You are on page 1of 4

SCHEDULE OF EXHAUST AIR FANS

ELECTRIC MOTOR
AIR
AREA A/U QTY FLOW E.S.P
SR NO ITEM CODE ITEM TYPE SERVED RATE (Pa) POWER SUPPLY kW
(I/S)

EF/9 GENTS TOILET/ABLUTION


1 ROOF EXTRACTOR TYPE NOS 1 1130 400 400V/ 3ø /50HZ
LEV-1
EF/6 GENTS TOILET
2 ROOF EXTRACTOR TYPE NOS 1 280 250 400V/ 3ø /50HZ
LEV-2
EF/7
3 ROOF EXTRACTOR TYPE LADIES TOILET NOS 1 380 250 400V/ 3ø /50HZ
LEV-2
EF/8 LADIES TOILET /ABLUTION/
4 ROOF EXTRACTOR TYPE NOS 1 1000 250 400V/ 3ø /50HZ
LEV-2 BABY ROOM/STORE
EF/9 GENTS TOILET/ABLUTION
5 ROOF EXTRACTOR TYPE NOS 1 1130 250 400V/ 3ø /50HZ
LEV-2

EF/10-1
TO
6 ROOF EXTRACTOR TYPE LADIES AND GENTS TOILETS-CIP NOS 2 170 250 400V/ 3ø /50HZ
EF/10-2
LEV-2

EF/11
7 ROOF EXTRACTOR TYPE PANTRY-CIP NOS 1 50 250 400V/ 3ø /50HZ
LEV-2

EF/12-1
TO
8 ROOF EXTRACTOR TYPE SMOKING ROOM NOS 2 600 250 400V/ 3ø /50HZ
EF/12-2
LEV-2

EF/1-1
9 TO CELING MOUNTED EXHAUST FAN TOILET NOS 2 45 150 230V/ 1ø /50HZ
EF/1-2

EF/2-1
10 TO PROPELLER TYPE FAN TOILET NOS 14 70 50 230V/ 1ø /50HZ
EF/2-14
EF/3-1
11 TO PROPELLER TYPE FAN TOILET NOS 2 120 50 230V/ 1ø /50HZ
EF/3-2

EF/4-1
12 TO PROPELLER TYPE FAN STORE/KITCHEN NOS 2 230 50 230V/ 1ø /50HZ
EF/4-2

EF/5-1 STORE/PANTRY
13 TO PROPELLER TYPE FAN NOS 2 280 50 230V/ 1ø /50HZ
MEZZANINE
EF/5-2
S

SERVICE MANUFACTURER COMPLIED STATE REMARKS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS

CONTINUOUS
CONTINUOUS

CONTINUOUS

CONTINUOUS