge Superheat is less than 14ºF and • REMOTE STOP
the Evaporator Pressure is more than 28.0 PSIG, • LEAVING CHILLED LIQUID - LOW
add 1% to the offset every 15 seconds, not to ex- TEMPERATURE
ceed the maximum offset.
• CONTROL PANEL - SCHEDULE
• W
hen Discharge Superheat more than 20ºF sub-
tract 1% from the offset every 15 seconds, not to The duration of the unload signal applied depends on
fall below the minimum offset. the software version:
JOHNSON CONTROLS 15
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
• With software version C.OPT.05.08.303 (and ear- til the temperature increases to more than 35.0ºF. After
lier), it is 60 seconds. the chiller has been shutdown for at least the time delay
programmed as the Freeze time setpoint, and the tem-
• With software version C.OPT.05.09.303 (and later),
perature decreases to less than 28.0ºF, “WARNING –
the duration is determined by the motor current
FREEZE THREAT FROM OPERATING CHILLER”
when the shutdown command is received as follows:
is displayed and alarm output is activated. When the
- 100% FLA or above equals 30 seconds. temperature increases to 28.0ºF, the warning message
and alarm output automatically clear. If this feature is
- 7 5% FLA and below equals 5 seconds, lin- desired, Freeze Warning must be enabled by a Service
ear between 75% and 100% FLA. Technician. A complete description of this feature is
In multiple chiller applications it may be possible for contained in the OptiView Control Center Service In-
the chilled liquid (Water or Brine) from an operating structions (Form 160.81-M1).
chiller to flow through the Evaporator of a standby Motor current overload protection is provided by the
chiller. This represents a possible freeze threat to the CM-2 Board (Electro-Mechanical Starters) and Liq-
Condenser of the standby chiller. The Standby Chiller uid Cooled Solid State Starter. The overload is a timed
Freeze Protection feature minimizes this freeze po- function beginning at 105% of the Chiller Full Load
tential by allowing the OptiView™ Control Center of Amps. With software version C.OPT.05.07.xxx (and
the standby chiller to cycle the condenser pump based later), there is also a motor current overload provided
on the standby chiller’s Condenser Saturation Tem- by the Microboard software. It also starts at 105% of
perature while it is shutdown. At chiller shutdown, the the chiller Full Load Amps and is adjustable over the
pump runs until the condenser saturation temperature range of 12 (default) to 40 seconds with the 105% Mo-
increases to more than 35.0ºF, whereupon the pump is tor Current Time setpoint. When the motor current has
turned OFF. While the chiller is shutdown, the condens- exceeded 105% of Chiller FLA continuously for the
er saturation temperature is monitored. If it decreases programmed time period, a safety shutdown is per-
to less than 30.0ºF, the pump is turned ON and runs un- formed and “105% Motor Current Overload” is dis-
played on the System Details Line of the Display.
16 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00565VIP
JOHNSON CONTROLS 17
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 19
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Change Setpoints 4. If the dialog box begins with “SELECT”, use the
On screens containing setpoints programmable at the ◄ and ► keys to select the desired value.
OPERATOR access level, a key with this label will be
5. If the previously defined setpoint is desired, press
visible if the present access level is VIEW. This key
the ‘X’ (Cancel) key to dismiss the dialog box.
brings up the Access Level prompt described above. It
allows the user to login at a higher Access Level with- 6. Press the ‘√’ (Enter) key.
out returning to the HOME screen. After login, the user
7. If the value is within range, it is accepted and the
may then modify setpoints on that screen.
dialog box disappears. The chiller will begin to
Setpoints operate based on the new programmed value. If
out of range, the value will not be accepted and
The control center uses the setpoint values to control the user is prompted to try again.
the chiller and other devices connected to the chiller
system. Setpoints can fall into several categories. They Manual Controls
could be numeric values (such as 45.0°F for the Leav- Some keys are used to perform manual control func-
ing Chilled Liquid Temperature), or they could Enable tions. These may involve manual control of items such
or Disable a feature or function. as the slide valve. Other keys in this category are used
Regardless of which setpoint is being programmed, the to initiate/terminate processes such as calibrations or
following procedure applies: reports.
1. Press the desired setpoint key. A dialog box ap- Free Cursor
pears displaying the present value, the upper and On screens containing many setpoints, a specific “soft”
lower limits of the programmable range, and the key may not be assigned to each setpoint value. A soft
default value. key will be assigned to enable the cursor arrow keys be-
2. If the dialog box begins with the word “ENTER”, low the numeric keypad which are used to “highlight”
use the numeric keys to enter the desired value. the desired setpoint field. At this point, the ‘√’ key is
Leading zeroes are not necessary. If a decimal pressed to bring up a dialog prompting the user to en-
point is necessary, press the ‘•’ key (i.e. 45.0). ter a new setpoint value. The ‘X’ key cancels Cursor
mode. (See the SCHEDULE screen for an example.)
3. Pressing the ▲ key, sets the entry value to the de-
fault for that setpoint. Pressing the ▼ key clears
the present entry. The ◄ key is a backspace key
and causes the entry point to move back one
space.
20 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Navigation
In order to maximize the amount of values which the HOME screen display, the upper-right “soft” key will
panel can display to the user, and in order to place those always return the user to the HOME screen. Navigating
values in context, multiple screens have been designed with “soft” keys is as simple as pressing the key next
to describe the chiller operation. In order to move from to the label containing the name of the desired screen.
one screen to the next, navigation keys have been de- The system will immediately refresh the display with 2
fined. These keys allow the user to either move “for- the graphics for that screen. Following is a layout of all
ward” to a sub-screen of the present screen, or move the screens and how they are connected.
“backward” to the previous screen. Except for the
HOME screen (page 23)
System Screen (page 25)
Evaporator Screen (page 27)
Sensitivity* (page 31)
Condenser Screen (page 32)
Refrigerant Level Control* (page 34)
Compressor Screen (page 36)
Hot Gas Bypass* (page 39)
Oil Sump (Separator) Screen (page 40)
Motor Screen (page 42)
Electro-Mechanical Starter (page 42)
- or -
Mod “B” Solid State Starter (page 44)
Ground Fault Protection* (page 46)
Setpoints Screen (page 48)
Setup (page 51)
Schedule (page 54)
User (page 56)
Comms (page 58)
Printer (page 60)
Sales Order (page 61)
Operations (page 63)
Diagnostics* (Refer to OptiView Control Center Service Instructions
History Screen (page 65) (Form 160.81-M1)
Trending (page 73)
View Details (must be activated once to view)
Trend Setup (page 75)
Slot #s *
Triggers
Advanced Trend Setup (page 77)
Trend Common Slots (page 79)
Custom View (page 71)
History (page 65)
Custom Setup (page 72)
Security Log (page 68)
JOHNSON CONTROLS 21
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Notes:
1. Saturation temperatures are calculated values. They are derived from applicable refrigerant pressure-temperature conversion lookup table
in the program. They will display XXX if the pressure used for the calculation is out of range.
2. Style B (and later) chillers are not equipped with an Evaporator Refrigerant Temperature Sensor (RT7). Software versions C.MLM.05.04.
xxx (and later) do not read or display this value.
22 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
HOME SCREEN
00551VIP
JOHNSON CONTROLS 23
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
the chiller controls. The access levels are listed above Warning Reset
in hierarchical order beginning with the lowest level Access Level Required: OPERATOR
and proceeding to the highest level. Users logged in
under higher access levels may perform any actions Use of this key acknowledges a warning condition and
permitted by lower access levels. resets the message display associated with it.
The OPERATOR access level is accompanied by a Navigation
10-minute timeout. After ten (10) successive minutes
without a key press, the panel will revert to the VIEW System
access level. This prevents unauthorized changes to the Used to provide additional system information.
chiller if a user was logged in at a higher access level
and failed to logout. Proper procedure requires that Evaporator
after making necessary setpoint adjustments the user A detailed view of all evaporator parameters, including
return to the HOME screen and logout. the programmable Leaving Chilled Liquid Setpoints.
Logout Condenser
Access Level Required: OPERATOR A detailed view of all condenser parameters.
This key is displayed when a user is logged in at any
Compressor
level other than VIEW. Pressing it will return the ac-
cess level to VIEW. A detailed view of all the compressor parameters. This
includes slide valve control, and Hot Gas Bypass Con-
Print trol and slide valve calibration.
Access Level Required: VIEW
Oil Sump
Use this key to generate a hard-copy report of the A detailed view of all the oil sump parameters. This
present system status. This provides a snapshot of the includes the seal lubrication functionality.
primary operating conditions at the time the key is
pressed. The History page provides enhanced report- Motor
ing capability. (See HISTORY below.) A detailed view of the Motor Controller parameters,
specific to the controller type presently utilized on the
Message Clear
chiller system. This allows programming of the Cur-
Access Level Required: SERVICE rent Limit and the Pulldown Demand Limit values.
When certain safety or cycling conditions have been Setpoints
detected and the chiller has been shutdown, the main
status display of the chiller will continue to display a This screen provides a single location to program the most
message indicating the cause of the shutdown. Using common system setpoints. It is also the gateway to many
this key, the message can be cleared once the condition of the general system setup parameters such as Date/Time,
has been removed. Display Units, Scheduling, Printer Setup, etc.
History
This screen provides access to a snapshot of system
data at each of the last 10 shutdown conditions.
24 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
SYSTEM SCREEN
LD09714
JOHNSON CONTROLS 25
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
26 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
EVAPORATOR SCREEN
LD09715
Displays the command presently sent by the control Leaving Chilled Liquid Temperature Setpoints
center to the Chilled Liquid Pump (RUN or STOP). – Setpoint
JOHNSON CONTROLS 27
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
to make ice at a faster rate as explained in the “Opera- displayed value is the difference between the present
tion” section. The water cooling setpoint range is 38°F Leaving Chilled Liquid Temperature setpoint and the
to 70°F. The Brine cooling setpoint range is 20°F to setpoint entered for the Leaving Chilled Liquid Tem-
70°F and the default is 45°F. When in Brine mode and perature Cycling Offset - Restart. If Ice Storage is ON
Ice Storage mode is ON, it is automatically activated and the Leaving Chilled Liquid Temperature setpoint is
and deactivated by the setpoint that is entered: less than or equal to 32.0ºF, the Restart Temperature is
the value programmed as the Ice Storage Restart Tem-
• At 20°F to 32°F Ice Storage mode is activated. perature.
• More than 32°F to 70°F deactivates Ice Storage
mode. Leaving Chilled Liquid Temperature Setpoints
– Restart Offset
This allows the chiller to be switched in and out of Ice
Displays the offset above the Leaving Chilled Liquid
Storage mode (when in Brine mode and ice storage is
Temperature setpoint at which the chiller will restart
ON) by locally or remotely changing this setpoint.
after it has shut down to avoid over-cooling. This is the
Leaving Chilled Liquid Temperature Setpoints Leaving Chilled Liquid Temperature Cycling - Restart
– Remote Range setpoint (See the description in the following section of
programmable setpoints). If Ice Storage is ON and the
Displays the present maximum range above the Leaving Leaving Chilled Liquid Temperature setpoint is less
Chilled Liquid Temperature setpoint that this setpoint than or equal to 32.0ºF, the Restart Offset is the value
can be remotely changed to. This is the Local Leaving programmed as the Ice Storage Restart Offset.
Chilled Liquid Temperature - Range setpoint (See the
description in the following section of programmable Ice Storage Active (LED)
setpoints).
