You are on page 1of 34

Design Guide to

Underfloor
Air Distribution

1
Design Guide to Underfloor Air Distribution

INTRODUCTION types of office moves is often referred to as


churn.
The concept of underfloor air is not new,
however changes in office space usage,
The costs associated with these churn moves
sustainable design and indoor air quality
are one of the largest costs an owner / tenant
issues have sparked considerable recent
may face. The costs associated with cabling
interest in the concept. Underfloor air
moves and to a lesser extent HVAC system
conditioning had its start in computer rooms,
are the major portion of these move costs.
at a time when mainframe computers
So a system that could greatly simplify the
generated considerable heat and had a
costs associated with churn moves could
considerable amount of complex cabling
help reduce total system life cycle cost. The
required by the computers. Access floor
advantage of access flooring is that cable
systems allowed plenty of open space to run
and HVAC moves are greatly simplified.
cabling and a generous pathway to supply
large quantities of cooling air under the
intense heat of the electronics. The natural
convection currents of warm air rising
Improved comfort
allowed cool air to enter low, cool the The second feature of underfloor air
equipment and remove the warm air near the distribution (UFAD) was that the same
ceiling. Of course today’s computer rooms principle of warm air rising from hot
have changed and the need for this type of electrical gear could also be applied to warm
cooling has decreased. However, access air around people. BOMA (Building Owners
floor systems have found new markets. and Managers Association) reported in their
“What Tenants Want Survey” that thermal
and indoor air quality concerns were two of
Reduced life cycle cost the top concerns and least met expectations
of tenants. Traditional overhead air
The recent interest in access floor systems
distribution systems are designed to do a
has been spurred by other applications that
very good job of mixing the air in the space
can make use of the two principles that these
and prevent stratification in the room.
earlier computer room systems addressed.
Without increased complexity and cost
First, the large open floor plenum was a
delivering thermal comfort to every
convenient space to run large amounts of
occupant while also providing personal
cable for power and communications. The
ventilation may be cost prohibitive.
greatest change in offices in the last 15 years
Overhead systems may require more fan
has been an ever-growing need for voice,
energy to overcome static losses of
data and power connections to every
generating the mixing, airflow patterns
worker’s workstation. This coupled with one
required within the space.
other trend in office space design that is the
use of more open plan space and a trend to
Delivery of ventilation air requires sufficient
move workers into cross-functional
mixing to assure that the ventilation
workgroups with great regularity. IFMA
component is delivered to the occupied
(International Facility Management
breathing zone. By applying the warm air
Association) reported in one of their recent
rising principle, air can be provided below
surveys that on average an office worker
the occupants and discharged directly into
experiences a move every 5-½ months; this
the breathing zone at relatively low velocity.
is 44 percent move rate. The term for these
The people warm the air and by natural

2
Design Guide to Underfloor Air Distribution

convection the air rises toward the ceiling. comfortable, and provides better ventilation
Since people only breath air in a zone from and improved indoor air quality.
approximately the floor to 6 feet, the space
above this zone can be treated as a stratified The application of an underfloor air
air layer and the load components in this distribution system requires the system
zone treated differently. The result is that air designer to view the design very differently.
provided underfloor can be supplied at low It requires special consideration throughout
pressure and the energy for space the design process from design schematic
conditioning can be reduced. The ventilation stage, to load estimate, to commissioning.
air can be provided in the zone where it is This document is intended to provide the
needed most with pollutants moved gently designer with some of the guidelines to
toward the return. Additionally, adjustable follow in systems design of underfloor air
diffusers, which discharge air to small areas distribution, UFAD. Further in depth
in the space, may be adjustable by the analysis of all aspects of UFAD design can
occupant and can result in an improvement be found in the ASHRAE UFAD Design
in personal thermal comfort. This results in Guide.
a system that can be more energy efficient,

Figure 1 – Typical Underfloor Air Distribution System

3
Design Guide to Underfloor Air Distribution

UFAD System Benefits without primary usage of the flooring systems is to


special air-handling provide a service and utility space to run
cabling for voice, data and power. As a
Several types of underfloor system designs
result, the floors can be as little as 4 inches
exist. This manual covers a system offered
over the structural floor or they may be
by Carrier Corporation (see Fig. 3c). This
much higher. When the floor space is to be
approach employs standard air handling
used as a supply plenum for air distribution,
equipment and uses duct supply
floor heights are normally at 12 to 18 inches
temperatures in the normal air conditioning
high.
range, which can best handle spot cooling
requirements that often arise on every
project. The air is distributed in the space
through a pressurized plenum with swirl
style floor grilles. The plenum is supplied
through a zone parallel fan power box with a
special DDC control to modulate
temperature and controls plenum pressure.
The primary damper provides the minimum
ventilation air to the zone and maintains
plenum pressure. The ECM style fan motor
in the box modulates to mix return and
Figure 2 – Access Flooring System
primary air to maintain required
temperature. Heating and cooling
Access floor systems are successfully
requirements for specialized high load
applied to many types of buildings both new
spaces and perimeter zones are handled with
construction and renovation. However, when
conventional overhead systems, underfloor
applied to retrofit situations a few special
series fan boxes or fan coil units.
considerations are required. Elevator lobbies
and bathrooms which are built on the
original structural floor need to be raised to
APPLICATION the new floor elevation or ramps provided to
CONSIDERATIONS get from the structural floor heights to the
raised floor height.
Access flooring systems
An access floor is a flooring system that is In new construction one architectural
installed above the standard structural floor consideration of the floor systems is that a
of the building. We will reference Haworth ceiling space could be reduced allowing a
Access Flooring System in our discussions floor-to-floor height one foot less than
(see Fig 2). The systems consist of a matrix standard. This can be accomplished by
of adjustable pedestals mounted normally on either the use of open ceiling space with
two-foot centers, which support the weight only lighting and sprinklers in the space, or
of the access floor panels and the loads on by reducing the ceiling plenum space since
the floor above. The two-by-two, large supply ducts are not required. Then for
approximately 1-1/8 inches thick concrete every 12 stories of building an additional
floor panels are laid into this grid system. story could be added with minimal
The structural floor below is normally sealed additional cost in the building shell cost. In
to provide a moisture and dust barrier. The buildings less than 12 stories the reduction

