1 Height Of Oil Tank (H) 3 m

2 Diameter of Oil Tank (D) 2 m


3 Area of A1 and A2 21.991149 m^2
4 Number of Oil tank 6
5 Number of oil tank caught in fire 2
6 Total Surface Area (A) 43.982297 m^2
7 Supply Duration (T) 60 min
8 Supply volume density 10.2 (lit/min)/m^2
9 Water Flow Rate (Q) 448.61943 (lit/min)
10 No of Nozzle 28
11 K-Factor 64 (lit/min)/(bar)^.05
12 Operating Pressure at Nozzle 1.4 bar
13 Water flow at Nozzle 75.725821 lit/min
14 Hose Stream Allowance 946 Lit/min
15 Estimated increased water hydraulic 10 %
16 Total Water Supply 92044.882 lit
17 92.0445 m^3
NFPA 13 Standards

Ordinary Hazards NFPA 13-11.2.3.1.2