3 Area of A1 and A2 21.991149 m^2 4 Number of Oil tank 6 5 Number of oil tank caught in fire 2 6 Total Surface Area (A) 43.982297 m^2 7 Supply Duration (T) 60 min 8 Supply volume density 10.2 (lit/min)/m^2 9 Water Flow Rate (Q) 448.61943 (lit/min) 10 No of Nozzle 28 11 K-Factor 64 (lit/min)/(bar)^.05 12 Operating Pressure at Nozzle 1.4 bar 13 Water flow at Nozzle 75.725821 lit/min 14 Hose Stream Allowance 946 Lit/min 15 Estimated increased water hydraulic 10 % 16 Total Water Supply 92044.882 lit 17 92.0445 m^3 NFPA 13 Standards