Industrial Solutions
M-PACT New
The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878.
In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General
Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the
original index in 1896.
Industrial Solutions
GE Industrial Solutions, a division of GE Energy Management, is a global leading provider in power distribution, offering a
wide range of products which include medium and low voltage power distribution equipment and components, and
motor & control systems that are safe, reliable and offer high performance. Its innovative solutions can improve energy
efficiency and environmental impact in power plants, power grids, oil & gas, mining, data center, overseas EPC,
industrial manufacturing, rail transportation, commercial buildings, residential houses, renewable energy and many
other industries.
2008 World’s Most Respected Companies 2007 World’s Best R&D Companies
M-PACT
Air Circuit Breaker
400-4000A
Technical overview
Air circuit breakers 400A-4000A
Technical overview A
A.4 Fixed Circuit Breaker
A.6 Withdrawable Circuit Breaker
A.7 Characteristics
A.9 State of the Art Electronic Trip Units
A.11
A.19
Time Current Curves
M-PACT Accessories
Order codes B
Wiring diagrams
Dimensional drawings C
A.2
B
A
C
Technical overview
A.3
M-PACT
Notes
Fixed Circuit Breaker
Rated from 400 to 4000A the M-PACT circuit
Specification
A
breaker has been designed to meet the most
stringent demands in fault detection and safe M-PACT air circuit breakers comply with the following
interruption thereof. specifications for Low Voltage Switchgear:
• IEC 60947-1
Available in 2 frame sizes: • IEC 60947-2
- frame size 1 ranging from 400 to 2500A • IEC 60947-3
- frame size 2 ranging from 800 to 4000A • Utilisation category B B
The range has been developed to be aesthetically
and technically co-ordinated with other protective
devices within the GE Power Controls industrial
product ranges. Approvals
The breaker range has a common height and depth and KEMA certification in accordance with IEC 60947-2
is available in both fixed pattern and drawout versions CCC certification in accordance with GB14048-2
CCS certification in accordance with China Certification of shipping
C
which can be manually or electrically operated.
Designed to offer multiple mains connection options it
also comes with a wide range of easy-to-install
accessories.
3 performance ranges*
A -50 kA (Icu)
D -65 kA (Icu)
H1, H2 -80 kA (Icu)
*Ratings shown at 415V AC
2 compact frame sizes
Frame size 1 - 400 to 2500A
Frame size 2 - 800 to 4000A
Fixed pattern and withdrawable versions
3 or 4 pole configuration
Front and rear access connections (horizontal/vertical)
Devices provided with or without protection relay
Manual or electrical operation
Common height and depth dimensions
Built-in safety features e.g. safety shutters
Wide range of protection settings offering full selectivity
Combinations of earth fault protection A D H1,H2
Easy-to-install accessories, common to entire range
Simple and efficient servicing on site
A.4
M-PACT
3 4 5 6
IP54 door panel is also available.
7
8
9
A 10
11
B 1
12
Installation
Fixed pattern M-PACT can be fastened into any suitable
switchboard or cubicle arrangement using four M8 bolts.
Clearance is only required above the unit for the removal and
inspection of the arc chutes (see dimensional drawings for
mounting details and recommended clearance distances).
An earthing point is provided on either side of the circuit breaker.
A.5
Withdrawable circuit breaker Power Supply
11
A
B
• Insulated, earthed steel shutters to isolate the main 3
contact zone
• Front access padlocking for safety shutters
• Secure padlocking in the "Disconnect" position
• Clearly visible operational position indication 2
• Carriage position switch (optional)
• Termination: Flat copper palms (standard) with captive M10 C
fixing nuts
• 'T' terminal adaptors for horizontal/vertical connection 1
(optional)
• Front access connections (optional) 10
• Automatic disconnect of secondary circuits
• Lifting lugs for ease of removing the circuit breaker from
the cassette 9
8 7 6
• Front access of secondary terminals for simple connection
• Cassette side mounting fixing parts (optional)
A.6
M-PACT
Characteristics
Performance Data
Characteristic Symbol Units
Rated current (40℃) 400 800 1000 1250
Endurance (number of operating cycles)