Illuminates when Ice Storage mode is active. It is ac-
Leaving Chilled Liquid Temperature Setpoints tive when Ice Storage mode has been turned ON and
– Shutdown the Leaving Chilled Liquid Temperature setpoint is set
to less than or equal to 32.0°F. Extinguished when Ice
Displays the Leaving Chilled Liquid Temperature at Storage mode is turned ON but not Active. It is not
which the chiller will shut down to avoid over-cooling active when the Leaving Chilled Liquid Temperature
the building. By default this value is 4°F below the setpoint is more than 32.0°F. If Ice Storage mode is
Leaving Chilled setpoint. The displayed value is the turned OFF, this indicator is not displayed.
difference between the present Leaving Chilled Liquid
Temperature setpoint and the setpoint entered for the Programmable
Leaving Chilled Liquid Temperature Cycling Offset –
Shutdown. Local Leaving Chilled Liquid Temperature –
Range
Leaving Chilled Liquid Temperature Setpoints Access Level Required: OPERATOR
– Shutdown Offset
This is the range over which an analog (0 to 20mA,
Displays the offset below the Leaving Chilled Liquid
4 to 20mA, 0 to 10VDC or 2 to 10VDC) in Analog
Temperature setpoint at which the chiller will shutdown
Remote mode or a digital signal (PWM) in Digital Re-
to avoid over-cooling. This is the Leaving Chilled Liq-
mote mode can reset the Leaving Chilled Liquid Tem-
uid Temperature Cycling – Shutdown setpoint (See the
perature setpoint above the operator programmed Base
description in the following section of programmable
setpoint (see below). Programmable as either 10, 20,
setpoints).
30, or 40°F, with a default of 10°F, it is added to the
Leaving Chilled Liquid Temperature Setpoints Base value to create a range over which the remote de-
– Restart vice can reset the setpoint. For example, if this setpoint
is programmed for 10°F and the operator programmed
Displays the Leaving Chilled Liquid Temperature at value is 45°F, then the remote device can set the Leav-
which the chiller will restart after it has shut down to ing Chilled Liquid Temperature setpoint over the range
avoid over-cooling. By default, the chiller will restart at 45.0° to 55.0°F.
the Leaving Chilled Liquid Temperature setpoint. The
28 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Local Leaving Chilled Liquid Temperature – Leaving Chilled Liquid Temperature Cycling
Setpoint Offset – Restart
Access Level Required: OPERATOR Access Level Required: OPERATOR
This value allows the user to define the Leaving This value allows the user to specify the Leaving Chilled
Chilled Liquid Temperature that is to be maintained Liquid Temperature at which the chiller will restart af-
by the chiller. It is programmable over the range of ter a shutdown on a LEAVING CHILLED LIQUID
2
38.0°F to 70.0°F (water) or 20.0°F to 70.0°F (brine). – LOW TEMPERATURE cycling shutdown. This is
(Microboard Program Jumper J35 must be removed for done by defining an offset above the Leaving Chilled
Brine cooling applications). If Smart Freeze (see below) Liquid Temperature setpoint. It is programmable over
is enabled, the range is 36.0°F to 70.0°F (water). If Ice a range of 0°F to 60°F above the setpoint, to a maxi-
Storage is ON and wanted, the range is 20°F to 32°F mum restart value of 80°F. If Ice Storage mode is ON,
(brine). A remote device can provide an analog signal there are two different Restart setpoints employed:
(0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC)
in Analog Remote mode, or PWM signal in Digital • One is programmed and will be in effect when the
Remote mode that changes the setpoint by creating an Leaving Chilled Liquid Temperature setpoint is
offset above this base or lowest setting allowed for the less than or equal to 32.0º F.
Leaving Chilled Liquid Temperature setpoint. This off- • The other is programmed and will be in effect
set may be defined up to 10, 20, 30, or 40°F above this when the setpoint is more than 32.0ºF. Each can
base setpoint (see the Remote Leaving Chilled Liquid be programmed to a different value.
Temperature Setpoint Range description above). Addi-
tionally, a MicroGateway (in ISN Remote mode) can The chiller will automatically restart when this tem-
define the setpoint through a serial data stream. In this perature is reached. This setpoint can be used to reduce
case, the incoming setpoint is not an offset that is ap- chiller cycling by delaying the chiller restart until the
plied to this locally programmed Base setpoint value, cooling load has increased.
but rather is the setpoint value itself.
Brine Low Evaporator Cutout
Leaving Chilled Liquid Temperature Cycling Access Level Required: SERVICE
Offset - Shutdown
This value is only available in Brine mode. It allows
Access Level Required: OPERATOR the user to specify the Evaporator Pressure at which a
This value allows the user to specify the Leaving safety shutdown is initiated. Service Technicians refer
Chilled Liquid Temperature at which the chiller will to OptiView Control Center Service Instructions (Form
shut down on a LEAVING CHILLED LIQUID – LOW 160.81-M1).
TEMPERATURE cycling shutdown. This is done by
Ice Storage (On / Off)
defining an offset below the Leaving Chilled Liquid
Temperature setpoint. It is programmable over a range Access Level Required: SERVICE
of 1°F to 64°F below the setpoint, to a minimum cut-
When in Brine mode this must be turned ON or OFF
out of 36°F (water), 34°F (water with Smart Freeze
via this toggle and then the Leaving Chilled Liquid
enabled) or 16°F (brine). It establishes the minimum
Temperature setpoint is used to automatically activate
allowable temperature for the Leaving Chilled Liquid
or deactivate Ice Storage mode. Service Technicians
Temperature and prevents over-cooling of the build-
refer to OptiView Control Center Service Instructions
ing. Anytime the Leaving Chilled Liquid Temperature
(Form 160.81-M1).
setpoint is increased, the shutdown threshold is 36.0°F
(water) or 16.0°F (brine) for the next ten (10) minutes.
If Smart Freeze (see below) is enabled, the threshold is
34.0°F for the next 10 minutes. After ten (10) minutes
have elapsed, the shutdown threshold becomes the pro-
grammed setpoint value.
JOHNSON CONTROLS 29
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
30 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
SENSITIVITY SCREEN
00650VIP
JOHNSON CONTROLS 31
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
CONDENSER SCREEN
LD11548
Displays the water temperature as it leaves the Indicates whether condenser liquid pump is operating.
condenser.
Drop Leg Refrigerant Temperature
Return Condenser Liquid Temperature Displays the temperature of the refrigerant in the Drop
Displays the water temperature as it enters the Leg between the condenser and evaporator shells. Not
condenser. displayed if function disabled.
Displays the refrigerant pressure in the condenser. Displays the difference between the Condenser Refrig-
erant temperature and the Drop-Leg Refrigerant tem-
Condenser Saturation Temperature perature. The Condenser Refrigerant temperature is
represented by the Condenser Saturation temperature.
Displays the saturation temperature in the condenser.
If the Drop Leg sensor is disabled, this temperature is
Small Temperature Difference not displayed.
Displays the difference between the Condenser Refrig- Refrigerant Level Position
erant temperature and the Leaving Condenser Liquid
Displays the present position of the refrigerant level.
temperature. The Condenser Refrigerant temperature
Not displayed if function disabled on OPERATIONS
will be represented by the Condenser Saturation tem-
screen.
perature.
32 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 33
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
LD14791
Overview Programmable
This screen displays a cutaway view of the chiller con- Setpoint
denser, along with the liquid refrigerant level sensor
The level control will control the condenser refriger-
and the flow control valve. All setpoints relating to
ant level to this level. Programmable over the range of
the liquid level control are maintained on this screen.
20% to 80% (default 30%). Service Technicians refer
Through animation, the Variable Orifice position is
to OptiView Control Center Service Instructions (Form
displayed. In addition, the refrigerant flow control
160.81-M1).
valve (Variable Orifice) can be manually operated.
Valve Preset Time
Display Only
Access Level Required: SERVICE
Refrigerant Level Position
Displays the present position of the liquid level. Sets the duration of time the refrigerant level control
valve is driven closed when a start is initiated. This pre-
Refrigerant Level Control Mode sets the valve to a position held during the first 3 min-
utes of chiller run. Defines the duration of the “Start
Indicates whether the liquid level control is under
Sequence Initiated” period. Programmable over the
manual or automatic control.
range of 30 to 300 seconds (default 50 seconds). Service
Raise (LED) Technicians refer to OptiView Control Center Service
Instructions (Form 160.81-M1).
Is ON when the digital output controlling the Level
Raise contact is ON. Ramp-up Time
Is ON when the digital output controlling the Level Access Level Required: SERVICE
Lower contact is ON.
Sets the duration of the ramp that is applied to the Lev-
el Control setpoint after the first 3 minutes of chiller
run when the actual level is greater than or less than
the setpoint. Programmable over the range of 3 to 15
minutes (default 8). Service Technicians refer to Op-
tiView Control Center Service Instructions (Form
160.81-M1).
34 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
[Refrigerant Level Control] Period [Refrigerant Level Control] Rate Limit Close
(Not applicable to software version C.MLM.05.04.xxx (Not applicable to software version C.MLM.05.04.xxx
and later). and later).
Access Level Required: SERVICE Access Level Required: SERVICE
Service Technicians refer to OptiView Control Center Service Technicians refer to OptiView Control Center 2
Service Instructions (Form 160.81-M1). Service Instructions (Form 160.81-M1).
[Refrigerant Level Control] Proportional Limit Open [Refrigerant Level Control] Raise (Manual)
(Not applicable to software version C.MLM.05.04.xxx Access Level Required: SERVICE
and later).
This key puts the level control into Manual mode and
Access Level Required: SERVICE sends a RAISE command to the Variable Orifice.
Service Technicians refer to OptiView Control Center [Refrigerant Level Control] Lower (Manual)
Service Instructions (Form 160.81-M1).
Access Level Required: SERVICE
[Refrigerant Level Control] Proportional Limit This key puts the level control into Manual mode and
Close sends a LOWER command to the Variable Orifice.
(Not applicable to software version C.MLM.05.04.xxx
and later). [Refrigerant Level Control] Hold (Manual)
Access Level Required: SERVICE
Access Level Required: SERVICE
This key puts the level control into Manual mode and
Service Technicians refer to OptiView Control Center
sends a HOLD command to the Variable Orifice.
Service Instructions (Form 160.81-M1).
[Refrigerant Level Control] Auto
[Refrigerant Level Control] Rate Limit Open
Access Level Required: SERVICE
(Not applicable to software version C.MLM.05.04.xxx
and later). Returns the Level Control to Automatic mode.
Access Level Required: SERVICE Navigation
Service Technicians refer to OptiView Control Center Home
Service Instructions (Form 160.81-M1).
Access Level Required: SERVICE
Causes an instant return to the HOME screen.
JOHNSON CONTROLS 35
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
COMPRESSOR SCREEN
LD09717
36 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
This key puts the slide valve control into Manual mode Allows the Service Technician to specify the Discharge
and holds the slide valve in its present position. The Temperature at which the Liquid Injection Solenoid
slide valve will remain at this position until the Load, Valve opens to inject liquid refrigerant into the com-
Unload, or Auto key is pressed. pressor. Service Technicians refer to OptiView Control
Center Service Instructions (Form 160.81-M1).
JOHNSON CONTROLS 37
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Navigation
Home
Access Level Required: VIEW
Causes an instant return to the HOME screen.
Hot Gas
Access Level Required: SERVICE
Only available if the system uses Hot Gas Bypass and
it is enabled. Moves to the sub-screen allowing for the
setup of Hot Gas. Service Technicians refer to OptiView
Control Center Service Instructions (Form 160.81-M1).
38 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
LD09718
This screen, accessed from the COMPRESSOR screen, less than or equal to the number of degrees of this ON
displays a pictorial of the bypass line and solenoid setpoint above the Leaving Chilled Liquid Tempera-
valve location on the chiller. The Hot Gas ON and OFF ture setpoint. The ON setpoint is programmed over
setpoints are programmed on this screen and system the range of 1.0ºF to 10.0ºF (default 1.0ºF). Refer to
parameters pertinent to Hot Gas Bypass operation are OptiView Control Center Service Instructions (Form
displayed. An LED illuminates when the Hot Gas So- 160.81-M1 for an explanation of this setpoint.
lenoid is ON. If the chiller is equipped with the Hot
Gas Bypass option, operation must be enabled on the Off Setpoint
OPERATIONS screen. Access Level Required: SERVICE
Display Only The Hot Gas Bypass solenoid valve is turned OFF
when the Return Chilled Liquid Temperature increases
Return Chilled Liquid Temperature above the Leaving Chilled Liquid Temperature setpoint
Displays the temperature of the liquid as it enters the by greater than or equal to the number of degrees of
evaporator. this OFF setpoint. The OFF setpoint is programmed
over the range of 2.0 to 15.0º F (default 2.0). Refer to
Leaving Chilled Liquid Temperature OptiView Control Center Service Instructions (Form
Displays the temperature of the liquid as it leaves the 160.81-M1 for an explanation of this setpoint.
evaporator.
