MEASUREMENTS

ISTAT I300
High Accuracy Analogue
Transducers

Improving competitiveness and performance is


key to any business. New solutions must be
developed to optimise the assets, benefit from the
latest technology capabilities and adapt to the
rapidly changing environment.
T&D offers complete solutions for the entire
energy chain, from the primary equipment up to
the market management software.

The ISTAT I300 range of analogue transducers is


designed to meet the world market requirements
of high accuracy and reliability with a stable
output.
Available in two compact case sizes of 55mm and
150mm wide, the transducers are supplied to
meet the customers precise needs.

APPLICATIONS

Applications can be found in substations of electrical utilities and industry, for


interfacing with SCADA (Supervisory Control and Data Acquisition), building
management systems, process control equipment and switchboard
instrumentation.

ISTAT I300 analogue transducers provide local and remote indication for precision
electrical measurement and control when used with instruments, data loggers
and SCADA systems.

WHY ISTAT I300 ANALOGUE TRANSDUCERS?

ISTAT I300 transducers have been designed to provide highly accurate and
Customer Benefits reliable measurements for integration into control systems. The transducer
• Comprehensive set design was based on research into the market needs on an international and
of measurements industrial scale.

• Proven reliabilty gained


from over 30 years of
manufacturing knowledge
• High accuracy and stability

AREVA T&D
ISTAT I300
Features and benefits

FEATURES AC MODEL RANGE


Model Application Case
> 0.2% full scale accuracy for current and voltage
transducers 3CA Mean sensing Current 55mm
3CC Triple Mean sensing 150mm
> 0.2% of reading accuracy for watt and var transducers Current
(based on 0.19% of reading + 0.01% FSD) 3CD True RMS Current 55mm
3CF Triple True RMS Current 150mm
> 4KV isolation withstand
3FA to 3FD 0.1% Frequency 55mm
> 3 x continuous current overload rating 3FE to 3FG 0.01% Frequency 150mm
3K Watt hour 150mm
> Integral dc auxiliary supply option 3P Phase Angle range 150mm
> DIN rail mounting 3R Vars range 150mm
3VA Mean sensing Voltage 55mm
> High packing density 3VC Triple Mean sensing Voltage 150mm
> Full range of ac and dc measurements 3VD True RMS Voltage 55mm
3VF Triple True RMS Voltage 150mm
> High stability 3VL Linear Inverse Voltage 55mm
3VX Suppressed Zero Voltage 55mm
3W Watts range 150mm

DC MODEL RANGE
BENEFITS
Model Application Case
3DA Tap Position Indicator 150mm > Significant gains in overall system accuracy can result
3DB Voltage 150mm from improvements in source measurement
3DC Current 150mm
3DD Summation 150mm > Compliance with international standards ensures
3DH Thermocouple 150mm transducers can be used world wide
3DL 3 wire Resistance 150mm
3DJ Thermocouple with CJC 150mm > Long life expectancy and very reliable operation in
most climates
DC/DC CONVERTER RANGE > Quick and simple means of transducer selection

> Three voltage or current transducers can be housed in


Model Application Case
a single 150mm package
3BA 24V 55mm
3BB 32V 55mm > Can be integrated into modern control schemes
3BC 48V 55mm utilising analogue technology
3BD 110V 55mm
> Gives accurate measurements of parameters critical
3BE 125V 55mm
for optimum plant use.
3BG 220/48V (use with 3BC) 55mm
> Minimal maintenance costs as readjustment is not
required