Mechanical (with maintenance) 20000 20000 20000 20000
Mechanical (without maintenance) 10000 10000 10000 10000
Electrical (at rated current) 5000 5000 5000 5000
Technical overview
A 600V
690V
50
40
50
40
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
The figures specified apply to withdrawable ACB's with flat face vertical
1600 Full Full Full - - - - - - copper connections
2000 Full Full Full Full - - - - - (1) Protection degree IP00.For use in enclosures with interior temperatures
2500 Full Full Full Full Full Full - - - of 40℃ to 70℃ the relevant IP values can be applied.
3200 Full Full Full Full Full Full - - -
4000 Full Full Full Full Full 2000 Full - -
A.7
1600 2000 2500 3200 4000
Characteristics
3&4 3&4 3&4 3&4 3&4
100% 100% 100% 100% 100%
A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2
1 1 2 2 1 1 2 2 1 1 2 2 2 2 2 2 2 2 2 2
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65
40 40 40 60 40 40 40 60 40 40 40 60 40 40 40 60 40 40 40 60
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80
50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
50
40
50
40
50
40
50
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60
50
40
50
40
50
40
65
60 A
50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80 50 65 65 80
40 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50
105 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176
105 143 143 176 105 143 143 176 105 143 143 176 105 143 143 176 105 143 143 176
105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143
84
284
84
196
84
98
105
86
84
224
84
224
84
163
105
143
84
351
84
351
84
255
105
223
84
418
84
418
84
418
105
366
84
571
84
571
84
571
105
571
B
574 392 209 184 490 490 347 306 765 765 542 478 888 888 888 783 1224 1224 1224 1224
M-PACT
• Each has a LCD screen with ammeter and a menu driven setting interface, allowing a simple and
accurate setting of all parameters.
• This global line of electronic trip units uses the most recent technology to offer each user an
unique combination of selectivity speed and functionality.
• LT-LTD protection
Each device has an overload setting range of 0.4 to 1 times In and
offer a choice of 22 time bands designed for use with circuit breakers.
C A second set of 22 time bands shaped to match the time current
curves of fuses is available on the MPRO-50 type.
• ST-STD protection
A timed delayed short circuit protection are installed with a current
setting of 2 to 12 times the set LT current value. The short circuit
protection time can be set, at one of 17 bands ranging from 90
milliseconds to 1 second.
Optionaly this device can be set to one of three I2t curves.
• I-protection
A switchable and selective instantaneous protection with a setting
range of 2 to 15 times the breaker rating that is programmed to wait
one half cycle until the downstream device has reacted.
A.10
M-PACT
The curves can be produced for any current setting within the range of the installed protection
Technical overview
10000
Time Current Curve
2h Breaker In= 2500A
----------------------------------
LT - Protection device
Set at Ie= 2400A
Ir at 0,9 =2160A
Band C-10
1000
ST - Protection device
A LT Band Set at 6x Ir of 2160A
Ist=12960A
Band STDB 10
I - Protection device
Set at 12 x Ie of 2400A
Ii = 28800A
100
GF - Protection device
Set at 0,6 x Ie of 2500A
B (Ig = 1500A)
Band GFDB 6
I²t ON & OFF
10
GF Band
C
1 ST Band
0,1 I Band
Tripping Time in Seconds (s)
0,01
HSIOC Band
A.11
Time Current Curves (cold state)
LT Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10000 10000
2h
LT set at Breaker Rating In - Time Current Curve 2h
LT set at Breaker Rating In - Time Current Curve
Setting Range Setting Range
LT-Protection Device LT-Protection Device
100 100
A
Tripping Time In Seconds (s)
Tripping Time In Seconds (s)
1 1
0,1
1,00 10,00 100,00
0,1
1,00 10,00 100,00
B
x Breaker Rating In 7,2x x Breaker Rating In 7,2x
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10000 10000
2h
LT set at Breaker Rating In - Time Current Curve 2h LT set at Breaker Rating In - Time Current Curve
Setting Range Setting Range
Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
LT-Protection Device LT-Protection Device
Ie= 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
C
Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-03 Ir= 0.4 - 1 x Ie in steps of 0.25 - Band C-04
Total Setting Range 0,2 - 1 x In
- Band C-08 Total Setting Range 0,2 - 1 x In
- Band C-09
- Band C-13 - Band C-14
- Band C-19 - Band C-20
1000 1000
100 100
1 1
0,1 0,1
1,00 10,00 100,00 1,00 10,00 100,00
x Breaker Rating In 7,2x x Breaker Rating In 7,2x
A.12
M-PACT
100 100
A
Tripping Time In Seconds (s)
1 1
B 0,1
1,00 10,00 100,00
0,1
1,00 10,00 100,00
x Breaker Rating In 7,2x x Breaker Rating In 7,2x
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve - 10 - Time Current Curve