4
Design Guide to Underfloor Air Distribution

in height would result in a reduction of 3.) The third concept is to provide


overall building shell cost. airflow from underfloor that is
controlled at the workstation. This
method is called Task Ambient
Basic Concepts Conditioning. The control is
A traditional underfloor air distribution normally accomplished with a small
system uses the floor space between the fan that directs an air jet at the
structural floor and the access floor as a occupant within the workstation.
supply air plenum.
We will use the UFAD approach in this
There are three concepts normally manual. The plenum may be configured
associated with providing floor level using one of two approaches. Either the
cooling, each with distinctive entire underfloor plenum is pressurized to a
characteristics: relative low pressure of approximately 0.10
1.) Displacement ventilation discharges inch WG or air is discharged into the
air horizontally near the floor at very plenum at zero or neutral pressure and fans
low velocities and near laminar flow near the outlets draw the supply air from the
conditions. The goal is to use only plenum and discharge it to the space.
the buoyancy effects to create air Neutral pressure plenums have a reduction
motion within the space and in leakage around floor tiles and plenum
maintain the stratification layer penetrations, but fan wiring and energy costs
above the controlled zone that is not negate some of the system’s inherent
mixed. While this provides excellent benefits. The use of the underfloor plenum
ventilation effectiveness in the has two major impacts on system design.
occupied zone it is not the optimum
solution for thermal comfort. This is First, since the air is brought in at floor
because of wide temperature level, a chance exits for a cold floor or for
variance, greater than the, ASHRAE cold discharge temperatures near the
(Std 55) accepted, 3 to 5 degree occupant’s feet. Both conditions are
spread from head to toe. objectionable so the air must be provided at
a much warmer temperature than normal air
2.) Under Floor Air Distribution conditioning levels. The accepted level is
(UFAD) uses the same buoyancy between 61 F to 65F. This impacts
principles as displacement however equipment selection and operation, and
the air is discharged into the space impacts air distribution devices. The second
with adequate velocity and air issue is that the large surface area and mass
pattern to provide mixing only of the structural slab provide both a thermal
within the occupied zone. The mass that shifts load patterns and creates
system still tries to maintain the significant amounts of thermal decay to
stagnant zone above the breathing diffusers located far from the point at which
zone. The system provides a more supply air enters the plenum.
uniform temperature variation in the
occupied zone to stay within the Conditioned air is handled in one of two
comfort envelope. methods. The first method is when the space
return air is removed near the ceiling and the
entire volume returned to the air-handler.

5
Design Guide to Underfloor Air Distribution

This method requires special treatment by Figure 3 – Basic System Design


the air-handler to bypass the required air and Options
condition the required supply amount
without losing control of temperature and 3a. Conventional Overhead Distribution
particularly humidity in the space (see 78°F Return to AHU
55°F Supply from AHU
fig.3b). The second approach is to use a
mixing box located near the space that 78°F
draws a portion of the return air near the
ceiling and mixes it with the supply air to
maintain the floor plenum pressure and
temperature. The Carrier system discussed
here uses the second method (fig.3c). 75°F 75°F

Perimeter zones and spaces such as


conference rooms present some interesting
challenges. These spaces have loads which
vary greatly with time and which may have air
requirements that cannot be handled by 65-
3b. UFAD with Full Return
degree air. To provide for these spot cooling 84°F Return to AHU
situations either a fan powered box is provided 62°F Supply to AHU
under the floor to increase airflow or a
separate unit that can use standard 55-degree 84°F
air can be used. A fan coil unit located under RETURN RETURN

the floor can also be used to provide for the


cooling and heating needs. When 55-degree
air is supplied to zone mixing units, the 75°F 75°F
system may also employ traditional methods
used with overhead air distribution, to meet
62°F
high load requirements. 62°F

Heating along the perimeter also presents


challenges for UFAD systems. To provide the
necessary heat, terminal units are frequently
provided to addresses this situation. One very 3c. UFAD with Zone Mixing Unit
common method is to use a fan coil unit that 84°F Return to AHU
55°F Supply from AHU
may be placed under the floor and near the
perimeter. The fan coil contains a heating coil,
electric or hot water and it is controlled to 84°F
overcome transmission losses.
84°F

75°F 75°F

62°F

6
Design Guide to Underfloor Air Distribution

Product Overview
A second type of diffuser is used with
underfloor mixing boxes and perimeter fan
Floor plenum - The space between the
coil units. This rectangular grille is used to
access floor and the structural floor is the
provide an air curtain washing exterior
floor plenum. Using this space as an air
surfaces with warm or cold air. These grilles
distribution plenum requires some special
depend on much higher velocities and can
considerations. First the floor panel seams
be used in various lengths to match the
must provide a tight seal to prevent air
airflow requirements of the mixing box or
leakage from the plenum into the space. In
fan coil unit. Either a 0° or 15° deflection
some cases ductwork is run through the
blade can be used to provide the required
space to special variable load areas and the
throw pattern. A version of the rectangular
space may need partitioning for life safety or
grilles can also be installed in a plenum that
thermal zoning. A typical underfloor
has a control damper to provide variable
plenum is between 12 and 18 inches in
volume control to selected spaces. The
height.
rectangular grilles can also be used to allow
return air from above the floor back down to
Diffusers – Room air distribution is the underfloor mixing boxes if desired. If
accomplished through one of two types of
used directly in the pressurized plenum, a
floor diffusers. Interior spaces are controlled
standard balancing damper can be added to
through a system of adjustable passive floor
adjust airflow.
mounted diffusers. Each diffuser consists of
an adjustable swirl plate located in a
mounting basket and mounts through a hole
cut in the concrete floor panel. The basket
catches any dirt or spilled liquids and
prevents contamination of the space below
the floor. The adjustable swirl plate allows
the occupants to adjust their diffusers to a
comfortable level in their space. The
diffusers are design to achieve mixing of the
approximately 65 F degree supply air within
a very tight radius of the diffuser and at very
low velocity. Typical diffuser airflow is
about 60 to 100 CFM per diffuser.