ISTAT I300:
Used by Industrial or Utility engineers,
at all voltage levels
2>3
RANGE • Technical specification
• Current nominal input 1 or 5A In
> AC Mean Sensing Current and Voltage • Current range of use 0 to 200% In
• Current burden 1.0VA
The 3CA current and 3VA voltage transducers will • Current overload 3 x In continuous
only require an external power supply if a biased 25 x In for 3s
4…20mA output is required. These transducers
50 x In for 1s
require a full specification before manufacture can
take place, these settings cannot be changed by the • Voltage input range 63.5 to 440Vn
user. The 3CC and 3VC are triple versions and are • Voltage range of use 0 to 150% Vn
housed in the larger 150mm case. • Voltage burden 0.1VA
• Voltage overload 1.5 x Vn continuous
• Technical specification 2 x Vn for 10s
• Current nominal input 1 or 5A In • Frequency range 45/55 or 55/65Hz
• Current range of use 0 to 200% In
• Current burden 1.5VA (0.6VA • Acuracy of the analogue output
biased output) • Nominal accuracy 0.2%
• Current overload 3 x In continuous • Current reference range 20 to 200% In
25 x In for 3s • Voltage reference range 25 to 150% Vn
50 x In for 1s
• Voltage input range 63.5 to 440Vn
• Voltage range of use 0 to 150% Vn > Frequency
• Voltage burden 1.0VA (0.3VA
biased output) The 3F frequency transducer can be supplied with
• Voltage overload 1.5 x Vn continuous an accuracy of either 0.1% or 0.01%. It can be
2 x Vn for 10s supplied with either an ac or dc auxiliary power
• Frequency range 45/55 or 55/65Hz supply. These transducers require a full
specification before manufacture can take place,
these settings cannot be changed by the user.
• Acuracy of the analogue output
• Nominal accuracy 0.2% 0.1% 0.01%
• Current reference range 0 to 200% In 45 … 55Hz 3FA N/a
(except biased output 0 to 100% In) 55 … 65Hz 3FB N/a
• Voltage reference range 25 to 150% Vn 48 … 52Hz 3FC 3FE
(except biased output 20 to 100% Vn) 58 … 62Hz 3FD 3FF
47 … 53Hz N/a 3FG

> AC True RMS Current and Voltage


• Technical specification
The 3CD current and 3VD rms voltage transducers • Voltage input range 63.5 to 440V, Vn
can be supplied with either an ac or dc auxiliary • Voltage range of use 0 to 120% V, Vn
power supply. These transducers require a full • Voltage burden 1.5VA (0.1%),
specification before manufacture can take place, 0.1VA (0.01%)
these settings cannot be changed by the user. The
3CF and 3VF are triple versions and are housed in • Acuracy of the analogue output
the larger 150mm case. • Nominal accuracy 0.1 or 0.01%
• Voltage reference range 80 to 120% Vn
The 3VX is a variant of the 3VD but is supplied with for 0.1% and
a suppressed characteristic. 20 to 120% Vn
for 0.01% models

> Watt hour with pulsed and analogue output

These transducers can be supplied with either an ac


or dc auxiliary power supply with the exception of
the 3KF which can also have the option of using the
3B Dc/Dc converter.. These transducers require a
full specification before manufacture can take place,
these settings cannot be changed by the user.

Connection Wh
single phase 3KA
3 phase, 3 wire balanced, 1El 3KB
3 phase, 4 wire balanced, 1El 3KC
ISTAT I300: 3 phase, 3 wire unbalanced, 2 El 3KD
comprehensive 3 phase, 4 wire unbalanced, 2.5 El 3KE
3 phase, 4 wire unbalanced, 3 El 3KF
ac measurement range
• Technical specification • Technical specification
• Current nominal input 1A or 5A In • Current nominal input 1A or 5A In
• Current range of use 0 to 160% In • Current range of use 0 to 160% In
• Current burden 0.3VA • Current burden 0.3VA
• Current overload 3 x In continuous • Current overload 3 x In continuous
25 x In for 3s 25 x In for 3s
50 x In for 1s 50 x In for 1s
• Voltage input range 63.5 to 440V, Vn • Voltage input range 63.5 to 440V, Vn
• Voltage range of use 0 to 150% Vn • Voltage range of use 0 to 150% Vn
• Voltage burden 0.1VA • Voltage burden 0.1VA
• Voltage overload 1.5 x Vn continuous • Voltage overload 1.5 x Vn continuous
2 x Vn for 10s 2 x Vn for 10s
• Frequency range 45/55 or 55/65Hz • Frequency range 45/55 or 55/65Hz

• Acuracy of the analogue output


• Nominal accuracy 0.2% of reading TRANSDUCER OUTPUTS
• Current reference range 10 to 160% In
• Voltage reference range 80 to 120% Vn True zero outputs Model number
reference
• Pulse output contact rating 0 … 1mA A
• Maximum switching power 10W, 10VA 0 … 5mA B
• Maximum switching voltage 125Vdc, 250Vac 0 … 8mA C
• Maximum switching current 0.5A 0 … 10mA D
• Isolation 0 …. 20mA E
750V rms between open circuits, 0 … 5 … 10mA H
1kVrms between analogue output and relay 1 … 0 … 1mA J
contacts 10 … 0 … 10mA K
0 ... 10V L
10 ...0...10V M
> Watts, Vars, phase angle and power factor 0 ... 5V N
5 ...0...5V P
These transducers can be supplied with either an ac
or dc auxiliary power supply with the exception of the Biased outputs Model number
reference
3WF# and 3RF # which also have the option of
using the 3B Dc/Dc converter. These transducers 4 … 20mA F
require a full specification before manufacture can 4 … 12 … 20mA G
take place, these settings cannot be changed by the
user.

