You are on page 1of 1

1.

Location : Control Room /CRP Panel

Feeder Name : Incomer Relay panel

2. Name plate details:

3. Secondary Injection Test:

3.1. MEASUREMENT:

Ref Applied Sec Voltage (A) Measured Voltage At Relay (KV)


R 63.5 132
Y 63.5 132
B 63.5 132

3.2 VECTOR JUMP TEST:

Ref Applied Sec Voltage (A) Operating time(sec)


R 63.5 ∟10o 0.046
Y 63.5∟-110o
B 63.5∟130o

4. FUNCTIONAL CHECKS:

Binary Inputs Checked OK


Binary Output Checked OK
LED Checks Checked OK
Relay to 86 Trip Checked OK
Breaker failure tripped to Upstream Checked OK

5. RESULT : Relay Found Healthy.