Figure 5 Rectangular grille w/


plenum – Model 35BF-D

Figure 4 Swirl Plate


Style – Model 35BF-R

7
Design Guide to Underfloor Air Distribution

Underfloor series fan powered Fan powered zone-mixing unit –


mixing boxes – These units are One box is used per plenum temperature
designed to fit underfloor in the space zone and is mounted in a closet or utility
between pedestals and the grids of the space to control the airflow to the underfloor
access flooring system. Size ranges from plenum. The product uses a standard Carrier
280 CFM to 1200 CFM. They are used for DDC controller configured for UFAD on a
perimeter spaces, conference rooms and parallel fan powered box to control the
other spaces with a highly variable load temperature and pressure of the zone. The
pattern. They typically use supply air from box uses standard 55°F supply air from an
the floor plenum and increase the volume air source and blends the air with return air
delivered to the room to meet the variable from the zone to provide the 63°F discharge
needs. The same style box can be used with air required in the plenum. The ECM motor
ducted primary air when that option is in the box varies speed as required to control
required to meet high thermal load plenum temperature by varying the amount
requirements. Heating can be provided with of recirculated air introduced into the
either hot water coils or with electric plenum, while the primary air damper
heaters. simultaneously maintains the plenum
pressure by controlling the amount of
primary air introduced into the plenum.
Minimum position stops assure that
ventilation air is always provided. Plenum
pressure is maintained at approximately
0.05-0.10 - inch WG.

Figure 6 – Underfloor Series Fan


Power Mixing Box – Model 45UC

Underfloor perimeter fan coil


boxes – These are another option to
handle spaces with variable loads patterns
and are well suited to addressing heating
requirements of perimeter zones. Available
in size from 325 to 2800 CFM these fan coil
units also fit underfloor in the space between
pedestals and the grids of the access flooring
system. Heating is provided in these with
either a hot water coil or an electric heater.
Figure 8 – Fan Powered Zone
Mixing Unit – Model 45XC

Figure 7 –Underfloor Perimeter Fan


Coils – Model 42KC

8
Design Guide to Underfloor Air Distribution

Central equipment – Since this system high perimeter to interior ratios or buildings
uses a zone mixing concept and air is with many spaces, which have highly
supplied at normal unit design conditions, variable loads. Normally, the best
special air-handling equipment is not applications in new construction spaces are
required. Mixing boxes may be used with offices with open plan construction. UFAD
air-handlers in chilled water or DX type may also be used successfully in other types
systems or with many types of packaged of space with mostly internal loads and open
VAV equipment as well. Careful plan construction, as is done in some schools
psychrometric analysis should be made of spaces.
coil entering conditions to be sure the coil
will meet the required leaving air conditions The second application is in retrofit
particular to what may be higher than situations where the building characteristics
normal entering sensible heat factors. Part make overhead air distribution systems
load operating conditions in terms of coil difficult to apply. Recent trends to
control or staging should be evaluated to be rehabilitate old warehouse space into offices
sure room humidity levels can be maintained and downtown revitalization of existing
below 60% RH. Economizers should be structures may fall into this category. The
used with all system types where local issues with elevator and plumbing fixture
climate permits and should use an integrated connections must be addressed. However,
differential enthalpy type control. Because the savings and ease of providing the
of low static pressure requirements, fan sizes cabling services and air distribution under
may be lower than conventional overhead the floor may well pay for the cost of access
systems. Due to varying air volumes to the flooring. The benefits of improved thermal
zones, the use of VFD’s is recommended, comfort and indoor air quality may make the
which will also improve system efficiency. space even more attractive to tenants.
The use of high-quality filtration is
recommend since a prime consideration of A third area where underfloor distribution
the UFAD system is good indoor air quality. may make sense is in buildings with very
high ceilings and no place to run overhead
Types of Buildings air distribution. Some places of assembly
Underfloor air systems are not the answer to (meeting rooms, churches, auditoriums) fit
every building but may represent significant into this category. Again, open plan and
life cycle cost savings when applied to the internal load concentration are the keys to
appropriate buildings. successful applications.

The solution is most often related to three System benefits and cautions
different types of applications. First, UFAD (+) Thermal comfort – Since UFAD
can be applied in new construction office systems allow the occupant a degree of
space where frequent office changes are control over ones own individual climate
anticipated. Owners can benefit from the through adjustment of the diffuser; there
reduced costs of moving offices particularly is a higher degree of perceived comfort.
as related to the cost of communications Air distribution diffusers have also been
cable and wiring. In general small spaces shown to provide good head to toe
within a building are not well suited to temperature variations without
underfloor air systems. Nor does UFAD disrupting the benefits of a stratification
make good sense in a building with very zone.