Connection Watts Vars Phase AUXILIARY SUPPLY OPTIONS


Angle

single phase 3WA 3RA 3PA AC Voltage Model number


reference
3 phase, 3WB 3RB 3PB
3 wire balanced, Self powered A
1El 63.5V B
69.3V C
3 phase, 3WC 3RN 3PC
4 wire balanced, 1El 100V D
110V E
3 phase, 3WD 3RD 3PD
115V F
3 wire unbalanced,2 El
120V G
3 phase, 3WE 3RH 3PE
208V H
4 wire unbalanced, 2.5 El
220V J
3 phase, 3WF # 3RF # N/a 230V V
4 wire unbalanced, 3 El 240V K
Phase difference N/a N/a 3PG 380V L
415V M
• Acuracy of the analogue output 440V N
Nominal accuracy 0.19% of reading
plus 0.01% full scale
DC Voltage Model number
except 3P which are reference
+1 degree
24V P
Current reference range 10 to 160% In 32V R
Voltage reference range 3W 40 to 150% Vn 48V S
3R 40 to 150% Vn 110V T
3P 20 to 150% Vn . 125V U
12V W
From 3B converter X
4>5
> Tap Position Indication > 3B DC/DC CONVERTER

The 3DA indicates the tap position by measuring the The 3B provides an isolated DC/DC power supply
tap resistance proportional to the actual tap with the exception of the 3BG which is non isolated.
position. The 3DA has a maximum of 33 taps. The 3B is only designed for use with the ISTAT I300
transducer.
These transducers require a full specification before
manufacture can take place, these settings cannot The type and output voltage are:
be changed by the user 3BA 24V dc 3BD 110V dc
3BB 32V dc 3BE 125V dc
• Technical specification
3BC 48V dc 3BG 220/48V dc
• Resistance input 50 to 10,000 ohms
• Input impedance 1M ohm

• Acuracy of the analogue output ORDERING INFORMATION


• Nominal accuracy 0.5%
> The ISTAT I300 model number comprises of 10 digits, the first 6
designates the basic type of transducer whilst the next 3 are specific
> Tap Position Indication resistor box to the customers precise configuration. The last digit is for design
suffix.
The 3EA is a resistor box that is used with the 3DA
1 2 3 4 5 6
to show the position of the tap changer. Each case
has 26 terminals and so a maximum of 25 resistors 3 W D K E 5
can be wired out. Basic Type, eg Watt 3ph 3wire
See Transducer output table, page 4
See Auxiliary Supply Options table, page 4
> DC Voltage and current
Frequency
Depending on the transducer, the following information is also required :
The 3DB voltage and 3DC current transducers
measure DC values and convert them to a Input parameters
proportional DC analogue value. Voltage, Current and power in secondary values
Transformer ratios and voltage, current and power in primarly values
These transducers require a full specification before
manufacture can take place, these settings cannot Scaling information : Output parameters
be changed by the user How is the analogue output configured, is it based on primary or
secondary values, and what do the maximum and minimum analogue
outputs scale to.
• Technical specification
> 3B DC/DC CONVERTER
• Current nominal input 1mA to 20mA
The DC/DC converter follows a different model numbering system
• Current range of use 0 to 120% In
using only 6 digits.
• Voltage input range 10mV to 500V
• Voltage range of use 0 to 120% Vn 1 2 3 4 5 6
• Input impedance 1M ohm 3 B C 0 0 1
(10mV to 1V dc) Basic Type, eg 48V
1K ohm/V Number of outputs, eg 1or 2 (note)
(1V to 500V dc)
Note : the 3BG has only a single output, but this can be used to supply
upto 8 3BC 48V converters.
• Acuracy of the analogue output
• Nominal accuracy 0.2% > 3EA RESISTOR BOX
• Current reference range 0 to 120% In The 3EA resistor box has 9 digits in the model number, the first 3
identify the type, the next 2 digits the number of resistors, the next
• Voltage reference range 0 to 120% Vn
3 digits the resistor values and the last digit being the design suffix.
1 2 3 4 5 6 7 8 9
3 E A 2 2 3 9 0 B
Type
Number of resistors, eg 22
Resistor value, eg 390 ohms
Design suffix, eg B