Navigation
Hot Gas Solenoid (LED)
Home
Indicates whether the solenoid is presently energized.
Access Level Required: SERVICE
Programmable Causes an instant return to the HOME screen.
On Setpoint
Compressor
Access Level Required: SERVICE
Access Level Required: SERVICE
The Hot Gas Bypass solenoid valve is turned ON when
Return to the COMPRESSOR screen.
the Return Chilled Liquid Temperature decreases to
JOHNSON CONTROLS 39
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
LD12825
40 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Offset Pressure (Not Displayed) shutdown on this safety each time the chiller is started.
The Offset Pressure is a calculated value that is used to Service Technicians refer to OptiView Control Center
calculate the differential pressure. The Offset Pressure Service Instructions (Form 160.81-M1 for program
is the pressure differential between the corresponding jumper positioning. This LED indicator is displayed
transducers during the first 15 seconds of Start Se- on this screen whether the oil level sensor is present
or not.
quence Initiated. This is the transducer auto-zeroing. 2
During this time the transducers will be sensing the
Condenser Saturation
same pressure and their outputs should be equal. How-
ever, due to accuracy tolerances in transducer design, Displays the saturation temperature in the condenser.
differences can exist. Therefore, to compensate for dif-
ferences between transducers and assure differential Evaporator Pressure
pressure sensing accuracy, the Offset Pressure is sub- Displays the refrigerant pressure in the evaporator.
tracted from the differential pressure. (Certain operat-
ing conditions could require the auto-zeroing to be dis- Condenser Pressure
abled. This must never be done by anyone other than a Displays the refrigerant pressure in the condenser.
qualified service technician.
Programmable
Oil Supply Solenoid (LED)
Auto Zero (Enabled / Disabled)
Indicates whether the solenoid is energized.
Access Level Required: SERVICE
Low Separator Oil
Allows the user to enable or disable the transducer
(Software version C.OPT.05.08.303 and later) auto-zeroing that is used to calculate the offset pres-
sure. (Refer to the description of the Offset Pressure).
Illuminated when there is insufficient oil level in the
Service Technicians refer to OptiView Control Center
Oil Separator. Otherwise, it is extinguished.
Service Instructions (Form 160.81-M1).
New production chillers after second quarter 2007 are
equipped with an Oil Level Sensor in the Oil Separator. Navigation
For proper oil level detection on chillers equipped with Home
this sensor, Microboard Program Jumper JP9 must be
positioned properly. For chillers not equipped with this Access Level Required: VIEW
sensor, if JP9 is not positioned properly, the chiller will Causes an instant return to the HOME screen.
JOHNSON CONTROLS 41
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
LD11550
Overview Programmable
This screen displays all information pertaining to an Local Motor Current Limit
Electro-Mechanical Starter.
Access Level Required: OPERATOR
Display Only Allows the user to specify the maximum allowed mo-
Motor Run (LED) tor current (as a percentage of FLA). When the mo-
tor current reaches this value, the slide valve will not
Illuminates when the compressor motor is being com-
be permitted to load further. If the motor current rises
manded to run.
above this value, the slide valve will unload to reduce
Motor Current % Full Load Amps the current to this value.
Displays the motor current as a percentage of the Full Pulldown Demand Limit
Load Amps (FLA) value. For the Electro-Mechanical
Access Level Required: OPERATOR
Starter this is the data returned by the CM-2 Board.
Allows the user to specify the current limit value (as a
Current Limit Setpoint percentage of FLA) to which the chiller will be limited
Displays the current limit value in use. This value could during the specified pulldown limit time. This value
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 will override the Motor Current Limit value during this
to 10VDC input in Analog Remote mode, PWM signal time period. This function is used to provide energy
in Digital Remote mode, MicroGateway interface in savings following chiller start-up.
ISN mode, or a locally programmed value.
Pulldown Demand Time
Pulldown Demand Time Left Access Level Required: OPERATOR
Displays the time remaining in the programmed
Allows the user to set a period of time for which the
pulldown period if the value is nonzero.
Pulldown Demand Limit will be in effect after the
Motor Temperature Switch (Open/Closed) chiller starts.
Displays the present position of the Motor Temperature
Switch. The normal position is closed. It is open when
there is a high temperature condition.
42 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Navigation
Home
Access Level Required: VIEW
Causes an instant return to the HOME screen.
2
Ground Fault Protection
Access Level Required: ADMIN
Moves to the GROUND FAULT PROTECTION
screen allowing clearing of a “Motor – Ground Fault”
safety shutdown. Refer to description of “Motor–
Ground Fault” in this manual and reset procedure in
OptiView Control Center Service Instructions (Form
160.81-M1).
JOHNSON CONTROLS 43
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
00654VIP
Figure 14 - MOD “B” SOLID STATE STARTER SCREEN
Overview kW Hours
This screen displays information pertaining to the Mod Displays the cumulative amount of Kilowatts used
“B” Solid State Starter. over time.
Input Power
Displays the Kilowatts measured by the Solid State
Starter.
44 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Allows the user to select specific line voltage range for Causes an instant return to the HOME screen.
voltage checking. When not disabled, this line volt-
Ground Fault Protection
age range is used to determine a low line and high line
voltage threshold for initiating a shutdown. Service Access Level Required: ADMIN
Technicians refer to OptiView Control Center Service
Moves to the GROUND FAULT PROTECTION
Instructions (Form 160.81-M1).
screen allowing clearing of a “Motor – Ground Fault”
safety shutdown. Refer to description of “Motor–
Ground Fault” in this manual and reset procedure in
OptiView Control Center Service Instructions (Form
160.81-M1).
JOHNSON CONTROLS 45
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
LD11549
46 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Navigation Motor
Home Access Level Required: ADMIN
Access Level required: ADMIN Return to the MOTOR screen.
Causes an instant return to the HOME screen.
2
JOHNSON CONTROLS 47
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
SETPOINTS SCREEN
LD12826
48 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Temperature setpoint above the operator programmed minutes. If Smart Freeze is enabled, the threshold is
Base setpoint (see below). Programmable as either 10, 34.0°F for the next 10 minutes. After ten (10) minutes
20, 30 or 40°F, with a default of 10°F, it is added to the have elapsed, the shutdown threshold becomes the pro-
Base value to create a range over which the remote de- grammed setpoint value.
vice can reset the setpoint. For example, if this setpoint
is programmed for 10°F and the operator programmed Leaving Chilled Liquid Temperature Cycling
value is 45°F, then the remote device can set the Leav- Offset - Restart
2
ing Chilled Liquid Temperature setpoint over the range Access Level Required: OPERATOR
45.0° to 55.0°F.
This value allows the user to specify the Leaving Chilled
Local Leaving Chilled Liquid Temperature Liquid Temperature at which the chiller will restart af-
Setpoint ter a shutdown on a LEAVING CHILLED LIQUID
Access Level Required: OPERATOR – LOW TEMPERATURE cycling shutdown. This is
done by defining an offset above the Leaving Chilled
This value allows the user to define the Leaving Liquid Temperature setpoint. It is programmable over a
Chilled Liquid Temperature that is to be maintained by range of 0°F to 70°F above the setpoint, to a maximum
the chiller. It is programmable over the range of 38.0°F restart value of 80°F. The chiller will automatically re-
to 70.0°F (water) or 20.0°F to 70.0°F (brine). If Smart start when this temperature is reached. This setpoint
Freeze is enabled, the range is 36.0°F to 70.0°F (wa- can be used to reduce chiller cycling by delaying the
ter). A remote device can provide an analog signal (0 to chiller restart until the cooling load has increased.
20mA, 4 to 20mA, 0 to 10VDC, or 2 to 10VDC) in An-
alog Remote mode, or PWM signal in Digital Remote Remote Analog Input Range
mode that changes the setpoint by creating an offset Access Level Required: OPERATOR
above the operator programmed Base Leaving Chilled
Liquid Temperature setpoint. This offset may be de- This setpoint defines, for the Control Center, the re-
fined up to 10.0°F, 20.0°F, 30.0°F, or 40.0°F above the mote signal range applied for remote reset of the Leav-
Base setpoint (see the Remote Leaving Chilled Liquid ing Chilled Liquid Temperature setpoint and Current
Temperature setpoint range description above). Addi- Limit setpoint in Analog Remote mode. If the remote
tionally, a remote MicroGateway device (in ISN Re- signal is 0 to 10VDC or 0 to 20mA, this setpoint must
mote mode) can define the setpoint through a serial be programmed for 0 to 10VDC. If the remote signal
data stream. In this case, the incoming setpoint is not is 2 to 10VDC or 4 to 20mA, this setpoint must be pro-
an offset that is applied to the locally programmed Base grammed for 2 to 10VDC.
setpoint value, but rather is the setpoint value itself.
Local Motor Current Limit
Leaving Chilled Liquid Temperature Cycling Access Level Required: OPERATOR
Offset - Shutdown
Allows the user to specify the maximum allowed mo-
Access Level Required: OPERATOR
tor current (as a percentage of FLA). When the mo-
This value allows the user to specify the Leaving tor current reaches this value, the slide valve will not
Chilled Liquid Temperature at which the chiller will be permitted to load further. If the motor current rises
shut down on a LEAVING CHILLED LIQUID – above this value, the slide valve will unload to reduce
LOW TEMPERATURE cycling shutdown. This is the current to this value.
done by defining an offset below the Leaving Chilled
Liquid Temperature setpoint. It is programmable over Pulldown Demand Limit
a range of 1°F to 64°F below the setpoint, to a mini- Access Level Required: OPERATOR
mum cutout of 36°F (water), 34°F (water with Smart
Freeze enabled) or 16°F (brine). It establishes the Allows the user to specify the current limit value (as
minimum allowed temperature for the Leaving Chilled a percentage of Full Load Amps) to which the chiller
Liquid Temperature and prevents over-cooling of the will be limited during the specified pulldown limit
building. Anytime the Leaving Chilled Liquid Tem- time. This value will override the Motor Current Limit
perature setpoint is increased, the shutdown threshold value during this time period. This function is used to
is 36.0°F (water) or 16.0°F (brine) for the next ten (10) provide energy savings following chiller startup.
JOHNSON CONTROLS 49
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Pulldown Demand Time er Full Load Amps continuously for the programmed
Access Level Required: OPERATOR time, a safety shutdown is performed and “105% Mo-
tor Current Overload” is displayed.
Allows the user to set a period of time for which the
Pulldown Demand Limit will be in effect after the Print
chiller starts. Access Level Required: VIEW
105% Motor Current Time Generates setpoints print report.
(Software version C.OPT.05.07.xxx (and later)
Navigation
Access Level Required: OPERATOR
Home
Allows the user to set the duration of the software 105% Access Level Required: VIEW
FLA motor current overload timer. Adjustable over the
range of 12(default) to 40 seconds (in 1 second incre- Causes an instant return to the HOME screen.
ments). It should not be set to a value other than the
Setup
default value unless advised by the Johnson Controls.
This overload protection is in addition to that which Access Level Required: VIEW
is provided by the CM-2 Board (electro mechanical
Moves to the sub-screen allowing setup of general sys-
starters) or the Logic/Trigger Board of the Solid State
tem parameters.
Starter. If the motor current exceeds 105% of the Chill-
50 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
SETUP SCREEN
LD09721
Power Failure Restart Allows the user to specify the present time. This value
Displays Manual or Automatic is critical to logging system shutdowns accurately and
for utilizing the scheduling capabilities. When prompt-
Liquid Type ed to enter a time value, the user must enter the hour
and minute desired (using leading zeroes as necessary).
Displays Water or Brine
JOHNSON CONTROLS 51
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
If the chiller is presently set to 24-hour mode, the time Motor Drive Type
must be entered in the 24-hour format. Otherwise, the Access Level Required: SERVICE
user must also select AM or PM for the entered time. If
out of range, the user is prompted for the information Allows a Service Technician to enter the applied com-
again. At this point the user may retry the time entry, or pressor motor type as either Electro - Mechanical (EM)
cancel the programming attempt. or Solid State Starter (SSS – Mod B). Service Tech-
nicians refer to OptiView Control Center Service In-
Clock (Enabled / Disabled) structions (Form 160.81-M1).
