EHV XLPE – Current Rating


APRIL 26, 2011 11 COMMENTS
Jignesh.Parmar
EHV XLPE Cable:

Blog Stats
3.8 / 6.6 KV(6.6 KV Earthed) Single Core AL/COPPER COND, XLPE INSULATED CABLES As per IS:7098 (Part-II)
15,295,254 hits
ARMOURED CABLE

About Jignesh Parmar:


Short Circuit Current
Cross-
Rating for Jignesh Parmar has completed M.Tech (Power
sectional Normal Current Rating in Amps
Overall 1Sec.duration in K.
System Control), B.E(Electrical). He is member
area
Diameter Amps of Institution of Engineers (MIE) and CEng,India.
(Sq MM)
(mm) Membership No:M-1473586.He has more than
Aluminum Conductor Copper Conductor 16 years experience in Transmission -
Aluminum Copper
Distribution-Electrical Energy theft detection-

Ground Duct Air Ground Duct Air Electrical Maintenance-Electrical Projects


(Planning-Designing-Technical Review-
1cX25 23 100 90 120 130 115 155 2.35 3.58coordination -Execution). He is Presently

105 associate with one of the leading business group


1cX 35 24 120 145 155 140 185 3.29 5.00as a Deputy Manager at Ahmedabad,India. He
has published numbers of Technical Articles in
125
“Electrical Mirror”, “Electrical India”, “Lighting
1cX50 25 140 170 185 160 220 4.70 7.15
India”,”Smart Energy”, “Industrial
155 Electrix”(Australian Power Publications)
1cX70 27 175 215 225 195 275 6.58 10.01
Magazines. He is Freelancer Programmer of
Advance Excel and design useful Excel base
180
1cX 95 28 205 260 265 235 340 8.93 Electrical Programs as per IS, NEC, IEC,IEEE
13.59
codes. He is Technical Blogger and Familiar with
205 English, Hindi, Gujarati, French languages. He
1cX120 30 235 305 300 265 390 11.28 17.16
wants to Share his experience & Knowledge and
230 help technical enthusiasts to find suitable
1cX150 32 260 345 335 295 440 14.10 solutions and updating themselves on various
21.45
Engineering Topics.
260
1cX185 34 295 395 380 330 510 17.39 26.46

300 Follow Blog via Email


1cX240 37 340 470 435 380 600 22.56 34.32
Enter your email address to follow this blog and
335 receive notifications of new posts by email.
1cX300 39 385 540 490 425 680 28.20 42.90
Join 12,051 other followers
440
1cX400 44 0.57 380 630 550 480 790 Enter your email address
37.60

1cX 500 495 Follow This Blog by Email


47 0.60 430 730 610 530 910 47.00

1cX 630 560


51 This site uses
Privacy & Cookies: 0.67cookies. By continuing
480 to use 840 680 to their
this website, you agree 580use. 1030 59.22
Close and accept
To find out more, including how to control cookies, see here: Cookie Policy
1cX800 57 0.76 620 530 960 740 630 1140 75.20 Follow
Electrical Notes-…
1cX1000 680 22K likes
61 0.82 580 1070 790 670 1250 94.00

3.8 / 6.6 KV(6.6 KV Earthed) Three Core AL/COPPER COND, XLPE INSULATED CABLES As per IS:7098 (Part-II) Like Page

ARMOURED CABLE
BUY ELECTRICAL NOTES IN PDF
Short Circuit Current
Cross-
Rating for
sectional Normal Current Rating in Amps
Overall 1Sec.duration in K.
area
Diameter Amps
(Sq MM)
(mm)
Aluminum Conductor Copper Conductor
Aluminum Copper
BUY ELECTRICAL SOFTWARES
Ground Duct Air Ground Duct Air

3cX 25 40 95 82 105 120 105 135 2.35 3.58

3cX 35 42 115 97 125 145 125 165 3.29 5.01

115
3cX 50 45 130 150 170 150 195 4.70 7.15

140 BUY ELECTRICAL NOTE IN PDF


3cX 70 49 160 190 210 180 240 6.58 10.01

165
3cX 95 54 190 230 250 215 295 8.93 13.59

3cX 120 190


58 220 260 280 240 335 11.28 17.16

3cX 150 210


61 245 295 310 270 380 14.10 21.45BUY ELECTRICAL SOFTWARES.
3cX 185 240
65 275 335 350 305 430 17.39 26.46

3cX 240 275


72 315 395 400 350 500 22.56 34.32

3cX 300 310


77 355 450 445 390 570 28.20 42.90
Proud to be an IndiBlogger
3cX 400 350
electricalnotes.wordpress.c...
88 400 520 500 440 650 37.60 57.20