ST-Protection Device ST-Protection Device
I 2t - OFF- I 2t - OFF-
6 4
5 3
0,1 2
1 0,1
4
3
2
1 Green Line = Full Clearing Time Green Line = Full Clearing Time
Red Line = Non Tripping Time Red Line = Non Tripping Time
0,01
Tripping Time In Seconds (s)
0,01
Tripping Time In Seconds (s)
0,001 0,001
1,00 10,00 100,00 1,00 10,00 100,00
x Breaker Rating In x Breaker Rating In
A.13
Time Current Curves (cold state)
ST Protection Device
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
ST- Protection Device ST- Protection Device
4
3
2
1 Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time
A
Tripping Time In Seconds (s)
00,1 00,1
0,01
1,00 10,00 100,00
0,01
1,00 10,00 100,00
B
x Breaker rating In x Breaker rating In
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
ST set at Breaker Rating In ST set at Breaker Rating In
ST- Protection Device ST- Protection Device
Setting Range Setting Range
1,5 to 12 × Ir in steps of 0,5 1,5 to 12 × Ir in steps of 0,5
I 2t ON “med” I 2t ON “med”
-
-
Band STDB 01
Band STDB 03
-
-
Band STDB 02
Band STDB 04
C
- Band STDB 05 - Band STDB 06
- Band STDB 07 - Band STDB 08
- Band STDB 09 - Band STDB 10
17 - Band STDB 11 - Band STDB 12
1 17 1 16
15 - Band STDB 13 16 - Band STDB 14
0,8 15 0,8 14
13 - Band STDB 15 14 - Band STDB 16
0,6 13 0,6
- Band STDB 17 12
11 12
0,4 11
0,4 10
9
10 8
9 7
8
0,2 7 0,2 6
5
6
5 3 4
0,1 1 0,1 2
4
3
1 2
Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time
Tripping Time In Seconds (s)
00,1 00,1
0,01 0,01
1,00 10,00 100,00 1,00 10,00 100,00
Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time
A
Tripping Time In Seconds (s)
0,01 0,01
B 0,01
1,00 10,00 100,00
0,01
1,00 10,00 100,00
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
1 1
- Time Current Curve - Time Current Curve
I set on breaker rating In I - Protection Device I set on breaker rating In HI - Protection Device
HI Setting Range RELT - Protection Device HI Setting Range RELT - Protection Device
C
2 to 15 × Ie in steps of 0,5 2 to 15 × Ie in steps of 0,5
Green Iine = Full Clearing time Green Iine = Full Clearing time
Red Line = Non Tripping time Red Line = Non Tripping time
0,01 0,01
Tripping Time In Seconds (s)
0,001 0,001
1,00 10,00 100,00 1,00 10,00 100,00
100kA
85kA
65kA
0,1 0,1 50kA
0,01 0,01
A
Tripping Time In Seconds (s)
50 kA
65 kA
85 kA
100 kA
0,01
1000 10000 100000 10000,00
0,01
1000 10000 100000 10000,00
B
Amps Amps
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
GF- Protection Device GF- Protection Device
I 2t -OFF- I 2t -OFF-
-
-
Band GFDB
Band GFDB
01
03
-
-
Band GFDB
Band GFDB
02
04
C
- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
GF set on breaker rating In - Band GFDB 09 GF set on breaker rating In - Band GFDB 10
Setting Range Setting Range
0,1 to 1 × In in steps of 0,01 - Band GFDB 11 0,1 to 1 × In in steps of 0,01 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14
14 14
13
0,8 13 0,8
12
11 12
0,6 0,6
11
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 0,2 4
5
3
4
2
3 1
0,1 0,1
Green Iine = Full Clearing time
Red Line = Non Tripping time
2
Tripping Time In Seconds (s)
0,01 0,01
0,10 1,00 10,00 0,10 1,00 10,00
1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 5 0,2 4
3
4 2
3 1
0,1 0,1
Green Iine = Full Clearing time
A
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)
B 0,01
0,10 1,00 10,00
0,01
0,10 1,00 10,00
MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit
10 - Time Current Curve 10 - Time Current Curve
GF set on breaker rating In GF- Protection Device GF set on breaker rating Inv GF- Protection Device
Setting Range Setting Range
I 2t “med” -ON-
C
0,1 to 1 × In in steps of 0,01 0,1 to 1 × In in steps of 0,01 I 2t “med” -ON-
- Band GFDB 01 - Band GFDB 02
- Band GFDB 03 - Band GFDB 04
- Band GFDB 05 - Band GFDB 06
- Band GFDB 07 - Band GFDB 08
- Band GFDB 09 - Band GFDB 10
- Band GFDB 11 - Band GFDB 12
- Band GFDB 13 - Band GFDB 14
1 1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
0,2 0,2 4
5
3
4 2
3 1
0,1 0,1
Green Iine = Full Clearing time
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)
0,01 0,01
0,10 1,00 10,00 0,10 1,00 10,00
1 1 14
13 14
0,8 13 0,8 12
11 12
0,6 11 0,6
10
9 10
0,4 0,4
9 8
7
8 6
7 5
6
4
0,2 5 0,2
3
4 2
3 1
0,1 0,1
Green Iine = Full Clearing time
A
Green Iine = Full Clearing time Red Line = Non Tripping time
Red Line = Non Tripping time 2
Tripping Time In Seconds (s)
0,01
0,10 1,00 10,00
0,01
0,10 1,00 10,00
B
x Breaker rating In x Breaker rating In
A.18
M-PACT
B
Circuit breaker closing coil
A.19
Auxiliary switches Cassette main terminal adaptors
The M-PACT circuit breaker is equipped with 5 NO and 3 NC
auxiliary switches as standard. Maximum number of contacts is 8,
for alternative configurations please contact for availability.