Access Level Required: OPERATOR
Anti-Recycle
Allows the user to enable or disable the real-time clock Access Level Required: SERVICE
in order to conserve battery life. The clock will be
disabled during manufacturing and must be enabled at Allows a Service Technician to Enable or Disable the
system commissioning. In addition, when preparing anti-recycle timer. Service Technicians refer to OptiV-
for prolonged shutdown the clock should once again be iew Control Center Service Instructions (Form 160.81-
disabled. M1).
Used to enter the following setpoints. Pressing this key Moves to the sub-screen allowing definition of the
places a green selection box around the first changeable chiller operation schedule.
setpoint. The access level determines which setpoints
can be changed. Use the ▲ and ▼ keys to place the Diagnostics
selection box around the desired setpoint. With the Access Level Required: SERVICE
setpoint selected, press the ENTER (√) key. A dialog
Moves to the sub-screen allowing limited diagnostic
box appears with the range of settings.
capability while operating. Refer to OptiView Control
Chilled Liquid Pump Operation Center Service Instructions (Form 160.81-M1).
Access Level Required: SERVICE Comms
Allows a Service Technician to select chilled liquid Access Level Required: VIEW
pump control contacts (I/O Board TB2-44/45) opera-
Moves to the sub-screen allowing configuration of sys-
tion as either Standard or Enhanced. Service Techni-
tem communications.
cians refer to OptiView Control Center Service In-
structions (Form 160.81-M1).
52 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Printer Operations
Access Level Required: VIEW Access Level Required: VIEW
Moves to the sub-screen allowing configuration and Moves to the sub-screen displaying operating param-
control of printer functions. eters of the chiller system.
JOHNSON CONTROLS 53
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
SCHEDULE SCREEN
00232VIP
Figure 18 - SCHEDULE SCREEN
Places a selection box around a start time for a given Return to the previous setup screen.
day. Use ◄, ►,▲ or ▼ cursor arrows to place the box
around the desired start or stop time for a given day.
JOHNSON CONTROLS 55
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
USER SCREEN
00343VIP
Each Custom User value is not linked to a specific Custom User ID (4)
button. Instead, the Change button is pressed which Access Level Required: SERVICE
enables the cursor arrows which are used to highlight
the Custom User parameter the user wishes to modify. This allows the user to specify up to four (4) Custom
At this point the ‘√’ (Check) button is pressed and the User ID values. Each User ID will then require a cor-
value may be entered. responding password and User Level. A User ID can
be defined for various maintenance personnel. Service
Display Only Technicians refer to OptiView Control Center Service
None Instructions (Form 160.81-M1).
56 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 57
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
COMMS SCREEN
00470VIP
58 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
Define the number of parity bits with which the panel Access Level Required: VIEW
shall communicate through the modem port. Causes an instant return to the HOME screen.
Setup
Access Level Required: VIEW
Return to the SETUP screen.
JOHNSON CONTROLS 59
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
PRINTER SCREEN
00235VIP
00236VIP
Factory defined model number of the chiller system. Access Level Required: SERVICE
Define the date at which the chiller was commis-
Panel Serial Number
sioned.
Factory defined serial number for the micropanel.
Job Name and Location
Chiller Serial Number
Access Level Required: SERVICE
Factory defined serial number for the chiller system.
Factory defined job name and location the chiller is
YORK Order Number destined for.
Factory defined order number under which the chiller Print
was sold.
Access Level Required: VIEW
System Information
Generates a Sales Order print report.
Factory defined conditions for which the chiller was
originally rated and sold.
JOHNSON CONTROLS 61
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Navigation Setup
Home Access Level Required: VIEW
Access Level Required: VIEW Return to the SETUP screen.
Causes an instant return to the HOME screen.
62 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
OPERATIONS SCREEN
LD09720
JOHNSON CONTROLS 63
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Hot Gas Bypass (Enabled / Disabled) Therefore, the actual type installed must be entered to
Access Level Required: SERVICE allow the program to read the correct input. Service
Technicians refer to OptiView Control Center Service
Enables and Disables the optional Hot Gas Bypass Instructions (Form 160.81-M1).
Control Feature.
Navigation
Flow Switch
Home
(Software version C.MLM.05.04.xxx and later)
Access Level Required: VIEW
Access Level Required: SERVICE
Causes an instant return to the HOME screen.
Used to enter the applicable Flow Switch type. Style
B and later chillers are equipped with Thermal – Type Setup
flow sensors. The referenced software supports either Access Level Required: VIEW
the Thermal-Type or Paddle-Type sensor. The differ-
ent types connect to different control center inputs. Return to the SETUP screen.
64 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
HISTORY SCREEN
00656VIP
This window displays the date and time and the de- Causes an instant return to the HOME screen.
scription of the last safety or cycling shutdown while
the system was running.
JOHNSON CONTROLS 65
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
66 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00655VIP
JOHNSON CONTROLS 67
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
00657VIP
Overview Programmable
This screen displays a listing of the last 75 setpoint Log Entry
changes. They are listed and numbered in reverse order
Access Level Required: SERVICE
in which they were changed, with the most recent listed
as number 1. Multiple pages are necessary to display Allows the user to select a particular setpoint change
all 75 changes. Not all setpoints are logged. Service for detail viewing.
Technicians refer to list in OptiView Control Center
Service Instructions (Form 160.81-M1). Print
The details of any setpoint change can be viewed by Access Level Required: SERVICE
navigating to a subscreen that displays the date and Generates a detailed report of all setpoint changes list-
time of the change, Access Level and User ID used to ed in the setpoint change log.
make the change, the old setpoint value and the new
setpoint value. Page Up
Display Only Access Level Required: SERVICE
68 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 69
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
00658VIP
70 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00428VIP
Overview Navigation
This screen allows up to 10 Service Technician select- Home
ed parameters to be displayed. These parameters are
Access Level Required: VIEW
selected from a list on the CUSTOM VIEW SETUP
screen. This allows the Service Technician to display Causes an instant return to the HOME screen.
parameters pertinent to a particular problem during
troubleshooting. At completion of the service call, the History
display can be cleared or the parameters can be left Access Level Required: VIEW
there for monitoring by operations personnel.
Causes an instant return to the HISTORY screen.
Display Only
None Setup
Access Level Required: OPERATOR
Programmable
Causes a jump to the sub-screen that allows selection
Print of the parameters to be displayed.
Access Level Required: VIEW
This generates a listing of the parameters displayed on
this screen.
JOHNSON CONTROLS 71
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
00241VIP
Overview
This screen allows the Service Technician to select up key places a green colored selection box around Cus-
to 10 parameters for display on the CUSTOM SETUP tom Slot 1. If it is desired to change an already entered
screen. parameter, use the 5 and 6 keys to place the selection
box around the slot number to be changed. With the
Display Only selection box around the slot number to be changed or
entered, press the ENTER (√) key. A dialog box is dis-
Slot Numbers
played permitting data entry. Using the numeric key-
Lists the available parameters that can be displayed. pad keys, enter the desired slot number and press the
The desired parameters for display are selected from ENTER (√) key.
this list.
Custom Slot (1-10)
Programmable
Access Level Required: SERVICE
Page Up
Use the SELECT key and numeric keypad keys as
Access Level Required: SERVICE described above and enter the slot number from Slot
Scroll up through list of available parameters. Numbers list. Setting the Slot number to zero clears the
display of this slot number.
Page Down
Navigation
Access Level Required: SERVICE
Home
Scroll down through list of available parameters.
Access Level Required: SERVICE
Select Causes a return to the HOME screen.
Access Level Required: SERVICE
Custom View
First use the Page Up and Page Down keys to scroll
through the Slot Numbers list and note the number of Access Level Required: SERVICE
the parameter(s) to be displayed. Pressing the SELECT Causes a return to the CUSTOM VIEW screen.
72 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
TRENDING SCREEN
00472VIP
Overview
As many as six operator selected parameters can be There are three types of charts that can be created:
plotted in an X/Y graph format. The X-Axis is scaled
per the selected Data Collection Interval and displayed • One Screen
in a time of day or elapsed time format, as selected • Continuous
with the X-AXIS toggle key. The Y-Axis is scaled for
each parameter per the selected minimum and maxi- • Triggered
mum value for each parameter. Analog parameters are When plotting reaches the end of the X-axis, if One
scaled in pressure, temperature, volts, amps, hertz or Screen is selected, trending stops and data is frozen. If
time. Digital ON/OFF parameters are scaled as zero Continuous is selected, the oldest data is dropped from
(OFF) and one (ON). Only one Y-Axis label is dis- the left-hand side of the graph at the next collection
played at a time. The Y-AXIS toggle Key is used to interval. Thereafter, the oldest data is dropped from the
toggle the Y-Axis labels through the different param- left hand-side of the graph at each data collection in-
eters. The Y-Axis label that is being displayed is identi- terval. If Triggered is selected, data collection can be
fied at the top of the graph. The DATA SELECT key is set to start or stop based upon the selected Trigger Ac-
used to display all trended Data Points simultaneously tion (Start or Stop). If Start is selected, data collection
or select a single Data Point for display. For identifi- will not begin until the Triggers have been satisfied and
cation, each plotted parameter and associated Y-Axis any selected Trigger Delay has elapsed. Data collection
labeling is color coordinated. will stop at the completion of one screen of data as with
the One Screen. If Stop is selected, data collection will
The parameters are sampled at the selected Data Col-
not stop until the Triggers have been satisfied and any
lection Interval and plotted using 450 data points across
selected Trigger Delay has elapsed.
the X-Axis. If the actual value of the sampled param-
eter is less than the Y-Axis label minimum for that If a power failure occurs while the trending is running,
parameter, the value will be plotted at the minimum the trending is stopped. Upon restoration of power,
value. Similarly, if the actual value is greater than the the last screen of data that was collected will be dis-
Y-Axis label maximum for that parameter, the value played on the trending screen. The START key must be
will be plotted at the maximum value. pressed to initiate a new TREND screen.
JOHNSON CONTROLS 73
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Stop Home
Access Level Required: OPERATOR Access Level Required: VIEW
Pressing this key stops the trending. The trend data is Causes a return to the HOME screen.
frozen on the display until another graph is started with
the START key. The Stop key is only available if trend- Trend Setup
ing is running. Access Level Required: OPERATOR
74 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00473VIP
JOHNSON CONTROLS 75
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Triggers
Access Level Required: OPERATOR
Causes a jump to the ADVANCED TREND SETUP
screen, where the start/stop Triggers can be setup. Only
displayed if Triggered has been selected as Chart Type.
76 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00474VIP
Overview
The desired data collection start/stop triggers are setup Entry fields are as follows:
on this screen. The trend data collection can be set to
start or stop based upon the status of up to two selected If Primary Trigger
Triggers. The Triggers can consist of digital events or Is Primary Operator Primary Test
analog parameters compared to thresholds. The Trig-
gers can be used individually or in combination. The Primary to Secondary Operator
digital and analog parameters are selected from the
COMMON SLOTS screen (or Master Slot Numbers
Secondary Trigger
List in this book).
Is Secondary Operator Secondary Test
The parameter selected as the Primary Trigger is com-
pared to a value selected as the Primary Test, using the then Trigger Action the data collection
Primary Operator as a comparator. If it is evaluated as
true, then the data collection is started or stopped (af- with a delay of Trigger Delay
ter any selected Trigger Delay) per the selected Trigger
Action.
After the desired Triggers are set, the START key on
A Secondary Trigger can be evaluated with the Prima- the TREND screen must be manually pressed before
ry Trigger to start/stop data collection. The Primary to the triggers will be evaluated. While waiting for the
Secondary Operator is used to define the Trigger com- triggers to start or stop data collection, a status message
binations required to be true to start/stop data collec- is displayed in the upper right corner of the TREND
tion. The Secondary Trigger is setup and evaluated the screen describing the pending action.
same as the Primary Trigger.
JOHNSON CONTROLS 77
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
Selects the first parameter to be evaluated. Selection Data collection will start/stop (as selected with Trigger
is made from the Slot Numbers listing on the TREND Action) when:
COMMON SLOTS screen or the Master Slot Numbers
• AND is selected, with both Primary and Second-
List in this book. Setting this slot number to zero dis-
ary true.
ables the Primary Trigger.