9
Design Guide to Underfloor Air Distribution

associated with office churn, UFAD


(+) Ventilation effectiveness – Fresh systems may have better total life cycle
air supply is introduced to the space low costs. In addition, this energy efficient
to the floor. As the air warms the air design will also increase the life cycle
rises and pollutants are carried toward cost benefit and may make the system
the ceiling by the warm air. Rather than look more appealing.
mixing the air within the entire space,
fresh air is provided to the breathing (+) Reduced Floor-to-Floor Height
zone. The effect of this ventilation – The ability to reduce the floor-to-floor
method may actually result in height by up to one foot per floor can
efficiencies greater than 100%, but has result in additional floor space or
not yet been documented. ASHRAE reduced shell construction cost. The
Standard 62, (Table 6.2) lists the reduction comes from reducing or
ventilation efficiency of UFAD systems eliminating ceiling plenums. However,
at 100%. The perceived indoor air this reduction must be evaluated based
quality is better and may potentially be on the need for ceilings to hide light
used to reduce total ventilation airflow, fixtures, piping for sprinklers, and to
although this is not generally help improve room acoustics.
recommended.
(+) Improved productivity and
health – It is often a controversial
thing to prove but recent studies have
shown that productivity can be improved
through good indoor air quality and
comfort. Since the costs associated with
employees far out weigh all other
operating costs, savings can be
significant.

(-) Cold floor – One of the most sensitive


points of thermal comfort on the body is
the ankle. Control of floor temperature
can be a critical issue in order to avoid
Figure 9 – Thermal Plume Effect complaints due to the radiant effects
from a cold floor. Also, the sensitivity to
cold drafts as the result of floor diffuser
(+) Energy usage – UFAD systems placement is an issue that should be
may have significant energy savings adequately addressed.
when compared to overhead air systems
because of lower fan static requirements. (-) Code issues – UFAD technology as
Economizer hours of operation may it is being applied is relatively new and
increase energy savings as well, but is not all building code officials may know
highly dependent on the local climate. how to interpret the codes as applied to
the technology. The result is that some
(+) Reduced Life Cycle Costs – life safety components such as fire
Based on the reduction in costs resistant materials, sprinklers and smoke

10
Design Guide to Underfloor Air Distribution

detectors may be required on certain This standard sets green building objectives
projects. in 5 categories that offer a total of 32 credits,
from which a design can accumulate up to
(-) Condensation – Even though the 69 points. The rating system is based on the
thermal mass effects of the plenum floor number of points awarded and goes from a
slabs can have a positive effect on certified level at 29 to platinum level at 52.
sensible load swings, care needs to be Some prerequisite requirements are
exercised with control schemes that pre- required, but other than that, the points may
cool the slab and then are allowed to come from any of the 5 categories. HVAC
bring in large quantities of potentially related systems account for 40% of the
moist outdoor air. Air supplied to the possible points. The points are based on the
underfloor plenum must be kept above entire building as a system. No particular
the dewpoint temperature of the floor product or system is certified by the
slab. program but rather the building in which
they are used. Underfloor air systems have
(-) Humidity control – The impact of potential in at least seven areas, primarily
local climate and part load control within the environmental and indoor air
methodologies must be carefully quality areas.
evaluated. The impact of higher supply
air temperatures has the potential to The largest points area in the program is
negate some of the central system’s optimizing energy performance. This credit
natural latent heat removal capability. varies from 1 point for exceeding ASHRAE
Design analysis should evaluate the 90.1 energy cost budget (ECB) model by
effects of part load latent control and 15%, up to 10 points for a 60% reduction. In
control methodology to make sure room most UFAD projects the analysis would
relative humidity is kept below 60%. involve using the ASHRAE energy cost
budget to compare the underfloor system to
Sustainability (LEED™ points) the energy costs of a VAV reheat system.
There is a nationwide trend toward
constructing buildings that are more UFAD systems may have a distinct
environmentally friendly to meet green advantage in this area since they incorporate
building or sustainable design construction many potential energy saving features.
standards. The best known green building Lower fan static requirements as the result
standard is the LEED-NC™ standard issued of low plenum pressure distribution will
by the U.S. Green Building council, but reduce required fan energy. Mechanical
additional standards like the LEED-CI for cooling requirements and hence equipment
interior systems is also being prototyped. size and part load efficiency may be
The LEED (Leadership in Energy and improved due to the use of higher discharge
Environmental Design) standards are a temperatures. Economizer usage may be
voluntary rating system that rates the extended to get more free cooling hours and
building design on its environmental impact help reduce part load energy requirements.
on the community, the site, the water In general, UFAD systems have the
efficiency, the energy efficiency and the potential to show significant energy savings
indoor environmental quality for the over the required base system used in the
occupants. energy budget model.

11
Design Guide to Underfloor Air Distribution

The UFAD system may also qualify for comfort envelope, the system can qualify for
points under the material and resources this credit as well.
category. Within this category 3 points can
be earned for building reuse. If the project UFAD has shown itself to be an excellent
involves an existing building, the percentage system to consider on projects seeking
of building shell reuse would help obtain LEED certification. Remember, however,
these credits. UFAD systems lend that certification is based on the total
themselves very well to certain retrofit building system and the points and overall
situations where the building is being rating for a specific project are dependent on
renovated to meet the requirements of new the design of that project.
technology without destroying the current
building structure. UFAD gives the architect
a range of options to achieve these goals.
Then, depending on the location, it is
possible that the floor system used would
qualify for the regional credit if the project
were within 200 or 500 miles of the
equipment manufacturing location.