M-PACT Accessories
Combinations of rear and front access connections possible for
Easily fitted, this useful accessory may be specified for use with entire range. Tested and approved from 50 to 80kA.
either manual or motor charged M-PACT circuit breakers.
It is clearly visible through the front panel, and the counter
provides an accurate record of the cumulative number of A
complete breaker closing operations.
Ronis: Type 1104B lock with standard key, 1/4" turn rotation to
trap the key, compulsory spindle size.
A.20
M-PACT
C Cluster contacts
These are the main isolating contacts which are fitted to the rear
terminals on the moving portion of the withdrawable unit.
As part of standard inspection and maintenance procedures,
cluster contacts have been designed to be easily and quickly
removed and replaced using universal cluster pliers.
A.21
Interlocks
Mechanical interlocks can be fitted to the following electrical systems and can link 2 or 3 circuit breakers of any
rating or number of poles, Fixed or Withdrawable.
M-PACT Accessories
Type A
Interlocking between 2 circuit breakers
B1 B2
B1 normal power supply
B2 generator (emergency) supply 0 0
I 0
0 I
Type B
Interlocking between 3 circuit breakers
Type C
Interlocking between 3 circuit breakers B
2 bus sections can be powered by a B1 B2 B3
single transformer (bus coupler 0 0 0
closed) or by both transformers I 0 0
(bus coupler open). 0 I 0
0 0 I
Available upon request.
I 0 I
C
0 I I
I I 0
Any 2 from 3 circuit breakers can be closed
Any 1 from 3 circuit breakers can be closed
A.22
M-PACT
Cassette interlock
A
Sealed
door panel
escutcheon
An optional IP54 complete front door
panel is available should a higher
degree of protection be necessary.
A.23
Plug-in Portable Test Unit (PTU) Auxiliary Power Unit (APU)