• OR is selected, with either Primary or Secondary
Primary Operator (or both) true.
Access Level Required: OPERATOR • XOR is selected, with either Primary or Second-
Selects the comparator for the Primary Trigger’s rela- ary (but not both) true.
tionship to the Primary Test. If the Primary Trigger is
Secondary Trigger
an analog value, selections are: <, <=, =, =>, >. If the
Primary Trigger is a digital event, selections are: Equal Access Level Required: OPERATOR
To, Not Equal To.
Selects the second parameter to be evaluated. Selection
Primary Test is made from the Slot Numbers listing on the TREND
COMMON SLOTS screen or the Master Slot Numbers
Access Level Required: OPERATOR List in this book. Setting this slot number to zero dis-
Selects the value or condition that the Primary Trig- ables the Secondary Trigger.
ger is compared to. Selection ranges from the Primary
Secondary Operator
Trigger minimum value to the Primary Trigger maxi-
mum value. Access Level required: OPERATOR
Trigger Action Selects the comparator for the Secondary Trigger’s re-
lationship to the Secondary Test. If the Secondary trig-
Access Level Required: OPERATOR ger is an Analog value, selections are: <, <=, =, =>, >.
Selects whether the trend data collection will Start or If the Secondary Trigger is a digital event, selections
Stop when the Trigger comparisons are true. If set to are Equal To or Not Equal To.
Start, data collection will stop after one screen of data
Secondary Test
is collected.
Access Level Required: OPERATOR
Trigger Delay
Selects the value or condition that the Secondary Trig-
Access Level Required: OPERATOR ger is compared to. Selection ranges from the Secondary
Allows the data collection start or stop to be delayed Trigger minimum to the Secondary Trigger maximum.
after the Triggers evaluate as true. The delay is select-
Navigation
able from 1 to 864000 seconds (10 days). Display is
in days, hours, minutes and seconds. The delay timer Home
begins when the triggers evaluate as true. If the Trigger Access Level Required: VIEW
Action is set to Start, data collection will begin after
the triggers evaluate as true and the delay timer has Causes an instant return to the HOME screen.
elapsed. If the Trigger Action is set to Stop, data col-
lection will stop after the Triggers evaluate as true and Trend Setup
the delay timer has elapsed. Access Level Required: OPERATOR
Causes an instant return to the TREND SETUP screen.
78 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
00244VIP
Overview Page Up
This screen displays the slot numbers of the commonly Access Level Required: OPERATOR
monitored parameters. The slot numbers for the re-
mainder of the available parameters are listed on the Scroll up in the displayed data.
Master Slot Numbers List that follows.
Print
From these lists, select up to six parameters to be trend- Access Level Required: OPERATOR
ed. Return to the TREND SETUP screen and enter the
parameters Slot Numbers into Data Points 1 through 6. Generates a list of the slot numbers of the available
parameters.
Display Only
Navigation
Slot Numbers
Home
These are the slot numbers of the most commonly used
parameters. Access Level Required: VIEW
Causes an instant return to the HOME screen.
Programmable
Page Down Trend Setup
Access Level Required: OPERATOR Access Level Required: OPERATOR
Scroll down in the displayed data. Causes a return to the TREND SETUP screen.
JOHNSON CONTROLS 79
Optiview Control Center
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
80 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 2 - OPTIVIEW™ CONTROL CENTER
ISSUE DATE 3/24/2011
SLOT SLOT
DESCRIPTION DESCRIPTION
NO. NO.
2308 Motor: Current Limit Local Setpoint 2585 Serial SSS: Is Serial Communications OK
2309 Motor: Current Limit Remote Analog Setpoint 2586 Serial SSS: Panel to SSS Comm Errors
2310 Motor: Current Limit Remote ISN Setpoint 2587 Serial SSS: to Panel Comm Errors 2
2311 Motor: Current Limit Remote Modem Setpoint 8206 Refrigerant Level: Position
2312 Motor: Current Limit Selected Setpoint
8207 Refrigerant Level: Is Valve Closing
2313 Motor: Pulldown Demand Time Remaining
2314 Motor: Pulldown Demand Limit Setpoint 8208 Refrigerant Level: Is Valve Opening
2315 Motor: Pulldown Demand Time Setpoint 16401 Oil: Pressure
2316 Motor: Anti‑Recycle Time Remaining 16402 Oil: Differential Pressure
2317 Motor: Current Limit Remote Digital Setpoint (Oil Pressure – Evaporator Pressure)
JOHNSON CONTROLS 81
SECTION 2 - OPTIVIEW™ CONTROL CENTER FORM 160.81-O1 (311)
ISSUE DATE 3/18/2011
82 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
• Warning messages - Yellow The chiller is running under the condition described in
the Details Line of the Status Bar.
• Cycling Shutdown messages - Orange
START INHIBIT
• Safety Shutdown messages - Red
The chiller is prevented from being started due to the
Note that there are three types of shutdowns: reason displayed on the Details Line of the Status Bar.
• Cycling Shutdown - If the chiller shuts down on
SLIDE VALVE UNLOADING BEFORE SHUTDOWN
a cycling shutdown, it will automatically restart
when the condition that caused the shutdown no To prevent an overcurrent condition when starting the
longer exists. compressor, the slide valve should be in the unloaded
position. While the unload signal is being applied,
• Safety Shutdown - These shutdowns require the
“Slide Valve Unloading Before Shutdown” is dis-
operator to perform a manual reset at the keypad.
played. To assist the slide valve in returning to the un-
• Normal Shutdown - These shutdowns occur from loaded position, an unload signal is applied to it while
a properly requested or scheduled shutdown. The the compressor is still running prior to shutting down
event that caused the shutdown is displayed on the on the following shutdowns:
Details Line.
• MULTIUNIT CYCLING - CONTACTS OPEN
STATUS MESSAGES • SYSTEM CYCLING - CONTACTS OPEN
SYSTEM READY TO START • REMOTE STOP
The chiller is shut down but will start upon receipt of a • LEAVING CHILLED LIQUID - LOW
Local or Remote start signal. TEMPERATURE
CYCLING SHUTDOWN – AUTO RESTART • CONTROL PANEL - SCHEDULE
The chiller is shut down on a cycling shutdown. The The duration of the unload signal applied depends on
cause of the shutdown is still in effect and is displayed the software version:
on the Details Line of the Status Bar. The chiller will
automatically restart when the Cycling condition clears. • With software version C.OPT.05.08.303 (and ear-
lier), it is 60 seconds.
SAFETY SHUTDOWN – MANUAL RESTART
• With software version C.OPT.05.09.303 (and later),
The chiller is shut down on a safety shutdown. The the duration is determined by the motor current
cause of the shutdown is still in effect and is displayed when the shutdown command is received as follows:
on the Details Line of the Status Bar. The chiller can
be started after the Safety condition clears and the op- - 100% FLA or above equals 30 seconds.
erator moves the COMPRESSOR switch to the Stop- - 7 5% FLA and below equals 5 seconds, lin-
Reset (O) position. ear between 75% and 100% FLA.
JOHNSON CONTROLS 83
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
84 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
START INHIBIT MESSAGES was detected during the initialization process that oc-
curs when power is applied to the Control Center. Due
ANTI-RECYCLE XXMIN/SEC to this failure, any or all of the programmed setpoints
The chiller is inhibited from starting because the 30 could have been corrupted. Therefore, all setpoints have
minute anti-recycle time has not yet elapsed. Time re- been automatically changed to their Default values. All
maining is displayed. setpoints will have to be programmed to their desired
values. This message will clear when the WARNING
MOTOR CURRENT >15% FLA RESET key is pressed in OPERATOR (or higher) ac-
The Control center has detected a compressor motor cess mode.
current of a magnitude that is more than 15% of the
chiller Full Load Amps for 10 continuous seconds, WARNING – CONDENSER – HIGH PRESSURE LIMIT 3
while the chiller is shutdown. As long as this condi- The Condenser Pressure exceeds the High Pressure
tion exists, the oil pump is turned ON. This is gener- Warning setpoint threshold, programmed by a Service
ally indicative of a failure of the motor starter, Control Technician logged in at SERVICE access level. While
Center start circuits or motor current feedback circuits. this condition is in effect, the slide valve is inhibited
After motor current is no longer detected, a SYSTEM from further loading. This message automatically
LOCKOUT DELAY is performed. The chiller can be clears and the slide valve is permitted to load when
started after motor current is no longer detected, the the Condenser pressure decreases to 5 PSIG below the
SYSTEM LOCKOUT DELAY has completed and the setpoint.
COMPRESSOR switch is placed in the Stop-Reset (O)
position. WARNING – EVAPORATOR – LOW PRESSURE
LIMIT
LCSSS - HIGH TEMPERATURE PHASE X - STOPPED The Evaporator pressure has decreased to the Warning
(Mod. “B” Solid State Starter only) threshold. This threshold is fixed in Water cooling ap-
plications. In Brine cooling applications, the threshold
The chiller is stopped and the Liquid Cooled Solid is a fixed amount above the programmable safety shut-
State Starter Logic/Trigger Board has detected that the down threshold. The Safety threshold in Brine applica-
temperature of phase A, B, or C (designated as X in this tions is determined by the Brine solution and is deter-
message) Silicon Controlled Rectifier (SCR) module mined by the Johnson Controls. While this condition is
is more than 110ºF. The starter cooling pump will run in effect, the slide valve is inhibited from further load-
and the chiller will be inhibited from starting until the ing. This message automatically clears and the Vanes
temperature decreases to less than109ºF. are permitted to open when the Evaporator pressure
increases to the reset value.
WARNING MESSAGES
WARNING RESET THRESHOLD
WARNING – REAL TIME CLOCK FAILURE THRESHOLD (PSIG) (PSIG)
During the initialization process that occurs when Water Brine Water Brine
power is applied to the Control Center, test data is writ- +2.0 more than +3.0 more than
R134a 27.0 28.0
ten to a location in the BRAM battery backed memory Safety setpoint Safety setpoint
device (IC location U52 on Microboard). This data is
then read from the BRAM and compared to the test WARNING – FREEZE THREAT FROM OPERATING
data. If the read data is not the same as that which was CHILLER
written to the device, it is assumed the BRAM and Real
Displayed after the chiller has been shutdown for at
time Clock operation is defective and this message is
least the amount of time programmed as the Freeze
displayed. The BRAM should be replaced by a quali-
Warning Bypass setpoint (programmed by a Service
fied Service Technician. This message automatically
Technician logged in at SERVICE access level) and
clears when the BRAM problem has been solved.
the Condenser Saturation Temperature decreases to
WARNING – SETPOINT OVERRIDE less than 28ºF.
A blank BRAM battery-backed memory device (IC lo- When the temperature increases to more than 28ºF, the
cation U52 on Microboard) or a failure of this device warning message clears.
JOHNSON CONTROLS 85
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
The Discharge Pressure is more than 185.3 PSIG while (Software version C.OPT.05.09.303 and later)
the chiller is running. While this condition is in effect, This warning is set when the chiller is running, the lev-
an unload signal is applied to the slide valve until the el control Valve Preset/Ramp-up Time is complete and
pressure is less than 175.3 PSIG, whereupon this warn- the condenser refrigerant level is less than 10% for 15
ing message automatically clears. continuous minutes. This warning is cleared when the
chiller is not running or the condenser refrigerant level
WARNING – LOW DISCHARGE SUPERHEAT LIMIT
increases to greater than 15%.