Looking at the Indoor Environmental


Quality category, UFAD systems have the
potential to qualify for points in 3 areas.
This is the area where many of the existing
certified projects have relied on points from
UFAD systems. The first is the area of
ventilation effectiveness. UFAD systems are
not rated by ASHRAE as having any
advantage in ventilation effectiveness as we
noted earlier. However, in the current
LEED documentation, it is implied to have
ventilation effectiveness greater than one.
As a result, the use of UFAD systems may
be a qualifying point. The second area
addresses system controllability, where the
LEED requirement is for interior zones to
provide individual control to at least 50% of
the occupants. Since UFAD diffuser
provides individual control inherently, the
system again is nearly an automatic
qualification for this point. The third area
relates to thermal comfort. Since UFAD
systems have been shown to provide a high
degree of personal comfort with space
control parameters that fall within the
guidelines of the ASHRAE standard 55

12
Design Guide to Underfloor Air Distribution

DESIGN PROCESS So for a typical side-fed core


location the maximum zone size
would be 120 ft by 60 ft, or 7200 ft2
Design Decisions or less.
When beginning the design of a UFAD • Open office interior zones, those that
system certain key differences and concepts have fairly uniform loading, lend
need to be remembered to avoid themselves to pressurized plenums
incorporating elements of traditional using passive swirl diffusers.
overhead mixing systems: • Open area zones with loading
• Underfloor systems work best when differences are hard to “isolate” from
a stratification layer is established at one another without plenum barriers
6 feet above the access floor. This beneath the access floor. Too many
creates a partial displacement barriers destroy the future ease of
ventilation effect within the room rezoning and utility access to points
and improves ventilation of use.
effectiveness, contaminant control, • Zones with high heating loads need
heat capture, and reduces loads to consider the use of ducted linear
within the space, transferring them bar diffusers that deliver the
directly to the return air. conditioned air to the load point
• Airflows need to be closely matched (usually exterior walls with glazing)
to the loads within the occupied zone without significant thermal decay.
so as not to over air the space, losing Insulate ductwork to prevent loss of
the partial displacement ventilation cooling capacity.
effect. • Perimeter zone size may be restricted
• Mixing only occurs within the by ASHRAE 90.1, requirements for
occupied zone and happens so exposure zoning, which limits linear
efficiently that it is normal for a 3 to wall per exposure to 50 feet.
5º F temperature gradient to occur, • Locating zone-mixing terminals in
right at the ASHRAE 55 comfort vertical equipment closets does take
standard limit. up more useable floor space
Do not include excess safety factors; it will compared to locating the units within
lead to over airing the zone spaces, resulting the underfloor plenum, but is a good
in many occupant comfort complaints and choice for reasons of ease of
loss of the stratification layer. maintenance and minimizing
obstructions within the plenum.
Zoning Decisions • When high cooling or
Because of the underfloor air supply plenum dehumidification loads are present,
aspects of a UFAD system, zoning decisions such as conference rooms and rooms
have a few complexities: with plants, process or large
• Thermal decay, the increase in equipment or solar loads, consider
cooling supply air temperature due to conditioning these spaces with
heat transfer to the floor slab and traditional VAV terminals using
access flooring, limits the zone lower temperature (50 to 55ºF)
maximum travel distance from the primary air. This hybrid system
terminal discharge into the plenum to design will result in smaller central
the furthest diffuser to 50-60 feet.

13
Design Guide to Underfloor Air Distribution

equipment, as well as ductwork and equipment chases strategically


mains and branches. located around the floor plate.
• When using zone fan powered
mixing boxes (FPMB) above the
General Layout access floor the chases must provide
When beginning the layout of a UFAD adequate room to locate the terminal
system it is best to think of it as an upside as well as provide required service
down conventional overhead system, with clearances.
the following similarities and differences: • UFAD systems use diffusers in the
• Central cooling and heating access floor, much closer to the
equipment, as well as ductwork occupants, so special care needs to
mains and branches to zone mixing be exercised in their layout. Since it
terminals, can be nearly identical to is a non-ducted system, simply
traditional overhead systems.
s. swapping floor panels can make
Systems that do not employ the use relocations easy.
of zone mixing terminals require • UFAD systems work best with
special consideration based on the uniformly loaded thermal areas. In
volume and temperature from the high-load and variable-loaded zones,
air-handling source. UFAD can be used in conjunction
• Zoning occurs in much the same way with traditional overhead systems.
as with other systems, but due to the This creates an overall hybrid system
duct mains above and zoned that utilizes the best features of both
distribution plenum below, there is a types of systems (figure 10b).
need for multiple vertical duct drops
Figure 10 – Carrier UFAD Design Solutions
84° RA to Air Source

55° SA from Air Source

84°F

RETU RETURN

84°F

75°F
75°F

62°F

Zone Parallel Passive Floor Diffusers Underfloor Fan Coil or


Fan Powered mixing Box Fan Powered mixing Box

Figure 10a - UFAD with Zone Mixing Box

14
Design Guide to Underfloor Air Distribution

UFAD Hybrid System


84° F Return to Air Source
55° F Supply from Air Source VAV Moduline Terminal

84 ° F
RETUR RETUR

84 ° F

75°F
75°F

62°F

Zone Parallel Fan Powered Passive Floor Diffusers Underfloor Fan Coil or Series
mixing Box
Fan Powered Mixing Box