M-PACT Accessories
Specially designed for reliable testing of the MCR and HSISC
protection systems on each phase, by means of tertiary
injection. Can be powered by 2 x 9 V batteries or main power
lead. Available to be fitted within the circuit breaker cubicle, an
APU ensures that M-PRO receives independent and
continuous
power at all times. The APU accepts any input supply
voltage within 380VAC, 110V, 220V AC/DC. Maximum
input current is 0.5 A. 1m length cable (twisted pair) should
be used to connect auxiliary supply and MPRO protection
relay. A
Motor operator
110-130
380-440
110-130
48, 60 0.85 to 1.1 times
AC-50VA
DC-50W C
24-30 rated voltage
220-250 220-250
110-130 110-130 AC-300VA
Closing coil
380-440 48 0.85 to 1.1 times DC-250W
24-30 rated voltage
220-250 220-250
110-130 110-130 AC-300VA
Shunt trip
380-440 48 0.70 to 1.1 times DC-250W
24-30 rated voltage
380-440 110-130 -
Instantanious Undervoltage Inrush power consumption 300VA
220-250 48 -
release Holding power consumption 20VA
110-130 24-30 -
Auxiliary power unit 110, 220, 380 110, 220 - -
A.24
Order codes
M-PACT
A Technical overview
B Order codes
B.2 Specify on the order
B.3 Breaker ordering code
B.5 M-PACT Air Circuit Breaker - Type A - 50kA
B.7 M-PACT Air Circuit Breaker - Type D - 65kA
B.9 M-PACT Air Circuit Breaker - Type H1,H2 - 80kA
B.11 Factory Mounted Trip Units
C B.12 Spare Trip Units
Wiring diagrams
Dimensional drawings
B.1
1. Customer Name 2. Project Name 3. Quanitity
Specify on the Order
3. Number of Poles □ 3 Pole □ 4Pole Left Neutral □ 4Pole Right Neutral * Viewed from front of breaker.
7. Protection □ Non automatic □ MPRO 27 □ MPRO 27 WITH GF □ MPRO 50L □ MPRO 50H
□ Mechanical Operation Counter □ Mechanical Trip Alarm Switch (1NO) A
8. Optional Features □ Portable Test Unit Auxillary Power Unit □ 110V AC/DC □ 220V AC/DC
Auxillary Contactor □ 5NC+3NC □ 4NC+4NC
9. Control Voltage MOP CC ST UV UVTD
24/30V DC □ □ □
48V DC □ □ □ □ □
B
60V DC □
110/130V DC □ □ □ □
110/130V AC □ □ □ □
220/250V DC □ □ □
220/250V AC □ □ □ □ □ C
380/440V AC □ □ □ □ □
11. Interlocks Door interlock □ left Door interlock (Hinge in left) □ Right door interlock(Hinge in right)
B.2
M-PACT
Breaker ordering code
M P A 3 1 F 0 8
Order codes
Poles
3 3 poles
Rating
4 4 poles
08 800A
Frame 10 1000A
1 Frame 1
12 1250A
A 2 Frame 2
Type 16 1600A
Breaking Capacity
others Acc
C 000 standard without any option
002 Earth Fault Protection(UEF)
006 Neutral protection
015 Ronis Key breaker Interlock (factory fitted)
016 Mechanical Trip alarm Switch (1n/o)
049 Carriage switch
025 UEF+Mechanical Trip alarm Switch (1n/o)+Ronis Key breaker Interlock (factory fitted)
028 Mechanical Trip alarm Switch (1n/o) + Carriage switch +UEF
029 Ronis Key breaker Interlock (factory fitted)+UEF
047 UEF+Mechanical Trip alarm Switch (1n/o)+Mechanical operations counter
104 UEF+Mechanical Trip alarm Switch (1n/o)+Carriage switch
107 UEF+Mechanical Trip alarm Switch (1n/o)
111 Mechanical Trip alarm Switch (1n/o)+Ronis Key breaker Interlock
For more option codes please ref to sheet "optional" or contact our local office.
B.3
N 4 4 4 0 X X X
MPro Shunt
0 Non-Auto 0 No
N Mpro 27 1 24/30V DC
V Mpro50L 2 48V DC
W Mpro50H 3 110/130V DC/AC A
4 220/250V DC/AC
Motor Operator 5 380/400V AC
0 No
1 24/30V DC
Undervoltage B
2 48V DC 0 No
B.4
M-PACT
A 2 4000
4
3
MPA42W32
MPA32W40
MPA42F32
MPA32F40
4 MPA42W40 MPA42F40
B.5
Air Circuit Breaker - TYPE A - 50kA
Front Access Connections
Fixed Type
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31FA16T FA31FA16B
4 FA41FA16T FA41FA16B
1 2000 to 2500 3 FA31FA25T FA31FA25B
4 FA41FA25T FA41FA25B
2 3200 3 FA32FA32T FA32FA32B
4 FA42FA32T FA42FA32B
2 4000 3 FA32FA40T FA32FA40B
4 FA42FA40T FA42FA40B
Cassette only
Basic cassette with flat copper terminals rear connected.
Frame size Rating (A) Poles Cat. no.
1 400 to 1600 3 MPA31C16
4 MPA41C16
1 2000 to 2500 3 MPA31C25
4 MPA41C25
2 3200 3 MPA32C32
2 4000
4
3
MPA42C32
MPA32C40
A
4 MPA42C40
1 1000
4
3
MPA41M08
MPA31M10
C
4 MPA41M10
1 1250 3 MPA31M12
4 MPA41M12
1 1600 3 MPA31M16
4 MPA41M16
1 2000 3 MPA31M20
4 MPA41M20
1 2500 3 MPA31M25
4 MPA41M25
2 3200 3 MPA32M32
4 MPA42M32
2 4000 3 MPA32M40
4 MPA42M40
B.6
M-PACT
A 2 4000
4
3
MPD42W32
MPD32W40
MPD42F32
MPD32F40
4 MPD42W40 MPD42F40
B.7
Air Circuit Breaker - TYPE D - 65kA
Front Access Connections
Fixed Type
TOP connections BOTTOM connections
Frame size Rating (A) Poles Cat. no. Cat. no.