6.6 / 11 KV (6.6KV Un-Earthed/ 11 KV Earthed) Single Core AL/COPPER COND, XLPE INSULATED, CABLES As per
IS:7098 (Part-II)
85 /100

ARMOURED CABLE

Short Circuit Current SEARCH


Cross-
Rating for
sectional Normal Current Rating in Amps
1Sec.duration in K.
area
Overall Copyright © 2018
Diameter Amps
(Sq MM)
The content in electricalnotes.wordpress.com is
(mm)
Aluminum Conductor Copper Conductor for personal, non-commercial use only. you can
Aluminum Copper
not reproduce,republish or communicate any of
the content , including files downloadable from
Ground Duct Air Ground Duct Air
this website, without the permission of the
1cX25 24 100 90 120 130 115 155 2.35 3.58copyright owner.The use of this content on any

105 other websites breaches copyright Act. If You


1cX 35 25 120 145 155 140 185 3.29 5.00find this content in any other site,it makes the
page you are viewing an infringement of the
1cX50 26 140 125 170 185 160 220 4.70 7.15
copyright.
155 Recent Posts
1cX70 28 175 215 225 195 275 6.58 10.01
Electrical Thumb Rules-VENTILATION &
180
CEILING FAN
1cX 95 30 205 260 265 235 340 8.93 13.59
Electrical Thumb Rules-Light Sources
205
Quick Reference-Fire Fighting (Part-2)
1cX120 32 235 305 300 265 390 11.28 17.16
Quick Reference-Fire Fighting (Part-1)
230
1cX150 33 260 345 335 295 440 14.10 Electrical Thumb Rule- High Rise Building (As
21.45
per NBC)
260
1cX185 36 295 395 380 330 510 17.39 Calculate Motor Pump Size
26.46

300 Calculate Size of Cable for Motor (As NEC)


1cX240 39 340 470 435 380 600 22.56 34.32
How to Design efficient Street lighting-(Part-6)
335 How to Design efficient Street lighting-(Part-5)
1cX300 41 385 540 490 425 680 28.20 42.90
How to Design efficient Street lighting-(Part-4)
380
How to Design efficient Street lighting-(Part-3)
1cX400 44 440 630 550 480 790 37.60 57.20
How to Design efficient Street lighting-(Part-2)
1cX 500 430
47 495 730 610 530 910 47.00 How to Design efficient Street lighting-(Part-1)
71.50

1cX 630 480 1030 Calculate Size of Pole Foundation & Wind

51 560 840 680 580 59.22 Pressure on Pole


90.10
Calculate Size of Circuit Breaker/ Fuse for
530 1140 114.40
Transformer (As per NEC)
1cX800 57 620 960 740 630 75.20
Selection of Various Types of UPS (Part-2)
1cX1000 580 1070 1250 143.00
61 680 790 670 94.00 Selection of Various Types of UPS (Part-1)

Electrical Thumb Rules-Illumination-(Part-19).

Electrical Thumb Rules-Illumination-(Part-18).


6.6 / 11 KV (6.6KV Un-Earthed/ 11 KV Earthed) Three Core AL/COPPER COND, XLPE INSULATED, CABLES As per
IS:7098 (Part-II) Electrical Thumb Rules-Illumination-(Part-17).

ARMOURED CABLE
Archives
Short Circuit Current
November 2019 (1)
Cross-
Rating for
sectional Normal Current Rating in Amps October 2019 (2)
Overall 1Sec.duration in K.
area September 2019 (2)
Diameter Amps
(Sq MM)
(mm) August 2019 (2)
Aluminum Conductor Copper Conductor
Aluminum July 2019 (2)
Copper
June 2019 (1)
Ground Duct Air Ground Duct Air
May 2019 (2)
3cX 25 43 95 82 105 120 105 135 2.35 3.58
April 2019 (3)
3cX 35 46 115 97 125 145 125 165 3.29 5.01
March 2019 (2)
115
3cX 50 50 130 150 170 150 195 4.70 7.15February 2019 (2)

140 January 2019 (3)

3cX 70 54 160 190 210 180 240 6.58 10.01


December 2018 (2)

165 November 2018 (2)


3cX 95 58 190 230 250 215 295 8.93 13.59
October 2018 (1)
3cX 120 190
September 2018 (2)
62 220 260 280 240 335 11.28 17.16
August 2018 (3)
3cX 150 210
July 2018 (1)
65 245 295 310 270 380 14.10 21.45
June 2018 (1)
3cX 185 240
70 275 335 350 305 430 17.39 May 2018 (1)
26.46
3cX 240 76 315 275 395 400 350 500 22.56 34.32
April 2018 (1)

March 2018 (1)


3cX 300 310
February 2018 (2)
80 355 450 445 390 570 28.20 42.90
January 2018 (1)
3cX 400 350
December 2017 (1)
90 400 520 500 440 650 37.60 57.20
November 2017 (1)