Figure 10b - UFAD Hybrid System

15
Design Guide to Underfloor Air Distribution

Building Load Considerations • Lighting energy is predominantly


radiant; so only assign 1/3rd of total
NEED FOR TWO ZONES - With an watts directly to the stratified zone.
effective stratification layer, running cooling When return air is taken through the
and heating zone loads for use with a UFAD light troffers, a greater portion of the
system is complex. The claim that loads total watts used, up to 50 percent,
that occur in the upper stratified zone do not can be assigned to the stratified zone.
affect the occupied zone have been observed • Exterior wall conductive load is still
in tests and completed projects, but to date, transferred into the zone as
no computerized load estimating program is predominantly radiant (often over 60
capable of modeling this condition. Using percent), so only 1/3rd of the upper
recent project experience, and not being wall area load should be assigned to
conservative in assigning loads or safety the stratified zone.
factors to the occupied space can reduce • Alternatively, lowering the zone
space cfm requirements with a UFAD ceiling height to the midpoint value
system. of the stratified zone would allow
most computerized load programs to
automatically assign the loads
addressed above to the return air.
• Solar loading through glazing is 100
percent radiant, unless internal
shading is used. Since manually
adjusted shades cannot be counted
on when sizing equipment or setting
airflows, do not assign any direct
solar load to the stratified zone.
• Solar wall loading becomes over
1/3rd convective, so an appreciable
portion of this amount can be
manually assigned to the upper
stratified zone, especially if wall-
Figure 11 – UFAD Design Load Concepts washing linear bar supply registers
and overhead perimeter returns are
used in the room air distribution
LOAD ESTIMATING CONCEPTS & design.
FACTORS - Manual output adjustment of • People loads should always remain
computer program inputs and outputs allow 100 percent assigned to the occupied
designers to more closely model UFAD zone.
systems and correctly assign loads and set • Equipment loading should not be
zone airflows. assigned to the stratified zone unless
• For stratification to benefit cooling return register placement near the
loads, floor diffuser 50 fpm throw equipment is used to capture a
cannot exceed 4 to 5 feet, so as not to portion of the load with the return
affect the stratification height, which air, or it is believed that aggressive
is typically 6 feet. thermal plumes will develop and

16
Design Guide to Underfloor Air Distribution

carry a substantial portion of the load T AHU Supply is the assumed primary
into the stratification zone. air temperature into the zone-mixing
• Infiltration loads always remain box.
within the occupied zone, and
outdoor air ventilation loads always 3. Finally, solve for TReturn from the
remain a part of the central stratified zone. This is the return air
equipment coil loading. temperature to the zone mixing box,
and the air handler before outdoor air
When the load estimates have been run with mixing occurs.
appropriate UFAD adjustments made, two
loads should be compiled by the designer,
TReturn = (Qunoccupied /1.10 * CFMroom)+ Troom
QOCCUPIED for the lower mixed zone, and
QUNOCCUPIED for the stratified zone above the Equation 3
stratification height. With these loads the Where:
designer can then calculate the following TRoom is the thermostat set point for the
system design parameters: space, and
1. First, solve for airflow in the occupied CFMRoom is the airflow required in the
zone. This is the supply air delivered occupied zone.
by the underfloor diffusers (the zone
mixing box total airflow). DON’T OVER AIR THE ZONE - When
working with Equation 1, the space set point
CFM room = Qoccupied / (1.10 * (Troom – T plenum supply)) temperature, TRoom, can be raised up closer
to the temperature at the stratification height
Equation 1 (approximately 75 F) to more accurately
determine the actual minimum airflow
Where: required to meet the occupied zone load.
TRoom is the thermostat set point for Similarly, in Equation 3, TRoom should use
the space, and the same higher value, remembering that
with UFAD systems and the partial
TPlenum Supply is assumed discharge displacement ventilation effect, return air
air temperature in the plenum temperatures are quite a bit higher than the
space set point temperature.
2. Solve for CFM primary air required. Other load-related concerns come from air
(This is the air supply from the air leakage out of the plenum through
handler and used in zone box construction gaps, leaks between the floor
selection) tiles directly cooling the occupied zone, and
radiant and convection cooling by the cooler
Equation 2 floor panels and structural sub-floor. The
last two lower the room CFM, and if not
CFMZone-Box = Qoccupied / (1.10 * (Troom – T AHU supply))
accounted for, will lead to undesirable zone
over airing and increased “too cold”
T Room is the thermostat set point for complaints from the occupants in the space.
the space, and

17
Design Guide to Underfloor Air Distribution

Central Equipment Selection dehumidification of outdoor air. Bypassing


While a UFAD system is thought of as a return air around the cooling coil is one
predominantly air distribution design method of obtaining the required 61 to 65º F
variation, there are many particulars supply air temperature to the underfloor
affecting central equipment selection that plenum. This can be done in the mechanical
the designer needs to pay attention to, equipment room, but is also effective by
particularly: blending in the return air off the suspended
ceiling return plenum using Parallel Fan
• Central fan energy should be less
Power Mixing Boxes (PFPMB).
than a traditional system because of
the low plenum pressure and
Fan Static Requirements
substantial reduction in ductwork
downstream from the air terminal. Reduced external static pressure on the
• Primary cooling air quantities can be central equipment is an advantage of a
reduced when potential load credits UFAD system. Supply ductwork runs and
are realized from the stratification air pressure drops on the zone terminals
zone partial displacement ventilation leading to the plenums are similar to
effect. conventional systems. The same is the case
• The entering coil psychrometrics with return ducts, but there is always less
should be checked to be sure that the than 0.10 in. wg pressure requirement on the
cooling coil selected would be able underfloor plenum and diffusers
to achieve the required Apparatus downstream from the zone mixing terminals.
Dew Point (ADP) and bypass factor. While this savings of 0.25 to 0.50 in. wg
In some cases this may require the appears small, add to it the overall reduction
use of larger coils, more coil rows or in primary airflow associated with UFAD’s
lower face velocities. partial displacement effect, we should see
real reductions in system fan motor
• Part load loss of humidity control
horsepower.
can be a significant issue. A part load
analysis should be done to determine
if the coil control methodology being
used or the refrigeration staging will
Terminal Equipment Selection
provide sufficient latent heat removal
Room Air Distribution
at part load operation.
• Air economizers should be used
whenever possible based on the local OCCUPIED ZONE DELIVERY
climate. The use of an enthalpy When a UFAD system is used, room air
wheel is recommended for periods distribution occurs within the occupied zone
when the 55° F supply air (up to 6 feet above finished floor), making
temperature off the coil is not this area a critical design element. Designs
required. Use care in setting up the can be either CAV (constant air volume) or
economizer changeover temperature VAV (variable air volume), or as is more
to ensure that the 60° F maximum often the case, a hybrid using some of both
space dewpoint temperature will not to satisfy the varying room requirements.
be exceeded. CAV systems usually vary the temperature
Traditional cooling coil leaving air of the supply air to meet the space
temperatures of 50 to 55º F should be used temperature set point, while VAV systems
for the coil selection in climates requiring provide constant temperature and vary the

