You are on page 1of 3

PHUKOT HEP (FIRE FIGHTING SYSTEM)

Number of units 6
Generator: CO2 Fire Fighting System
1 Height of generator 3.9 m
2 Diameter of generator 7.1 m
3 Volume of generator 154.4085 m^3 assuming 65% of space inside generator is vacant, whe
4 Volume of CO2 occupancy 100.3655 m^3 will be supplied

Source: Modern Hydro Electric Practice in India: Volu


5 Minimum design concentration for CO2 30 % Mechanical Auxuliaries System
6 FOS 1.5
7 Required CO2 concentration 45 %
8 Volume of CO2 required 45.16448 m^3
9 Density of CO2 1.98 kg/m^3
10 Mass of CO2 required 89.42568 kg
11 weight of unit CO2 cylinder 45.4 kg
12 Number of CO2 cylinder 1.969729 units. for 1 generator
Total number of CO2 cylinder requierd 11.81837
13 units.
for all 6 generators for 6 generator
~12 units.
DIMENSION

generator is vacant, where CO2


supplied

ric Practice in India: Volume-II,


xuliaries System

Weight
S.N. lb kg

1 50 22.7

2 75 34
3 100 45.4
References:
Industrial CO2 extinguishing Systems
Design, Installation and Maintenance Manual

Actuation type:
1 Electrical
2 Manual
3 Pneumatic

You might also like