If the chiller has been running for at least 3 minutes and
the Discharge Superheat is less than or equal to 10.0ºF WARNING – CONDENSER – UNSTABLE REFRIG-
(R134a), this message is displayed and the slide valve ERANT LEVEL
is inhibited from loading. If this condition exists con- (Software version C.OPT.05.09.303 and later)
tinuously for 10 seconds, the Slide valve is driven with
0.5 second unload pulses, applied every 3.5 seconds This warning tracks the amount of time the refrigerant
until the Discharge Superheat is more than or equal to level is more than 20% below or 20% above the Ef-
12.0ºF (R134a), whereupon this message is replaced fective Refrigerant Level setpoint. This warning is set
with “WARNING – LOW DISCHARGE SUPER- when the accumulated time is greater than 10 minutes
HEAT DETECTED”. within a 20 minute window. The 20 minute window be-
gins at the first detection of the level outside of the plus
WARNING – LOW DISCHARGE SUPERHEAT or minus 20% limit, after the chiller has been running
DETECTED for at least 15 minutes. As soon as 10 minutes have ac-
Refer to “WARNING - LOW DISCHARGE SUPER- cumulated with the level outside the range, the warning
HEAT LIMIT” message above. This message will is set and the window is reset. When the first 20 minute
clear when the WARNING RESET key is pressed in window times out, the next is started, and so on until
OPERATOR (or higher) access level. the warning is released. The warning is released when
the condenser refrigerant level accumulated time does
WARNING – OIL - DIRTY FILTER not cause the warning to be set by the end by the end
Displayed if the Oil Filter Differential Pressure exceeds of the 20 minute window. Once released, the next win-
the following threshold for 8 continuous seconds: 18 dow will start with the detection of the level outside
PSID (software version C.OPT.05.09.303 and later); the range.
20 PSID (software version C.MLM.05.03.303 and ear-
lier); 28 PSID (software version C.OPT.05.04.303 to ROUTINE SHUTDOWN MESSAGES
C.OPT.05.08.303). This message automatically clears REMOTE STOP
when the condition clears.
A shutdown command has been received from a re-
WARNING – OIL - HIGH TEMPERATURE mote device. Remote Stop commands can be received
Displayed when the oil temperature rises to 165ºF. This
message automatically clears when the temperature de-
creases to less than or equal to 160ºF.
86 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
in Digital Remote mode via I/O Board TB4-7/8 or in LEAVING CHILLED LIQUID –LOW TEMPERATURE
ISN (Integrated Systems Network) Remote mode via The Leaving Chilled Liquid Temperature has decreased
the MicroGateway serial communications. If the chiller to the programmed Shutdown Temperature setpoint. If
is running when this occurs, the Pre-rotation Vanes are the chiller is running when this occurs, the slide valve
driven fully closed prior to shutting down the chiller. is fully unloaded prior to shutting down the chiller. The
LOCAL STOP
chiller will automatically restart when the tempera-
ture increases to the programmed Restart Temperature
A local shutdown command has been received by plac- setpoint.
ing the Keypad Start-Run-Stop/Reset Switch in the
stop (O) position. LEAVING CHILLED LIQUID – FLOW SWITCH OPEN
The Chilled Liquid Flow Switch has remained open 3
PLACE COMPRESSOR SWITCH IN RUN POSITION
for 2 continuous seconds while the chiller was running
The Control Center is in either Digital or ISN (Inte- or failed to close during the Start Sequence Initiated
grated Systems Network) Remote mode. The operator period. The chiller will automatically restart when the
is requested to place the COMPRESSOR switch in the Flow Switch closes.
RUN position. The Control Center will not accept a
Remote start/stop command unless the switch is in the CONDENSER – FLOW SWITCH OPEN
RUN position.
The Condenser Water Flow Switch has remained open
CYCLING SHUTDOWN MESSAGES for 2 continuous seconds while the chiller was run-
ning. With software version C.MLM.05.06.xxx (and
MULTIUNIT CYCLING – CONTACTS OPEN later) or C.OPT.05.06.xxx (and later), this check is
The Multi-Unit Cycling contacts connected to I/O bypassed until the PUMP DELAY setpoint timer has
Board TB4-9, have opened to initiate a cycling shut- been elapsed for at least 30 seconds. With all previous
down. If the chiller is running when this occurs, the software, this check is bypassed for the first 30 seconds
slide valve is fully unloaded prior to shutting down the of “System Run”. The chiller will automatically restart
chiller. The chiller will automatically restart when the when the Flow Switch closes.
contacts close. The CM-2 Current module (Electro-Mechanical Start-
er applications) has shutdown the chiller. When detect-
SYSTEM CYCLING – CONTACTS OPEN ing a fault condition that places the starter or motor at
The System Cycling contacts connected to I/O Board risk, these devices open the Motor Controller contacts
TB4-13, have opened to initiate a cycling shutdown. If “CM” (located on the respective device and connected
the chiller is running when this occurs, the slide valve between TB6-16 and TB6-53 in the Control Center) to
is fully unloaded prior to shutting down the chiller. initiate a shutdown. Since there are several different
The chiller will automatically restart when the contacts faults that are monitored, LEDs on the respective de-
close. vice illuminate to identify the specific fault that has oc-
curred. The chiller will automatically restart when the
CONTROL PANEL – POWER FAILURE Motor Controller contacts close. On some shutdowns,
A Control Power failure has occurred. If the power the respective device automatically closes the contacts
failure occurred while the chiller was running, it will when the fault condition clears. Other shutdowns re-
automatically restart when power is restored. This quire the operator to perform a Manual Reset at the
message can indicate a Cycling (auto-restart after pow- respective device.
er failure) or Safety (manual restart after power failure)
shutdown, depending upon Control Center configura- MANUAL AUTOMATIC RESET
DEVICE
tion. It indicates a cycling shutdown when displayed RESET FAULT FAULT
in orange characters; safety shutdown when displayed CM-2 Module Overload None
in red characters. The Control Center is configured for
auto-restart or manual restart after power failure by a
qualified Service Technician following instructions in
OptiView Control Center Service Instructions (Form
160.81-M1).
JOHNSON CONTROLS 87
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
MOTOR CONTROLLER – LOSS OF CURRENT message, if the Liquid Cooled Solid State Starter does
The compressor motor current decreased to 10% Full not receive a response from the control center after 10
Load Amps (FLA) for 25 continuous seconds while the consecutive attempts to communicate with the Control
chiller was running. This could be caused by the start- Center after initialization has been successfully com-
er de-energizing during run or a defect in the motor pleted. The Control Center attempts to establish com-
current feedback circuitry to the Control Center. The munications until successful.
chiller will automatically restart at the completion of LCSSS SHUTDOWN - REQUESTING FAULT
SYSTEM LOCKOUT DELAY. DATA...
POWER FAULT The Liquid Cooled State Starter Logic/Trigger Board
has shut down the chiller but the Control Center has
The CM-2 Current Module (Electro-Mechanical start-
not yet received the cause of the fault from the LCSSS,
er applications) has shutdown the chiller because it de-
via the serial communications link. The LCSSS shuts
tected a fault condition that places the motor at risk.
down the chiller by opening the Motor Controller
This device opens and closes the Motor Controller
LCSSS Stop Contacts (K1 relay located on the starter
“CM” contacts (connected between TB6-16 and TB6-
Logic/Trigger Board and connected between TB6-16
53 in the Control Center) in less than 3 seconds to initi-
and TB6-53 in the Control Center). The Microboard,
ate the shutdown and produce this message. An LED
in the Control Center then sends a request for the cause
on the CM-2 Board illuminates to identify the fault.
of the fault to the Logic/Trigger Board over the serial
The chiller will automatically restart when the contacts
communications link. Since serial communications are
close.
initiated every 2 seconds, this message is typically dis-
CONTROL PANEL – SCHEDULE played for a few seconds and then replaced with one of
the following fault messages.
The programmed Daily Schedule setpoint has shut-
down the chiller. If this occurs while the chiller is run- LCSSS - STOP CONTACTS OPEN
ning, the Pre-rotation Vanes are driven fully closed
Refer to “LCSSS SHUTDOWN – REQUESTING
prior to shutting down the chiller. The chiller will auto-
FAULT DATA ...” above. If the Control Center’s
matically restart at the next scheduled start time.
Microboard does not receive the cause of a starter ini-
MOD “B” SOLID STATE STARTER CYCLING tiated shutdown with 20 seconds of the shutdown, it
SHUTDOWN MESSAGES is assumed it is not forthcoming and that message is
replaced with this message. The chiller can be start-
LCSSS INITIALIZATION FAILED ed when the Motor Controller LCSSS Stop Contacts
When AC power is restored to the system after a power close.
failure, an initialization process occurs wherein the A missing interlock jumper between Starter Logic/
Control Center attempts to establish communications Trigger Board J1-1 and J1-12 will also produce this
through the serial communications link with the Liquid message.
Cooled Solid State Starter. If communications are not
established within 10 consecutive attempts, a cycling LCSSS - POWER FAULT
shutdown is performed and this message is displayed.
The Liquid Cooled Solid State Starter Logic/Trigger
The Control Center attempts to establish communica-
Board has detected that the compressor motor current
tions until successful.
in one or more phases has decreased to less than10% of
LCSSS - SERIAL COMMUNICATIONS
the FLA for a minimum of 1 line cycle. This check is
inhibited during the first 4 seconds of System Run and
After communications have been successfully estab- until the motor current is more than 25% of the FLA.
lished in the initialization process, the Control Center The chiller will automatically restart upon completion
initiates a data transmission to the Liquid Cooled Solid of SYSTEM LOCKOUT DELAY.
State Starter on the serial communications link every 2
seconds. After these communications have been estab- LCSSS - LOW PHASE (X) TEMPERATURE SENSOR
lished, if the Control Center does not receive a reply The Liquid Cooled Solid State Starter Logic/Trigger
within 10 consecutive attempts, a cycling shutdown is Board has detected that the temperature of the starter
performed and this message is displayed. This same phase A, B or C (designated as X in the message) Sili-
cycling shutdown is performed, along with the same con Controlled Rectifier (SCR) Module has decreased
88 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
to less than 37°F. This would generally be indicative SUPPLY VOLTAGE SHUTDOWN RESTART
of a disconnected or defective sensor. If all three SCR RANGE (VOLTS) (VOLTS) (VOLTS)
Modules are indicating a temperature of less than 37°F, 400 320 349
the SCR Module cooling pump turns ON. This is ac-
415 335 362
complished by disconnecting all three sensors. This
440-480 370 400
feature allows Service Technicians to run the cooling
550-600 460 502
pump while filling the cooling system by disconnect-
ing plugs P2, P3 and P4 in the LCSSS.
LCSSS - HIGH SUPPLY LINE VOLTAGE
LCSSS - RUN SIGNAL The Liquid Cooled Solid State Starter Logic/Trigger
The Liquid Cooled Solid State Starter receives two Board has detected that the compressor motor AC pow- 3
start signals from the Control Center simultaneously; er line voltage, in any phase, exceeded the high line
one via the serial communications link and one via the voltage threshold continuously for 20 seconds. The
start relay TB6-24 in the Control Center. If they are chiller will automatically restart when the voltage in
not received within 5 seconds of one another, a cycling all phases returns to the restart level. The thresholds
shutdown is performed and this message is displayed. are as follows:
This is generally indicative of defective wiring. SUPPLY VOLTAGE SHUTDOWN RESTART
RANGE (VOLTS) (VOLTS) (VOLTS)
LCSSS - INVALID CURRENT SCALE SELECTION
Disabled None N/A
There is an invalid compressor motor current scale 200-208 227 226
jumper combination installed in the Liquid Cooled
220-240 262 261
Solid Starter Logic/Trigger Board J1. Jumper combina-
380 415 414
tion determines allowable “100% FLA” setpoint range;
7L-35 to 260A, 14L-65 to 510A, 26L-125 to 850A and 400 436 435
33L-215 to 1050A. The chiller will be permitted to 415 454 453
start when the jumpers are configured correctly. Refer 440-480 524 523
to YORK Starter Service Manual 160.00-O2 for valid 550-600 655 654
jumper configurations.
LCSSS - LOGIC BOARD PROCESSOR
LCSSS - PHASE LOCKED LOOP
Communication between the V25 Microprocessor and
The Liquid Cooled Solid State Starter Logic/Trigger Digital Signal Processor (DSP) on the Liquid Cooled
Board phase locked loop circuit was not able to main- Solid State Starter Logic/Trigger Board has been in-
tain lock with phase A of the power line. This could be terrupted. The chiller will automatically restart when
caused by a power line anomaly such as sag or jitter. A communications are restored.
power line frequency jitter of up to 3Hz/second can be
tolerated. The chiller will automatically restart when LCSSS - LOGIC BOARD POWER SUPPLY
lock has resumed. Following application of power, this message is dis-
played and a snapshot of the LCSSS parameters and
LCSSS - LOW SUPPLY LINE VOLTAGE
time of power failure are sent to the Control Center.