18
Design Guide to Underfloor Air Distribution

quantity of air supplied to the zone. These ventilation effectiveness might cause a
concepts are not as clear-cut as with designer to lower overall outdoor air
overhead systems because UFAD allows the quantities, it is recommended to retain the
occupants to easily adjust the diffusers of values derived using the assumed 100
either system to affect airflow volume and percent ventilation effectiveness found in
even pattern or direction in some instances. ASHRAE Standard 62, Ventilation for
Acceptable Indoor Air Quality. Working
Since the supply air is introduced into the with either the multiple space equation or
occupied mixing zone it has to be warmer the new ventilation rate formulas in
than traditional systems, around 61-65º F, or Standard 62-2004, you will find minimal
only 8-13º F below the usual space cooling CFM reductions for the increased ventilation
set point. To avoid comfort complaints the effectiveness (not addressed yet in
air must mix quickly into the room and not ASHRAE 62, but believed to be above 1.0
project outside the occupied zone so that the and below 1.2).
stratification zone remains intact. Tests
have shown an ideal airflow of 0.6 CFM/sqft CORE vs. PERIMETER
for good mixing, while maintaining the UFAD systems work best with spaces like
stratification height at 6 feet, and keeping core areas and open perimeters with limited
the room temperature gradient below 5º F. glass that have low load variations. These
zones tend to be larger and constant volume
designs will provide the most cost effective
installations with superior IAQ. When load
concentrations increase and/or high load
variability is present, CFM delivery to the
space can increase significantly due to the
low delta temperature of UFAD systems,
and adding VAV equipment will increase
system cost. Perimeter offices with high
glazing areas, conference rooms, and areas
with large equipment loads are examples of
zones where use of dedicated traditional
systems make the most sense. The resulting
Figure 12 – UFAD Room hybrid design makes the most of both
Temperature Gradient traditional mixing ventilation systems with
lower cooling supply air temperatures for
IAQ BENEFITS limited zones, while retaining UFAD
Real benefits from the stratification zone benefits for the base design.
and partial displacement ventilation effect
include eliminating short-circuiting to the
return registers and better heat removal, Diffuser Selection and Layout
especially of localized loading when returns
are located near the load. The overall NOT LIKE OVERHEAD
upward movement of the air within the room Since the occupant is much closer to the
has shown reduced total particulate counts diffuser in a UFAD system it must be a high
and improved local air change indexes in induction design to quickly even out the
recent studies. While such improvements in space temperature in the surrounding area

19
Design Guide to Underfloor Air Distribution

and avoid drafts and occupant comfort comprehensive information is available to


complaints. The higher supply air learn more about these UFAD refinements.
temperature of a UFAD system and the need
for quick mixing results in greater numbers Passive type diffusers can be easily
of diffusers located in the access floor. rearranged by just moving floor panels;
Since the diffusers have low pressure drops active types require moving fan units, power
and plenum pressure is very uniform, UFAD and control wiring and potentially ductwork.
designs can be considered self-balancing at Active diffusers are found more often in
the diffuser. TAC/PEM designs and as part of hybrid
solutions to satisfy heavy and/or widely
APPLYING DIFFERENT TYPES AND variable loaded spaces. UFAD diffusers
STYLES should not be used where liquid spillage
There are two basic types of diffusers to potential is high, even though they have a
choose from: passive and active. Passive are catch basin for incidental spills, and they
used in pressurized plenum systems and should not be placed in traffic areas where
active diffusers are used in neutral pressure high rolling loads are expected.
or fan-assisted pressurized plenum systems.
There are three basic styles of diffusers, To select a passive diffuser, determine the
swirl, VAV floor grille and linear bar grille. required room airflow with Equation 1 and
Passive styles are able to move required air divide it by the tabulated airflow for the
quantities at low plenum pressures (0.05 to diffuser at the pressure maintained in the
0.10 in. wg) and have very low noise plenum. This will be the approximate
generation values, usually under NC20. In number of diffusers required. Adjustments
fact, a white noise generation system within may be made to be sure all spaces receive
the plenum is often recommended for proper adequate coverage.
acoustic privacy in open office situations.

The table below summarizes the various


#Diffusers = CFMRoom/Diffuser CFMat Plenum Pressure
features and application recommendations
for these products. Use of other products, Equation 4
such as task/ambient conditioning (TAC)
and personal environmental modules (PEM), Cooling Terminal Selection
are not covered in this guide, but Each zone (thermostat) will require a
DIFFUSER DIFFUSE UNIFORM VARIABLE dedicated air terminal to satisfy cooling and
TYPE R STYLE LOADING LOADING heating airflows to the areas covered by the
Core – open zone. Larger, more uniformly loaded open
areas &
Swirl offices Base loading office interior zones can be supplied by
Passive
Perimeter – parallel fan-powered mixing boxes
open areas (PFPMB) all the way up to 3,700 CFM
Large equip.
Floor
loads, few Base loading
primary airflow (5,800 CFM mixed airflow).
grilles Smaller perimeter zones and partitioned
people