1 400 to 1600 3 FA31FD16T FA31FD16B
4 FA41FD16T FA41FD16B
1 2000 to 2500 3 FA31FD25T FA31FD25B
4 FA41FD25T FA41FD25B
2 3200 3 FA32FD32T FA32FD32B
4 FA42FD32T FA42FD32B
2 4000 3 FA32FD40T FA32FD40B
4 FA42FD40T FA42FD40B
Cassette only
Basic cassette with flat copper terminals rear connected.
Frame size Rating (A) Poles Cat. no.
1 400 to 1600 3 MPD31C25
4 MPD41C25
2 3200 3 MPD32C32
4 MPD42C32
2 4000 3 MPD32C40
4 MPD42C40
A
B.8
M-PACT
A 2 3200 3
4
MPH32W32
MPH42W32
MPH32F32
MPH42F32
MPH232W32
MPH242W32
MPH232F32
MPH242F32
2 4000 3 MPH32W40 MPH32F40 MPH232W40 MPH232F40
4 MPH42W40 MPH42F40 MPH242W40 MPH242F40
B.9
Air Circuit Breaker - TYPE H1,H2 - 80kA
Cassette only
Basic cassette with flat copper terminals rear connected.
B.10
M-PACT
MPRO-27
Basic functionality Functionality and application Cat. No.
MPRO-27 trip unit For Frame 1 GL100M3-SF
Extended functionality
MPRO-27 trip unit For Frame 1 GL100M5-SF
A MPRO-50
MPRO-50L For Frame 1 GH100M7-6SF
LT band choice (LT-C or LT-F)
LT-C 0.4-1 x In = Ir Dual GF protection (Res./SUM or CT)
-ORLT- Relt Instantaneous &
Basic functionality
F 0.4-1 x In = Ir Modbus Communiction
ST
STD
B GF sum. I2t ON or OFF For Frame 2 GH200M7-6SF
-AND/ORGF LT band choice (LT-C or LT-F)
CR I2t ON or OFF Dual GF protection (Res./SUM or CT)
GFDB Relt Instantaneous &
I Modbus Communiction
RELT
Input supply 24V AC(1)
Accessories
Designation
Digital test kit GTUTK20
Mechanical Accessories
2 way Interlocking Type A 1 from 3 wayInterlocking Type B
Frame Type Poles Cable Frame Type Poles Cable
size Cat. no. Ref. no. size Cat. no. Ref. no.
1 Withdrawable 3 2WCI3PW 406342 1 Withdrawable 3 B13WCI3PW 406350 C
1 4 2WCI4PW 406343 1 4 B13WCI4PW 406351
2 3 2WCI3PW 405459 2 3 B13WCIF23PW 405475
2 4 2WCI4PW 405461 2 4 B13WCIF24PW 405477
1 Fixed 3 2WCI3PF 406340 1 Fixed 3 B13WCI3PF 406348
1 4 2WCI4PF 406341 1 4 B13WCI4PF 406349
2 3 2WCI3PF 405463 2 3 B13WCIF23PF 405479
2 4 2WCI4PF 405465 2 4 B13WCIF24PF 405481
Interlocks Miscellaneous
Item Cat. no. Order Code Item Cat. no. Order Code
Mechanical Operations Counter MOC B40006511
left Door interlock (Hinge in left) DILHS B40006546
Ronis Key breaker Interlock⑴ RONLOK B40006515 Right door interlock(Hinge in right) DIRHS B40006504
Ronis Key Cassette Interlock(factory fitted) RONCASFF B40011378 Mis-Insertion Device ACBMID B40006503
IP54 Door IP54DOOR B40006507
Lifting Truck ACBLIFT B40006832
Mechanical Trip Alarm Switch MPROMAC B40006573
Frame 1, 2
Spare parts
Neutral (4th) Rogowski coil
Current transformer with mounting kit(1)
with mounting kit(2)
A 1
2
800 ELCT8001
ELCT8002
RCMK8001
RCMK8002
1 1000 ELCT10001 RCMK10001
2 ELCT10002 RCMK10002
1 1250 ELCT12501 RCMK12501
2 ELCT12502 RCMK12502
1 1600 ELCT16001 RCMK16001
2 ELCT16002 RCMK16002
1 2000 ELCT20001 RCMK20001
B 2 ELCT20002 RCMK20002
1 2500 ELCT25001 RCMK25001
2 ELCT25002 RCMK25002
2 3200 ELCT32002 RCMK32002
2 4000 ELCT40002 RCMK40002
(1) The earth CT leg is used for GF CT function which offered by MPOR50. But it is not default with MPOR50 as standard parts.