A special 3EA resistor box has been designed for use with the
MICOM KVGC voltage regulation relay, this is called 3EA22A390A

ISTAT I300:
comprehensive
dc measurement range
> Resistance • Dc Technical specification
• Voltage input 12 to 125V, Vx
The 3DL (3-wire measurement) transducer • Operating range 80 to 140% Vx
measures a resistance value and converts this to a • Power supply burden 2VA
proportional DC analogue value. The 3DL is
designed for use with PT100 temperature probes.
> Compliance and open circuit voltage
These transducers require a full specification before on the analogue output
manufacture can take place, these settings cannot
be changed by the user. • Compliance voltage 15V (note below)
• Open circuit voltage 25V
• Technical specification
• Resistence input 10 to 300 ohms Note: The compliance voltage for mean sensing 0...1mA
• Input impedance 1M ohm output is 12V, for combined Watt/Var is 11V.

• Acuracy of the analogue output


• Nominal accuracy 0.5% > Temperature

Reference range 0 … 50 C
> Temperature (thermocouple) except 3F 0 …. 40 C
Temperature 0.008%/ C
The 3DH transducer measures temperature and co-efficient except 3VX 0.04%/C
converts this to a proportional DC analogue value. 3F class 0.1Hz 0.004%/C
The 3DH is designed for use with thermocouples. 3F class 0.01Hz 0.001%/C
The 3DJ also offers cold junction compensation 3P 0.02 degree / C
(CJC). Nominal -10 . . . +60 C
range of use
These transducers require a full specification before
manufacture can take place, these settings cannot
be changed by the user. > Applicable standards

• Technical specification • Isolation


• Voltage input 5mV to 50mV, Vn 4kV rms 50Hz for 60 seconds
• Input range 0 to 120% Vn
• Input impedance 1M ohm • Impulse test
5kV (1.2/50us) for BS923 and IEC 60255-22-1

• Acuracy of the analogue output • Surge withstand


• Nominal accuracy 1.0% IEC 60255-22-1 and ANSI C37-90A IEEE std 472
SWC where applicable
• Voltage reference range 0 to 100% Vn

• Electromagnetic compatibility
EN50081-2:1994 Emissions
TECHNICAL SPECIFICATION EN50082-2:1995 Immunity
Directive 89/336/EEC

> Auxiliary supply • Safety requirements


EN61010-1:1993
Directive 72/23/EEC
Transducers can be supplied as self powered,
dc or ac powered.
• Humidity, non condensing
93% RH
• Ac Technical specification
• Voltage input 63.5 to 440V , Vx
• Operating range 80 to 120% Vx
• Frequency range 45 - 65Hz
• Power supply burden 2VA

6>7
CASE OUTLINE AND FIXING DETAILS

Detachable terminal covers


1,5
120
55

74
35 78
55

Terminal 10,7 Terminal DIN rail fixing 3


No.1 pitch 35 x 7,5 DIN rail
to spec EN 50 022
(B.S. 5584) 2 Holes Ø5,4 to accept M5 stud fixing
as alternative to DIN rail

128 60

40
7,5

Outline of 55mm case

Detachable terminal covers


1,5
150 120

55 74
35 78

10,7 Terminal
Terminal No.1 pitch DIN rail fixing 3
35 x 7,5 DIN rail
to spec EN 50 022
(B.S. 5584)

4 Holes Ø5,4 to accept M5 stud fixing


as alternative to DIN rail

128
60

135
7,5
Outline of 150 mm case
ISTAT and MiCOM are registered trademarks of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-I300-BR-07.05-1039-GB - © - AREVA - 2005. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
http://www.areva-td.com/contactcentre/ design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
Tel.: +44 (0) 1785 250 070 should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
www.areva-td.com it. We cannot be held responsible for any reliance on any
decisions taken on its contents without specific advice.
www.areva-td.com/measurements