October 2017 (1)


11 KV(11 KV Un-Earthed) Single Core AL/COPPER COND., XLPE INSULATED CABLES As per IS:7098 (Part-II)
September 2017 (1)

ARMOURED CABLE August 2017 (1)

July 2017 (2)


Short Circuit Current
Cross- June 2017 (1)
Rating for
sectional Normal Current Rating in Amps
May 2017 (1)
1Sec.duration in K.
Overall
area
Diameter Amps
(Sq MM) April 2017 (1)
(mm)
March 2017 (1)
Aluminum Conductor Copper Conductor
Aluminum Copper
February 2017 (1)

Ground Duct Air Ground Duct Air January 2017 (1)

1cX25 28 100 90 120 130 115 155 2.35 3.58December 2016 (1)

105 November 2016 (1)


1cX 35 29 120 145 155 140 185 3.29 5.00
October 2016 (1)
125 September 2016 (1)
1cX50 31 140 170 185 160 220 4.70 7.15
August 2016 (1)
155
July 2016 (1)
1cX70 33 175 215 225 195 275 6.58 10.01
June 2016 (1)
180
1cX 95 34 205 260 265 235 340 8.93 May 2016 (1)
13.59

205 April 2016 (2)


1cX120 37 235 305 300 265 390 11.28 17.16
March 2016 (2)

230 February 2016 (2)


1cX150 38 260 345 335 295 440 14.10 21.45
January 2016 (2)
260
December 2015 (1)
1cX185 40 295 395 380 330 510 17.39 26.46
November 2015 (1)
300
October 2015 (2)
1cX240 43 340 470 435 380 600 22.56 34.32
September 2015 (1)
335
1cX300 44 385 540 490 425 680 28.20 42.90
August 2015 (1)

380 July 2015 (1)


1cX400 48 440 630 550 480 790 37.60 57.20
June 2015 (1)
1cX 500 430 May 2015 (1)
53 495 730 610 530 910 47.00 71.50
April 2015 (1)
1cX 630 480 1030
March 2015 (2)
56 560 840 680 580 59.22 90.10
February 2015 (2)
530 1140 114.40
1cX800 61 620 960 740 630 75.20 January 2015 (2)

1cX1000 580 1070 1250 December 2014 (2)


143.00
65 680 790 670 94.00 November 2014 (2)

October 2014 (2)

11 KV(11 KV Un-Earthed) Three Core AL/COPPER COND., XLPE INSULATED CABLES As per IS:7098 (Part-II) September 2014 (2)

August 2014 (3)


Cross- ARMOURED CABLE
July 2014 (2)
sectional
area Overall Normal Current Rating in Amps June 2014 (2)
Short Circuit Current
(Sq MM) Diameter Rating for May 2014 (2)
(mm) 1Sec.duration in K.
April 2014 (2)
Amps
March 2014 (3)

Aluminum Conductor Copper Conductor February 2014 (4)


Aluminum Copper
January 2014 (2)
Ground Duct Air Ground Duct Air
December 2013 (1)
3cX 25 54 95 82 105 120 105 135 2.35 3.58
November 2013 (1)
3cX 35 57 115 97 125 145 125 165 3.29 5.01
October 2013 (2)
115
September 2013 (3)
3cX 50 60 130 150 170 150 195 4.70 7.15
August 2013 (3)
140
July 2013 (3)
3cX 70 64 160 190 210 180 240 6.58 10.01
June 2013 (3)
165
3cX 95 69 190 230 250 215 295 8.93 May 2013 (3)
13.59

3cX 120 190 April 2013 (2)


73 220 260 280 240 335 11.28 17.16
March 2013 (3)

3cX 150 210 February 2013 (2)


76 245 295 310 270 380 14.10 21.45
January 2013 (3)
3cX 185 240
December 2012 (2)
80 275 335 350 305 430 17.39 26.46
November 2012 (3)
3cX 240 275
85 315 395 400 350 500 22.56 October 2012 (1)
34.32
September 2012 (3)
3cX 300 310
91 355 450 445 390 570 28.20 42.90
August 2012 (7)

3cX 400 350 July 2012 (2)


98 400 520 500 440 650 37.60 57.20
May 2012 (7)

April 2012 (2)

March 2012 (3)

February 2012 (2)


38 / 66KV (66 KV Un-Earthed) single Core AL COND, XLPE INSULATED CABLES
January 2012 (1)

Cross-sectional ARMOURED CABLE December 2011 (3)


area (Sq MM November 2011 (2)
Overall Diameter Weight Current Rating in Amps
October 2011 (4)
(mm)
September 2011 (2)
Ground Duct
August 2011 (1)
51 2700 195 240 June 2011 (5)
1cX 95
May 2011 (3)
53 2900 220 280
1cX120 April 2011 (12)