Please contact with GE local office,if you have any inquire.
C (2) Rogowski coils are provided with twisted pair cables of (max. length 2m).
The 4th Rogowski coil for GF protection comes default with 3 pole breakers. If you need a separate 4th Rogowski coil please
contact your local GE Energy Industrial Solutions office.
B.13
Air circuit breakers 400A-4000A
Technical overview A
Order codes B
Wiring Diagrams
Dimensional drawings C
C.2 Mpro 27 & 50 Connection Scheme
C.6 Dimensional drawings
C.1
M-PACT
Wiring Diagrams
Mpro 27 & 50 Connection Scheme
A9 A8 B5 B6
Dimensional drawings
Connection scheme
Wiring diagrams
Interposing CT
EL CT N-RC N-RC Relay O/P1 Relay O/P2 Relay O/P3 Relay O/P4 24V+ 24V-
- +
N
+24-
N VDC
Connection scheme
A
Communication
Input 1 - 4
Electronic Trip Unit
MPRO 50 C 1 2 3 4
SCR RX- RX+ TX- TX+
OFF
B OFF ON
C9
C11
C13
C15
B11
B13
B15
(+VE)
(+VE)
C1
C3
C5
C7
B9
B1
B7
C A A B B B A A A A A
C
AL ML
D
UVR
M ST CC UVTD
(-VE)
(-VE)
C10
C12
C14
C16
B12
B16
B10
B14
B2
C6
C8
C4
B8
C2
LP7
LP5
LP6
LP4
Breaker accessories
C.2
Dimensional drawings
Mounting hole - Fixed Type
Frame 1 - ¢ 9.2mm , Recommend bolt M8 x 4.
Frame 2 - ¢ 11.2mm , Recommend bolt M10 x 4.
Dimensional drawings
Minimum space to earth metal
and for arc chute removal
Centre line of operating panel
Insulated metal or insulated
sheet ( customer supplied )
Centre line of
operating panel
A
100 to door
Centre line of
operating panel
100 to door
C.3
M-PACT
Centre line of
operating panel
100 to door
Centre line of
operating panel
100 to door
Dimensional drawings
Minimum space to earth metal
and for arc chute removal Insulated metal or insulated
Centre line of operating panel sheet ( customer supplied )
Centre line of
operating panel
A
100 to door
Centre line of
operating panel
100 to door
C.5
M-PACT
Centre line of
A operating panel
100 to door
Centre line of
operating panel
100 to door
Dimensional drawings
to door Minimum clearance
to cassette side
Ventilation
Centre line of
operating panel
B
Type A-4 pole- Frame size 1, In=400A to 1600A
to door C
Minimum clearance
to cassette side
Ventilation
Centre line of
operating panel
35 Test Connected
Centre line of operating panel
50 Disconnected
C.7
M-PACT
Ventilation
Centre line of
operating panel
B
Type A-4 pole- Frame size 1, In=2000A & 2500A
Type D-4 pole- Frame size 1, In=400A to 2500A
C
to door
Minimum clearance
to cassette side
Ventilation
Centre line of
operating panel
C.8
Rear access connection
Withdrawable pattern
Type A, D-3 pole- Frame size 2, In=3200A
Dimensional drawings
Type H-3 pole- Frame size 2, In=800A to 3200A
to door
Minimum clearance to cassette side
Ventilation
Center line of
operating panel
B
Type A, D-4 pole- Frame size 2, In=3200A
Type H-4 pole- Frame size 2, In=800A to 3200A
to door
Minimum clearance to cassette side
C
Ventilation
Center line of
operating panel
C.9
M-PACT
to door
Ventilation
Center line of
operating panel
Center line of
operating panel 35 Test Connected
A 50 Disconnected
275 Fully withdrawn
B
Type A, D,H - 4 pole - Frame size 2, ln=4000A
Ventilation
Center line of
operating panel
C.10
Front access connection
Fixed pattern
Dimensional drawings
Minimum space to earth metal
Minimum clearance and for arc chute removal
to breaker side Insulated metal
or insulated sheet
(customer supplied)
Center line of
operating panel
100 to door
Center line of
operating panel
A
B
Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A
Minimum clearance
and for arc chute removal
Insulated metal
C