The Liquid Cooled Solid State Starter Logic/Trigger
Board has detected that the compressor motor AC LCSSS - PHASE LOSS
power line voltage, in any phase, decreased below the The Liquid Cooled Solid State Starter Logic/Trigger
low line voltage threshold continuously for 20 seconds. Board has detected the line-to-line RMS voltage in any
The chiller will automatically restart when the voltage phase has decreased to less than or equal to 30% of the
in all phases returns to the restart level. The thresholds lowest value of the programmed voltage range. If the
are as follows: programmed voltage range is “Disabled”, a value of
60VAC is used as the threshold. The chiller will auto-
SUPPLY VOLTAGE SHUTDOWN RESTART
matically restart when the line voltage is more than the
RANGE (VOLTS) (VOLTS) (VOLTS)
shutdown threshold. The voltage range is programmed
Disabled None N/A
by a Service Technician following instructions in Op-
200-208 160 174 tiView Control Center Service Instructions (Form
220-240 185 200 160.81-M1).
380 305 331
JOHNSON CONTROLS 89
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
SAFETY SHUTDOWN MESSAGES freeze is based on how far the evaporator refrigerant
temperature is below the freeze threshold as follows:
EVAPORATOR – LOW PRESSURE
(This message is applicable only if the Smart Freeze Number of seconds to freezing = (4053.7) / (freeze
feature is not activated. If Smart Freeze is activated and threshold-evaporator refrigerant temperature)
has initiated the shutdown, “Evaporator - Low Pressure Smart Freeze is activated only if the feature has been
- Smart Freeze” is displayed. Its description follows). enabled by a Service Technician (following instruc-
The evaporator pressure, as sensed by the Evapora- tions in OptiView Control Center Service Instructions
tor Transducer, has decreased to the safety shutdown (Form 160.81-M1) and the Leaving Chilled Liquid
threshold. For water cooling applications, the safety Temperature setpoint is less than 38.0ºF.
shutdown threshold is a fixed value for the respective The Smart Freeze feature has been removed from pres-
refrigerant. For Brine cooling applications, the safety ent production software. It is no longer available in
shutdown threshold varies according to the concentra- software versions C.MLM.05.04.xxx (and later).
tion of the Brine solution. The Brine shutdown thresh-
old is programmed at the Johnson Controls. It should EVAPORATOR – TRANSDUCER OR LEAVING
not be changed by anyone other than a qualified Service LIQUID PROBE
Technician following instructions in OptiView Control A possible defective Evaporator Pressure Transducer
Center Service Instructions (Form 160.81-M1). The or Leaving Chilled Liquid Temperature Thermistor has
chiller can be started after the evaporator pressure in- been detected. The pressure and temperature that these
creases to the restart threshold and the COMPRESSOR devices are indicating are not in the correct relation-
switch is placed in the Stop-Reset (O) position. ship to each other. The Control Center converts the
evaporator pressure to a Saturated Temperature value
SHUTDOWN and compares this value to the Leaving Chilled Liquid
RESTART (PSIG)
(PSIG) Temperature (difference = chilled liquid temp – evap-
Water cooling orator saturated temp). The difference should not be
25.0 25.1
-R134a outside the range of –2.5ºF to +25.0ºF. If the transducer
Brine cooling - 6.0 to 25.0 as
+0.1 more and thermistor are accurate, the Evaporator Saturated
R134a programmed
than shutdown Temperature should not be more than 2.5º warmer or
threshold more than 25.0ºF colder than the Leaving Chilled Liq-
EVAPORATOR – LOW PRESSURE - SMART uid Temperature. In order to initiate a shutdown, the
FREEZE difference must be outside the acceptable range contin-
uously for 10 minutes. The chiller can be started after
(Not applicable to Software version C.MLM.05.04. the COMPRESSOR switch is placed in the Stop-Reset
xxx (and later). (O) position. This check is not performed when the op-
Smart Freeze Protection is activated and has shut down tional Hot Gas feature is enabled in Brine mode.
the chiller because the evaporator temperature has
EVAPORATOR – TRANSDUCER OR TEMPERA-
been below the Smart Freeze threshold for greater than
TURE SENSOR
the allowable number of seconds. If the Evaporator
Refrigerant Temperature Sensor RT7 is enabled (us- (Not applicable to software version C.MLM.05.04.xxx
ing procedure in OptiView Control Center Service In- (and later).
structions (Form 160.81-M1), this parameter is used as
A possible defective Evaporator Pressure Transducer
the evaporator refrigerant temperature and the freeze
or Refrigerant Temperature Sensor has been detected.
threshold is 32.8ºF. If RT7 is not enabled, the evapo-
The Control Center converts the evaporator pressure to
rator refrigerant temperature used is the Evaporator
a Saturated Temperature value and compares this value
Saturation Temperature, derived from the Evaporator
to the optional Evaporator Refrigerant Temperature
Pressure Transducer and the freeze threshold is 34.0°F.
Sensor. If the difference between these temperatures is
The count is incremented once for every second the greater than 3.0ºF, continuously for 1 minute, this shut-
evaporator refrigerant temperature is below the freeze down is performed.
threshold (but is never decremented below zero). The
This check is only performed under the following con-
number of seconds it will take the chilled liquid to
ditions:
90 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
• Chiller has been running for at least 10 minutes. CONDENSER – PRESSURE TRANSDUCER OUT
OF RANGE
• Evaporator Refrigerant Temperature Sensor (RT7)
has been enabled by a Service Technicians using The Condenser Pressure Transducer is indicating a
instructions in OptiView Control Center Service pressure that is more than 315.0 PSIG. This is outside
Instructions (Form 160.81-M1). the normal operating range of the transducer. This is
generally indicates a defective transducer. The chiller
• Not in Brine Cooling mode. can be started after the transducer is indicating a pres-
• Smart Freeze is enabled. sure that is within range and the COMPRESSOR
switch is placed in the Stop-Reset (O) position.
• Evaporator Temperature Sensor (RT7) or Evapo-
rator Saturation Temperature is indicating a tem- AUXILIARY SAFETY – CONTACTS CLOSED 3
perature of less than 32.0 ºF. The Auxiliary safety shutdown contacts, connected to
The chiller can be started after the temperatures are I/O Board TB4-31 have closed, initiating a safety shut-
within 3.0ºF of one another and the COMPRESSOR down. This input is a general-purpose, user defined
switch is placed in the Stop-Reset (O) position. safety shutdown input. The chiller can be started after
the contacts open and the COMPRESSOR switch is
CONDENSER – HIGH PRESSURE CONTACTS OPEN placed in the Stop-Reset (O) position.
The contacts of the Electro-Mechanical high pressure
DISCHARGE – HIGH PRESSURE
safety device, located on the condenser shell, have
opened because this device has detected a pressure The discharge pressure, as sensed by the Discharge
more than 200.0 PSIG. The contacts will automati- Pressure Transducer, has increased to more than190
cally close when the condenser pressure decreases to PSIG. The chiller can be started after the pressure de-
less than 140.0 PSIG. The chiller can be started after creases to less than 189.5 PSIG and the COMPRES-
the contacts close and the COMPRESSOR switch is SOR switch is placed in the Stop-Reset (O) position.
placed in the Stop-Reset (O) position.
DISCHARGE – HIGH TEMPERATURE
CONDENSER – HIGH PRESSURE The discharge temperature, as sensed by the Discharge
The condenser pressure, as sensed by the Condenser Temperature Thermistor, has increased to more than
Transducer, has increased to more than190.0 PSIG. 175.0º F. The chiller can be started after the temperature
The chiller can be started after the pressure decreases decreases to less than 175.0º F and the COMPRESSOR
to less than 150.0 PSIG and the COMPRESSOR switch switch is placed in the Stop-Reset (O) position.
is placed in the Stop-Reset (O) position.
DISCHARGE – LOW TEMPERATURE
CONDENSER – HIGH PRESSURE – STOPPED The discharge temperature, as sensed by the Discharge
(Software versions C.MLM.05.05.xxx and later or Temperature Thermistor, has decreased to less than
C.OPT.05.05.302 (and later)) The condenser pressure 30.0º F. The chiller can be started after the temperature
exceeded 170.0 PSIG while the chiller was stopped. increases to more than 30.0º F and the COMPRESSOR
High temperature condenser water flowing through the switch is placed in the Stop-Reset (O) position.
condenser while the chiller is shutdown can cause a
condenser high pressure condition resulting in loss of EXCESSIVE LOW DISCHARGE SUPERHEAT
refrigerant. This safety fault anticipates this problem (Software version C.MLM.05.04.xxx (and later))
by annunciating the condenser high pressure condition.
The chiller can be restarted after a Service Technician The chiller has accumulated more than or equal to 30
performs a special reset preset procedure contained in minutes of low discharge superheat run time within 300
OptiView Control Center Service Instructions (Form run hours. Refer to message “Warning – Low Discharge
160.81-M1). Superheat Limit” for the low discharge superheat thresh-
old. The number of and total duration of low discharge
superheat events within the last 300 hours is displayed
on the COMPRESSOR screen (in SERVICE access
level) and print reports as “Low Discharge Superheat
Events” and “Low Discharge Superheat Run Time”.
JOHNSON CONTROLS 91
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
92 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 3 - DISPLAY MESSAGES
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 93
SECTION 3 - DISPLAY MESSAGES FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
MOD “B” SOLID STATE STARTER LCSSS - PHASE (X) SHORTED SCR
SAFETY SHUTDOWN MESSAGES A shorted Silicon Controlled Rectifier (SCR) in phase
LCSSS SHUTDOWN - REQUESTING FAULT A, B or C (designated as X in the message) has been de-
DATA... tected by the Liquid Cooled Solid State Starter Logic/
Trigger Board. The voltage across each SCR in moni-
The Liquid Cooled Solid State Starter Logic/Trig- tored to detect the shorted condition. The shorted con-
ger Board has shut down the chiller but the Control dition must exist continuously for 5 seconds in order to
Center has not yet received the cause of the fault from annunciate the fault. This check is disabled while the
the LCSSS, via the serial communications link. The chiller is running. The chiller can be started after the
LCSSS shuts down the chiller by opening the Motor condition has been corrected and the COMPRESSOR
Controller LCSSS Stop Contacts (K1 relay located on switch is placed in the Stop‑Reset (O) position.
the Logic/Trigger Board and connected between TB6-
16 and TB6-53 in the Control Center). The Microboard, LCSSS - OPEN SCR
in the Control Center, then sends a request for the cause
An open Silicon Controlled Rectifier (SCR) has been
of the fault to the Logic/Trigger Board over the serial
detected by the Liquid Cooled Solid State Starter Log-
communications link. Since serial communications are
ic/Trigger Board. The open condition must exist con-
initiated every 2 seconds, this message is typically dis-
tinuously for 5 seconds in order to annunciate the fault.
played for a few seconds and then replaced with one of
The chiller can be started after the condition has been
the following fault messages.
corrected and the COMPRESSOR switch is placed in
LCSSS - HIGH INSTANTANEOUS CURRENT
the Stop-Reset (O) position. This check is disabled
when the chiller is shut down. In certain applications,
The Liquid Cooled Solid State Starter Logic/Trigger local power line conditions could interfere with the
Board detected that the compressor motor current in open SCR detection technique. This requires a quali-
any phase exceeded 1.1(1.414 x RMS value of the pro- fied Service Technician to disable this check. Refer to
grammed Start Current) for a minimum of 1 second. YORK Service Manual 160.81‑M1.
The chiller can be started after the COMPRESSOR
switch is placed in the Stop-Reset (O) position. LCSSS – PHASE (X) OPEN SCR
LCSSS - HIGH PHASE (X) HEATSINK (Software versions C.MLM.05.05.xxx and later or
TEMPERATURE - RUNNING C.OPT.05.05.302 and later).
The Liquid Cooled Solid State Starter Logic/Trigger An open SCR in phase A, B or C (designated as X in
Board has detected the temperature of phase A, B or message) has been detected. This safety shutdown has
C (designed as X in the message) Silicon Controlled the same criteria as “LCSSS – OPEN SCR” above.