55 3300 240 335 March 2011 (17)


1cX150

58 3600 275 380


1cX185 EEP
60 3900 320 450
1cX240

62 4300 360 510


1cX300

66 4900 410 595


1cX400

69 5300 460 690


1cX 500

75 6400 525 800


1cX 630
1cX800 79 7300 590 910

84 8400 650 1010


1cX1000

Rate this:
8 Votes

Share this:
 Facebook  Email  LinkedIn  More

Like
Be the first to like this. Pages
Abstract

Related Abstract of CPWD-Part 1

Abstract of IE Rules
XLPE Cable-Current Rating PCV Cable-Current Rating
With 194 comments With 18 comments Abstract of IS Code.

IS 1255

Cable Construction & Cable Selection- Part:4 IS 15652/11171/1445/1678


With 15 comments
IS 3043 / 5039

IS 5613

FILED UNDER UNCATEGORIZED IS 694 / 1554 / 11892

IE Rules for DP Structure

About Jignesh.Parmar Electrical Notes

Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of ElectRICAL. Q&A
Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16
Electrical Q&A Part-1
years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical
Electrical Q&A Part-2
Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has published Electrical Q&A Part-3
numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial
Electrical Q&A Part-4
Electrix”(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance Excel and design
useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with Electrical.Tool
English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and help technical
EXCEL TOOL
enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.

Top Clicks
11 Responses to EHV XLPE – Current Rating electricalnotes.files.wor…

electricalnotes.files.wor…
jigar says:
mediafire.com/file/5040ut…
August 8, 2011 at 4:21 pm
instamojo.com/jiguparmar/…
please,help me to find the losses of cable.
mediafire.com/file/0qu8mt…
i wanna find losses of cable of 400 sq mm. 33 kv. 3080 mtr length
mediafire.com/file/bkzwat…
is there any cap. effect include in it???
electricalnotes.files.wor…
Reply
mediafire.com/file/vc7vfk…

CHANDRASHEKHAR M says:
July 6, 2012 at 4:53 pm
Recent Comments
Dr Mukesh Kumar on Electrical Thumb
FOR 22 KV GRADE ,XLPE CABLE , THREE CORE ,EARTHED CABLE WHAT SHOULD BE THE FAULT
Rules-VENTILA…
CURRENT
Muhammad Mohsin Ansa… on Electrical
Reply Thumb Rules-VENTILA…
Muhammad Mohsin Ansa… on Electrical
Thumb Rules-Light…
Faisal Cm says:
Muhammad Mohsin Ansa… on Quick
November 6, 2013 at 1:49 pm
Reference-Fire Fighting…
Sir we got a cable work of 1cx800 sq mm copper cable ,length/drum=600 m, what kind(power)of electric winch Nikhil Garde on Quick Reference-Fire
require for this cable? Fighting…
J.Sridharan on Electrical Thumb Rule- High
Reply
Ri…
Muhammad Mohsin Ansa… on Electrical
Jignesh.Parmar says:
Thumb Rule- High Ri…
November 6, 2013 at 1:55 pm
AKHIL S M on Current Transformer
Not getting Point ?? Subhabrata Sarkar on Calculate Motor
Pump Size
Reply
Muhammad Mohsin Ansa… on Calculate
Motor Pump Size

BS VAIDYA says:
August 21, 2014 at 3:47 pm

I want to use 400 sq. mm XLPE cables for 66 KV sub station. Is there any restriction from GETCO/DGVCL?

Reply

yousuf khan says:


September 3, 2014 at 11:06 am

Dear Sir, i need information above EHV Cable more than 1000 Sq mm cable details current ratings.

Reply

Mohammed Shiyas says:


November 6, 2014 at 6:53 am

Dear Sir,
How to find maximum short circuit current to calculate min. conductor size in 1C X 630 Sq mm Armoured XLPE
cable.

Reply

Saju says:
May 10, 2015 at 9:29 am

Sir,

what size of pvc sleeve using for 240mm Sq. cable

Reply

Chandrahas says:
July 31, 2015 at 7:12 am

Which is best insulation LV cable types for long distance in size of 3.5 core in 300 mm aluminium

Reply

Chandrahas says:
July 31, 2015 at 8:11 am

Please suggest chart for selection of LV Cables size 3.5 core X 300 mm in Aluminium conductor for length approx
230 meters

Reply
Dinesh says:
January 18, 2016 at 5:11 pm

Dear Sir what about voltage levels above 66 KV

Reply

Leave a Reply

Enter your comment here...

This site uses Akismet to reduce spam. Learn how your comment data is processed.

You might also like