to breaker side or insulated sheet
(customer supplied)
Center line of
operating panel
100 to door
Center line of
operating panel
C.11
M-PACT
Insulated metal
or insulated sheet
(customer supplied)
Center line of
operating panel
100 to door
A
Center line of
operating panel
B
Type A, D - 4 pole - Frame size 1, ln = 2000A to 2500A
Center line of
operating panel
100 to door
Center line of
operating panel
C.12
Front access connection
Fixed pattern
Center line of
operating panel
100 to door
Center line of
operating panel
A
B
Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000A
Type H - 4 pole - Frame size 2, ln = 800A to 4000A
Center line of
operating panel
100 to door
Center line of
operating panel
C.13
M-PACT
Plqlpxp#fohdudqfh
wr#euhdnhu#vlgh
to door
Wiring diagrams
Fhqwhu#olqh#ri
rshudwlqj#sdqho
Connected
A Disconnected
Fhqwhu#olqh#ri Test
rshudwlqj#sdqho
B
Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A
Center line of
operating panel
Connected
Disconnected
Center line of Test
operating panel
C.14
Front access connection
Withdrawable pattern
to door
Center line of
operating panel
Connected
Test
Disconnected A
Center line of
operating panel
Center line of
operating panel
Connected
Disconnected
Center line of Test
operating panel
C.15
M-PACT
to door
Wiring diagrams
Center line of
operating panel
Connected
Test Disconnected
Center line of
operating panel
A
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.
B
Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000A
Type H - 4 pole - Frame size 2, ln = 800A to 4000A
Center line of
operating panel
Connected
Disconnected
Test
Center line of
operating panel
C.16
Adaptor connections
B
Rear Adapter Vertical / Horizontal Connection
Type D - Frame 1 - ln = 400A to 2500A (max) Type A,D,H - Frame 2 - ln = 800A to3200A (max)
C.17
M-PACT
Type A - Frame 1 - ln = 400A to 2500A (max) Type A,D - Frame 2 - ln = 3200A to 4000A (max)
Type D - Frame 1 - ln = 400A to 2500A (max) Type H - Frame 2 - ln = 800A to 4000A (max)
Dimensional drawings
Wiring diagrams
Type A,D,H - Frame 2 - ln = 4000A IP54 Door (Withdrawable unit only - Frame 1&2 only)
C.18
Cassette mounting details
Adaptor connections
Terminals
A Centre line of A
operating panel
3 pole 4 pole
3 pole 4 pole
3 pole 4 pole B
Terminals
C
Centre line of
A A
operating panel
3 pole 4 pole
3 pole 4 pole
Door cut-outs
Fixed pattern
Dimensional drawings
Wiring diagrams
Door
281
270.2 Door
19 131
5.4
16 off M3 x 6
self tapping screw
Escutcheon
28
378
178
358
ACB facia
ACB facia
centre line of ACB
A mounting hole
175
100
175 100
5.4
Frame 1 = 42.5 263
40 13 Frame 2 = 102.5
Withdrawable pattern
Door
16 off M3 x 6
self tapping screw
Escutcheon
ACB facia
benchmark of
breaker left side
benchmark of
Frame 1: Max.2500A=40
breaker button side
Frame 2: Max.4000A=100
C.20
2-Way cable interlocking
Door cut-outs
A
C
Frame 1-3P = 329
Frame 1-4P = 429
Frame 2-3P = 419
Frame 2-4P = 549
900 Max vertical base to base
Min.
Min. clearance
clearance below
below cassette
cassette
C.21
M-PACT
1250 MAX
F13P=322
55 F14P=422 55
Wiring diagrams
55
F23P=410
F24P=540
30
40 MIN. CLEARENCE
BELOW CASETTE
C.22
GE
Industrial Solutions
Greater China
Shanghai Taiwan
4F, Building 2, CTP, No.1 Hua Tuo Rd. 6F, No. 8, Min Sheng E. Rd., Sec. 3,
Zhang Jiang Hi-Tech Park Taipei 10480
Shanghai, China 201203 T : +886 2 2183 7000
T : +86 21 3877 7888 F : +886 2 2516 6829
F : +86 21 3877 7600
ANZ
Australia New Zealand
125-127 Long Street Level 1, 8 Tangihua Street
Smithfield, Sydney, NSW 2164 Auckland, North Island