Current Transducer HAL 50 .. 600-S IPN = 50 ..

600 A
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.

Electrical data
Type Primary nominal Primary current,
rms current measuring range Features
IPN (A) IPM (A)
HAL 50-S 50 ±150 ●● Hall effect measuring principle
HAL 100-S 100 ±300 ●● Insulating plastic case recognized
HAL 200-S 200 ±600 according to UL 94-V0.
HAL 300-S 300 ±900
HAL 400-S 400 ±1000
Advantages
HAL 500-S 500 ±1000 ●● Easy installation
HAL 600-S 600 ±1000 ●● Low power consumption
ÎP Overload capability (Ampere Turns) 30000 At ●● Small size and space saving
Vout Output voltage (Analog) @ ±IPN ±4 V ●● Only one design for wide current
RL Load resistance @ TA = 0 °C .. 70 °C >1 kΩ ratings range
@ TA = -25 °C .. +85 °C >3 kΩ ●● High immunity to external
UC Supply voltage (±5 %) ±15 V interference.
IC Current consumption <±25 mA
RIS Insulation resistance @ 500 V DC >500 MΩ Applications
Accuracy - Dynamic performance data ●● AC variable speed drives and
servo motor drives
X Accuracy @ IPN, TA = 25 °C, ±15 V <±1 % of IPN
●● Static converters for DC motor
εL Linearity error 1) <±0.5 % of IPN
drivers
VOE Electrical offset voltage @ TA = 25 °C HAL 50-S <±20 mV
●● Battery supplied applications
HAL 100 .. 600-S <±10 mV
●● Uninterruptible Power Supplies
VOM Magnetic offset voltage @ IP = 0,
(UPS)
after an overload of 3 × IPN
●● Switched Mode Power Supplies
HAL 50-S <±30 mV
(SMPS)
HAL 100 .. 200-S <±20 mV
●● Power suppliers for welding
HAL 300 .. 600-S <±10 mV
applications.
TCVOE Temperature coefficient of VOE HAL 50-S <±2.0 mV/K
HAL 100 .. 600-S <±1.0 mV/K Application domain
TCVout Temperature coefficient of Vout (% of reading) <±0.05 %/K
tr Step response time to 90 % of IPN ≤3 µs ●● Industrial.
BW Frequency bandwidth (-3 dB) 2) DC .. 50 kHz

General data
TA Ambient operating temperature -25 .. +85 °C
TS Ambient storage temperature -25 .. +85 °C
m Mass 75 g
Standards EN 50178: 1997
UL 508: 2010
Deviation in output when tested to EN 61000-4-6 <20 % of IPN
Deviation in output when tested to EN 61000-4-3 <20 % of IPN
Notes: 1) Excludes the electrical offset
2)
Derating is needed to avoid excessive core heating at high frequency.

N° 60.62.25.000.4, N° 60.62.34.000.4, N° 60.62.44.000.4, N° 60.62.46.000.4, N° 60.62.48.000.4, N° 60.62.50.000.4, N° 60.62.50.000.4 Page 1/4

1July2015/version 7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
UL 508:Ratings and assumptions of certification HAL 50 .. 600-S
File # E189713 Volume: 2 Section: 1

Standards
●● CSA C22.2 NO. 14 - 10 INDUSTRIAL CONTROL EQUIPMENT - Edition 11 - Revision Date 2011/08/01
●● UL 508 STANDARD FOR INDUSTRIAL CONTROL EQUIPMENT - Edition 17 - Revision Date 2010/04/15.

Parameter Symbol Unit Value


Primary involved potential V AC/DC 300
Max surrounding air temperature TA °C 80

According to series primary


Primary current IP A
currents

Secondary supply voltage UC V DC ±15


Output voltage Vout V 0 to 4

Conditions of acceptability

When installed in the end-use equipment, consideration shall be given to the following:
1 - These devices must be mounted in a suitable end-use enclosure.
2 - The terminals have not been evaluated for field wiring.
3 - Low voltage circuits are intended to be powered by a circuit derived from an isolating source (such as a transformer,optical
isolator,limiting impedance or electro-mechanical relay) and having no direct connection back to the primary circuit (other
than through the grounding means).
4 - Base on results of temperature tests, in the end use application, a maximum of 100 °C cannot be exceeded at soldering
point between primary coil pin and soldering point of on the primary bus bar (corrected to the appropriate evaluated max.
surrounding air).

Marking

Only those products bearing the UL or UR Mark should be considered to be Listed or Recognized and covered under UL’s
Follow-Up Service.Always look for the Mark on the product.

Page 2/4

1July2015/version 7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer HAL 50 .. 600-S

Insulation coordination
U d Rms voltage for AC insulation test, 50 Hz/1 min 3 kV
ÛW Impluse withstand voltage 1.2/50 µs >8 kV
Min
dCp Creepage distance 12.1 mm
dCI Clearance 9.8 mm
CTI Comparative tracking index (group I) 600

Applications examples

According to EN 50178 and IEC 61010-1 standards and following conditions:

●● Over voltage category OV 3


●● Pollution degree PD2
●● Non-uniform field

EN 50178 IEC 61010-1


dCp, dCI, ÛW Rated insulation voltage Nominal voltage
Basic insulation 1000 V 1000 V
Reinforced insulation 600 V 300 V

Safety

This transducer must be used in limited-energy secondary circuits according to


IEC 61010-1.

This transducer must be used in electric/electronic equipment with respect to


applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.

Caution, risk of electrical shock

When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.

Page 3/4

1July2015/version 7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions HAL 50 .. 600-S (in mm)

第一视角

第三视角

Connection
第一视角
IP Connection
UC
第三视角
IP
UC
RM
IP
UC
UC RM

RM
UC

UC

dCl

dCl dCp

Mechanical characteristics Remarks


●● General tolerance ±0.5 mm ●● Vout is positive when IP flows in the direction of the arrow.
●● Transducer fastening 3 holes ⌀ 4.5 ●● Temperature of the primary conductor should not exceed
3 M4 steel screws 90 °C.
Recommended fastening torque 1.2 N·m (±10 %) ●● Installation of the transducer must be done unless
●● Primary through-hole 20.5 × 15 mm otherwise specified on the datasheet, according to LEM
●● Connection of secondary Molex 5045-04A
Transducer Generic Mounting Rules. Please refer to
LEM document N°ANE120504 available on our Web site:
Products/Product Documentation.
●● Dynamic performances (di/dt and response time) are
best with a single bar completely filling the primary hole.
●● This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.

Page 4/4

1July2015/version 7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com