High Accuracy Analogue
Transducers
APPLICATIONS
ISTAT I300 analogue transducers provide local and remote indication for precision
electrical measurement and control when used with instruments, data loggers
and SCADA systems.
ISTAT I300 transducers have been designed to provide highly accurate and
Customer Benefits reliable measurements for integration into control systems. The transducer
• Comprehensive set design was based on research into the market needs on an international and
of measurements industrial scale.
AREVA T&D
ISTAT I300
Features and benefits
DC MODEL RANGE
BENEFITS
Model Application Case
3DA Tap Position Indicator 150mm > Significant gains in overall system accuracy can result
3DB Voltage 150mm from improvements in source measurement
3DC Current 150mm
3DD Summation 150mm > Compliance with international standards ensures
3DH Thermocouple 150mm transducers can be used world wide
3DL 3 wire Resistance 150mm
3DJ Thermocouple with CJC 150mm > Long life expectancy and very reliable operation in
most climates
DC/DC CONVERTER RANGE > Quick and simple means of transducer selection
ISTAT I300:
Used by Industrial or Utility engineers,
at all voltage levels
2>3
RANGE • Technical specification
• Current nominal input 1 or 5A In
> AC Mean Sensing Current and Voltage • Current range of use 0 to 200% In
• Current burden 1.0VA
The 3CA current and 3VA voltage transducers will • Current overload 3 x In continuous
only require an external power supply if a biased 25 x In for 3s
4…20mA output is required. These transducers
50 x In for 1s
require a full specification before manufacture can
take place, these settings cannot be changed by the • Voltage input range 63.5 to 440Vn
user. The 3CC and 3VC are triple versions and are • Voltage range of use 0 to 150% Vn
housed in the larger 150mm case. • Voltage burden 0.1VA
• Voltage overload 1.5 x Vn continuous
• Technical specification 2 x Vn for 10s
• Current nominal input 1 or 5A In • Frequency range 45/55 or 55/65Hz
• Current range of use 0 to 200% In
• Current burden 1.5VA (0.6VA • Acuracy of the analogue output
biased output) • Nominal accuracy 0.2%
• Current overload 3 x In continuous • Current reference range 20 to 200% In
25 x In for 3s • Voltage reference range 25 to 150% Vn
50 x In for 1s
• Voltage input range 63.5 to 440Vn
• Voltage range of use 0 to 150% Vn > Frequency
• Voltage burden 1.0VA (0.3VA
biased output) The 3F frequency transducer can be supplied with
• Voltage overload 1.5 x Vn continuous an accuracy of either 0.1% or 0.01%. It can be
2 x Vn for 10s supplied with either an ac or dc auxiliary power
• Frequency range 45/55 or 55/65Hz supply. These transducers require a full
specification before manufacture can take place,
these settings cannot be changed by the user.
• Acuracy of the analogue output
• Nominal accuracy 0.2% 0.1% 0.01%
• Current reference range 0 to 200% In 45 … 55Hz 3FA N/a
(except biased output 0 to 100% In) 55 … 65Hz 3FB N/a
• Voltage reference range 25 to 150% Vn 48 … 52Hz 3FC 3FE
(except biased output 20 to 100% Vn) 58 … 62Hz 3FD 3FF
47 … 53Hz N/a 3FG
Connection Wh
single phase 3KA
3 phase, 3 wire balanced, 1El 3KB
3 phase, 4 wire balanced, 1El 3KC
ISTAT I300: 3 phase, 3 wire unbalanced, 2 El 3KD
comprehensive 3 phase, 4 wire unbalanced, 2.5 El 3KE
3 phase, 4 wire unbalanced, 3 El 3KF
ac measurement range
• Technical specification • Technical specification
• Current nominal input 1A or 5A In • Current nominal input 1A or 5A In
• Current range of use 0 to 160% In • Current range of use 0 to 160% In
• Current burden 0.3VA • Current burden 0.3VA
• Current overload 3 x In continuous • Current overload 3 x In continuous
25 x In for 3s 25 x In for 3s
50 x In for 1s 50 x In for 1s
• Voltage input range 63.5 to 440V, Vn • Voltage input range 63.5 to 440V, Vn
• Voltage range of use 0 to 150% Vn • Voltage range of use 0 to 150% Vn
• Voltage burden 0.1VA • Voltage burden 0.1VA
• Voltage overload 1.5 x Vn continuous • Voltage overload 1.5 x Vn continuous
2 x Vn for 10s 2 x Vn for 10s
• Frequency range 45/55 or 55/65Hz • Frequency range 45/55 or 55/65Hz
The 3DA indicates the tap position by measuring the The 3B provides an isolated DC/DC power supply
tap resistance proportional to the actual tap with the exception of the 3BG which is non isolated.
position. The 3DA has a maximum of 33 taps. The 3B is only designed for use with the ISTAT I300
transducer.
These transducers require a full specification before
manufacture can take place, these settings cannot The type and output voltage are:
be changed by the user 3BA 24V dc 3BD 110V dc
3BB 32V dc 3BE 125V dc
• Technical specification
3BC 48V dc 3BG 220/48V dc
• Resistance input 50 to 10,000 ohms
• Input impedance 1M ohm
A special 3EA resistor box has been designed for use with the
MICOM KVGC voltage regulation relay, this is called 3EA22A390A
ISTAT I300:
comprehensive
dc measurement range
> Resistance • Dc Technical specification
• Voltage input 12 to 125V, Vx
The 3DL (3-wire measurement) transducer • Operating range 80 to 140% Vx
measures a resistance value and converts this to a • Power supply burden 2VA
proportional DC analogue value. The 3DL is
designed for use with PT100 temperature probes.
> Compliance and open circuit voltage
These transducers require a full specification before on the analogue output
manufacture can take place, these settings cannot
be changed by the user. • Compliance voltage 15V (note below)
• Open circuit voltage 25V
• Technical specification
• Resistence input 10 to 300 ohms Note: The compliance voltage for mean sensing 0...1mA
• Input impedance 1M ohm output is 12V, for combined Watt/Var is 11V.
Reference range 0 … 50 C
> Temperature (thermocouple) except 3F 0 …. 40 C
Temperature 0.008%/ C
The 3DH transducer measures temperature and co-efficient except 3VX 0.04%/C
converts this to a proportional DC analogue value. 3F class 0.1Hz 0.004%/C
The 3DH is designed for use with thermocouples. 3F class 0.01Hz 0.001%/C
The 3DJ also offers cold junction compensation 3P 0.02 degree / C
(CJC). Nominal -10 . . . +60 C
range of use
These transducers require a full specification before
manufacture can take place, these settings cannot
be changed by the user. > Applicable standards
• Electromagnetic compatibility
EN50081-2:1994 Emissions
TECHNICAL SPECIFICATION EN50082-2:1995 Immunity
Directive 89/336/EEC
6>7
CASE OUTLINE AND FIXING DETAILS
74
35 78
55
128 60
40
7,5
55 74
35 78
10,7 Terminal
Terminal No.1 pitch DIN rail fixing 3
35 x 7,5 DIN rail
to spec EN 50 022
(B.S. 5584)
128
60
135
7,5
Outline of 150 mm case
ISTAT and MiCOM are registered trademarks of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-I300-BR-07.05-1039-GB - © - AREVA - 2005. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
http://www.areva-td.com/contactcentre/ design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
Tel.: +44 (0) 1785 250 070 should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
www.areva-td.com it. We cannot be held responsible for any reliance on any
decisions taken on its contents without specific advice.
www.areva-td.com/measurements