Rectifier (SCR) Modules has exceeded 212°F while However, when the Solid State Starter Logic/Trigger
the chiller was running. The safety can be reset after all Board is equipped with EPROM version C.SSS.01.03
SCR temperatures are less than 210°F and the COM- (and later) and the OptiView™ Control Center is
PRESSOR switch is placed in the Stop‑Reset posi- equipped with above software, the phase in which the
tion (O). However, the chiller cannot be started until open SCR occurred is identified.
all SCR temperatures are less than 109°F. During the
shutdown, the starter cooling pump runs until the tem- LCSSS - PHASE ROTATION
perature is less than 109°F. The Liquid Cooled Solid State Starter Logic/Trigger
Board has detected the three phase compressor motor
LCSSS - 105% MOTOR CURRENT OVERLOAD power line voltage phase rotation is not correct. The
The highest phase of the compressor motor current in- chiller can be started after the phase rotation is correct
creased to more than 105% of the programmed 100% and the COMPRESSOR switch is placed in the Stop-
chiller Full Load Amps continuously for 40 seconds. Reset (O) position.
The chiller can be started after the COMPRESSOR
switch is placed in the Stop‑Reset (O) position.
94 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 4 - PRINTERS
ISSUE DATE 3/24/2011
SECTION 4 - PRINTERS
REPORTS • Figure 38 ‑ Sales Order
A printer can be connected to the Control Center’s • Figure 39 ‑ History
Microboard to print the following reports. The screen
• Figure 40 -
Security Log (Flash Memory Card
from which each report can be generated is listed in
version C.MLM.05.02.xxx and later)
parenthesis.
• Figure 41 - Trend
• Status ‑ Present system parameters (Printer,
Home). • Figure 42 - CUSTOM screen
• Setpoints ‑ Present programmed values of all set- PRINTER TYPES
points (Printer, Setpoints).
The following Printers can be used. Printers must be
• Schedule ‑ Present value of programmed daily equipped with an RS‑232 Serial interface.
schedule (Printer, Schedule).
Okidata
• Sales Order ‑ Information on SALES ORDER
• Models: 182,182 turbo, 184 turbo
4
screen (Printer, Sales Order).
• History ‑ System parameters at the time of the last • Dimensions: 14 in. wide x 10.5 in. deep
normal stop, last fault while running and last 10 • Paper: 8.5 in. wide
faults, whether running or not (Printer, History).
• Type: Dot matrix impact
• Cycling or Safety shutdown initiated Print ‑
Snapshot of all system parameters at instant of • Purchase: 800‑Okidata
shutdown. Automatically occurs if printer is con-
Weigh‑Tronix
nected at time of shutdown.
• Models: 2600, 1220
• Trend - Prints a snapshot of the existing trend
screen data or prints new data collected after the • Dimensions: 2.3 in. wide x 2.8 in. deep
TREND PRINT key is pressed. • Paper: 2.25 in. wide
• Security Log Report - Prints all of the setpoint • Type: Dot matrix impact
changes listed in the Setpoint Change Log on
the SECURITY LOG screen. Also, an individual • Purchase: USA 800‑982‑6622
setpoint change can be printed from the SECU- International 707‑527‑5555
RITY LOG DETAILS screen.
Seiko
• Custom Screen - Prints the information listed on
• Printer Model: DPU414-30B
the CUSTOM screen.
• Power Supply (120VAC/60Hz): PW-4007-U1
The printer can be permanently connected to the Con-
trol Center or connected as required to produce a re- • Thermal Paper: SS112-025B
port. If permanently connected, a DATA LOGGING
• Dimensions: 6.3 in. wide x 6.7 in. deep
feature can produce a status report automatically, be-
ginning at an operator selected start time and occurring • Paper: 4.4 in. wide
at an operator selected interval thereafter.
• Type: Thermal
The following figures are examples of the different
• P
urchase: JACO Electronics, INC
print reports. Solid State Starter application print re-
13710 Reptron Blvd.
ports shown. Electro-Mechanical starter and Variable
Tampa, FL 33626
Speed Drive reports are similar but print parameters
jacoelectronics.com
applicable to those devices.
Phone: 800-800-5441 ext. 4686
• Figure 35 ‑ Status Fax. 813-891-4056
Attn: Katy Buelow
• Figure 36 ‑ Setpoints (Kbuelow@jacoelect.com)
• Figure 37 ‑ Schedule
JOHNSON CONTROLS 95
SECTION 4 - PRINTERS FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
23887A
23889A
WEIGH-TRONIX
00085VIP
SEIKO DPU-414
Figure 34 - PRINTERS
96 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 4 - PRINTERS
ISSUE DATE 3/24/2011
JOHNSON CONTROLS 97
SECTION 4 - PRINTERS FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
If equipped with HIGH SPEED serial board: DipSW 2‑1 ON Printing Columns - 40
DipSW 2‑2 = ON User Font Back‑Up ‑ ON
CONTROL BOARD SWITCH SETTINGS
DipSW 2‑3 = ON Character Select ‑ Normal
SW1 OFF (‑) Low When Busy
DipSW 2‑4 = OFF Zero ‑ Slash
SW2 OFF 1200 Baud*
International Character Set ‑
SW3 OFF 1200 Baud* DipSW 2‑5 = ON
American
SW4 ON 1200 Baud* International Character Set ‑
SW5 Not Used DipSW 2‑6 = ON
American
SW6 OFF No Parity International Character Set ‑
DipSW 2‑7 = ON
SW7 OFF Pin 20 & Pin 11 Act As Busy Line American
International Character Set ‑
Weigh - Tronix Printer DipSW 2‑8 = OFF
American
IMP‑24 MODEL 2600
SW1 - OFF 1200 Baud* DipSW 3‑1 = ON Data Length ‑ 8 Bits
SW2 - ON 1200 Baud* DipSW 3‑2 = ON Parity Setting ‑ No
98 JOHNSON CONTROLS
FORM 160.81-O1 (311)
SECTION 4 - PRINTERS
ISSUE DATE 3/24/2011
Using the PRINTER screen, the actual Printer type • Output Interval ‑ Enter the desired interval be-
connected to the Control Center must be entered. Se- tween prints.
lection determines the control codes that are sent to the
Printer. These codes determine such things as lines per
inch, character width and general formatting. Available
selections are: Okidata, Weigh‑Tronix and Seiko.
JOHNSON CONTROLS 99
SECTION 4 - PRINTERS FORM 160.81-O1 (311)
ISSUE DATE 3/24/2011
YORK UPDATE [Skip the following section if Hot Gas Bypass is not enabled] Hot Gas
CHILLER ID 0 ––––––––––––––––––––––––––––––––––––––––––––––––––––––
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION Hot Gas Solenoid On = False
Mon 21 Jun 1999 1:26:51 PM
Oil Sump
SYSTEM RUN ––––––––––––––––––––––––––––––––––––––––––––––––––––––
LEAVING CHILLED LIQUID CONTROL Oil Pressure = 120.7 Psig
[List all warnings presently active] Differential Oil Pressure = 41.6 Psid
Differential Filter Pressure = 13.1 Psid
Controls C.MLM.05.02.102 Oil Supply Solenoid = On
Run Time 0 Days 2 Hr 59 Min
Operating Hours = 298 Hr [Skip the following section if Level Control is not enabled] Refrigerant
Number Of Starts = 106 Level Control
Control Source = Local ––––––––––––––––––––––––––––––––––––––––––––––––––––––
Refrigerant Level Target = 80 %
Evaporator Refrigerant Level Position = 35 %
––––––––––––––––––––––––––––––––––––––––––––––––––––– Ramp Up Time Remaining = 15 Sec
Leaving Chilled Active Setpoint = 45.0°F [If Ramp Up in effect]
Chilled Liquid Pump = Run
Chilled Liquid Flow Switch = Closed [Skip the following section if Motor Type is not EM]
Leaving Chilled Liquid Temperature = 50.0°F Electro-Mechanical Starter
Return Chilled Liquid Temperature = 59.3°F –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Evaporator Pressure = 78.2 Psig Motor Run = On % Full Load Amps = 94 %
Evaporator Saturation Temperature = 41.1°F
Small Temperature Difference = 10.0 ~F [Skip the following section if Motor Type is not Mod A SSS] Liquid-
Cooled Solid State Starter
Condenser ––––––––––––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––––––––––––––– Motor Run = On
Condenser Liquid Pump = Run % Full Load Amps = 94
Condenser Liquid Flow Switch = Closed % Phase A Voltage = 447 V
Leaving Condenser Liquid Temperature = 85.0°F Phase B Voltage = 409 V
Return Condenser Liquid Temperature = 94.9°F Phase C Voltage = 442 V
Condenser Pressure = 135.8 Psig Phase A Current = 193 A
Condenser Saturation Temperature = 71.7°F Phase B Current = 204 A
Small Temperature Difference = -13.3°F Phase C Current = 190 A
Drop Leg Refrigerant Temperature = 85.0°F
[If Drop Leg Sensor enabled] [Skip the following section if Motor Type is not Mod B SSS]
Sub Cooling Temperature = 2.0°F
[If Drop Leg Sensor enabled] Liquid-Cooled Solid State Starter
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Compressor Motor Run = On
––––––––––––––––––––––––––––––––––––––––––––––––––––– % Full Load Amps = 94
Discharge Temperature = 121.6°F % Starter Model = 33L
Discharge Pressure = 135.7 Psig KW Hours = 20723 KWH
Discharge Saturation Temperature = 120.6ºF Input Power = 145 KW
Discharge Superheat = 1.0°F Phase A Voltage = 447 V
Liquid Injector = Open Phase B Voltage = 409 V
Low Superheat Event =6 Phase C Voltage = 442 V
Low Superheat Run Time = 8 min Phase A Current = 193 A
Phase B Current = 204 A
Phase C Current = 190 A
Phase A Temperature = 88 ~F
Phase B Temperature = 89 ~F
Phase C Temperature = 75 ~F
YORK SCHEDULE
CHILLER ID 3
© 1997 - 1999 YORK INTERNATIONAL CORPORATION
MON 29 MAR 1999 1 27 PM
SCHEDULE = OFF 4
STANDARD SCHEDULE
––––––––––––––––––––––––––––––––––––––––––––––––––––––
SUN START = OFF STOP = OFF
MON START = 06:00 AM STOP = 05:00 PM
TUE START = 06:00 AM STOP = 05:00 PM
WED START = 06:00 AM STOP = 05:00 PM
THU START = 06:00 AM STOP = 05:00 PM
FRI START = 06:00 AM STOP = 05:00 PM
SAT START = OFF STOP = OFF
EXCEPTION DAYS
––––––––––––––––––––––––––––––––––––––––––––––––––––––
15 JUL 1999 START = OFF STOP = OFF
16 JUL 1999 START = 08:00 AM STOP = 10:00 PM
YORK TREND
CHILLER ID 163
© 1997 – 2000 YORK INTERNATIONAL CORPORATION
MON 09 OCT 2000 3:33:47 PM
SI METRIC CONVERSION
The following factors can be used to convert from Eng-
lish to the most common SI Metric values.
MEASUREMENT MULTIPLY THIS BY ENGLISH VALUE BY TO OBTAIN THIS METRIC VALUE
CAPACITY TONS REFRIGERANT EFFECT (ton) 3.516 KILOWATTS (kW)
KILOWATTS (kW) NO CHANGE KILOWATTS (kW)
POWER
HORSEPOWER (hp) 0.7457 KILOWATTS (kW)
FLOW RATE GALLONS / MINUTE (gpm) 0.0631 LITERS / SECOND (L/s)
FEET (ft) 304.8 MILLIMETERS (mm)
LENGTH
INCHES (in) 25.4 MILLIMETERS (mm)
WEIGHT POUNDS (lb) 0.4536 KILOGRAMS (kg)
VELOCITY FEET / SECOND (fps) 0.3048 METERS / SECOND (m/s)
FEET OF WATER (ft) 2.989 KILOPASCALS (kPa)
PRESSURE DROP
POUNDS / SQ. INCH (psi) 6.895 KILOPASCALS (kPa)
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C) subtract 32° and multiply by 5/9 or 0.5556.
To convert a temperature range (i.e., 10°F or 12°F
chilled water range) from Fahrenheit to Celsius, multi-
ply by 5/9 or 0.5556.