Swirl
Not Not interior zones can be handled with the same
recommended recommended equipment down to 500 CFM primary
Active Linear Bar Spaces with Conference
(fan-forced) or tighter Rooms
airflow.
Floor temperature Perimeter,
grilles tolerances Htg & Clg

20
Design Guide to Underfloor Air Distribution

Once cooling loads have been completed, Heating Terminal Selection


basic terminal selection can occur, using
traditional manual or software methods. Heating loads that are significant along a
Keep the following items in mind when perimeter wall should be handled with
selecting units for UFAD systems: dedicated ducted fan-coils located under the
access floor or from overhead. First stage of
• Primary airflow can come from a heat would be recirculated room or ceiling
traditional temperature source (50 to plenum air in larger zones, with additional
55º F +) or even from a low- zones of heat provided by either hot water or
temperature central system, keeping electric heating coils in the fan-coil. When
supply ductwork mains and branches zones have low density uniform heating
small. needs, either on the perimeter or the interior,
• Primary airflow is the airflow it is possible to provide warm-up and/or
determined with equation 2 and is zone heating using a low-profile series fan
based on the air handler supply air powered box used for cooling, with either
temperature. Total airflow is the hot water or electric heating coils.
amount calculated by equation 1
above. Remember that a UFAD system in heating
• Care must be exercised in the mode is no different than any other system;
selection of the zone mixing unit to there is a heating demand placed on the
be sure it will provide the total space by the minimum ventilation airflow
mixed airflow based on calculated setting of the terminal, determined by the
entering conditions to the zone temperature offset between the room set
mixing unit. The use of selection point and the supply air temperature to the
software is recommended. terminal.
• Since the units are closer to the
occupied space, often mounted Load/Design Considerations
vertically within an equipment
closet, care needs to be taken so that UFAD Systems will create a high degree of
acoustic values are acceptable, by personal comfort when designed with floor
keeping inlet duct pressures down, diffusers that provide a well-mixed zone in
selecting units in the low end of their the lower portion of the room. Warm return
range, and using the appropriate air travels upward through natural
acoustic attenuation options convection and is carried back to the HVAC
available. system. If the diffusers are not designed
• Optional filters on the recirculated properly, the distance the air travels from the
air opening are advisable, removing diffuser into the space could be excessive,
particulate from the return air stream causing stratified air to circulate back into
before it mixes with the primary air. the occupied space. Improper system design
could result in poor temperature control and
Control options that meet the sequences of the ability to manage building loads.
operation will be required. Control schemes
tend to be more complex with UFAD, The 35BF-R Swirl diffuser throw is a
making a DDC system a logical choice. function of both airflow and ΔT. Quite
often, space loads are over estimated.
UFAD systems were designed around

21
Design Guide to Underfloor Air Distribution

100cfm/person at a 10° FΔT from room to The temperature/velocity profiles are shown
discharge air temperature. System analysis on figure 14.
proves that with many projects, the cfm was
too great causing over cooling, and with the At the perimeter, or in conference rooms,
10° FΔT, difficult to control humidity. As a where higher cooling demand requires
result of this analysis, many current project considerably more air than in normal interior
designs have elected to reduce the supply zones, there are other considerations to
temperature in the underfloor plenum from review. With the typical supply air
66° F to 62° F and the supply airflow rate temperature of 65° F, the quantity of air may
from 1cfm/ft2 to 0.8 cfm/ft2 or less. be such that the diffuser throw may create
unwanted mixing in the upper part of the
The optimal airflow/delivery rate of the room.
35BF-R, swirl diffuser is 15° FΔT and 80
cfm per diffuser. This tested performance Figure 13 shows the performance of a
ensures the ideal throw of 6’ within the typical rectangular floor grille in a perimeter
occupied zone. Temperature and velocity zone. By lowering the diffuser discharge
profiles for the 35BF-R, swirl diffuser, have temperature, we can reduce the throw and
been measured with an anemometer avoid affecting the stratification in the
/temperature “tree” in accordance with interior zones.
ASHRAE Standard 113-90.

Figure 13 Perimeter Throw

22
Design Guide to Underfloor Air Distribution

Figure 14 Temperature/Velocity Profile Charts

23
Design Guide to Underfloor Air Distribution

Distribution System Design detailing is analogous to pressurized


stairwell and smoke-barrier
With UFAD the major differences over construction in high-rise buildings.
more conventional systems become quite Since these are not sheet metal ducts
apparent once the designer begins working governed by industry standards like
on the air distribution system. The ductwork SMACNA, engineers must work
from the air source to the zones is essentially closely with architects to assure
the same as any other all-air system, but proper design and close follow-up
with air delivery occurring underfloor there during construction to make sure the
are routing and design requirements that are work is done and done properly.
quite different than one is used to, especially • Sealing concrete floor slabs reduces
with air diffusion occurring within the particulate generation, though
occupied zone (6 inches to 6 feet above the heavier dirt accumulation within the
finished floor). plenum will not be entrained by the
low velocity airflows.
• Insulate plenum exterior surfaces,
Plenum Design Considerations both floor and sidewall, to minimize
Plenums for UFAD systems are grouped thermal losses, which can affect the
into two types, pressurized and zero- temperature of the supply air,
pressure or neutral. Pressurized are more delivered to the furthest diffusers.
common because they offer the greatest • Obstructions within the plenum
offsetting cost benefits from reduction in should be kept to less than 50% of
HVAC system components, but neutral the plenum depth to avoid affecting
plenum designs are easier to zone and are airflow. This is more an issue with
not affected by plenum air leakage. shallow plenums.
Pressurized plenums predominantly use • Plenum dividers, a part of a
passive diffusers while neutral plenums manufactured access flooring
require the use of active style diffusers. system, should be provided when
zoning is critical, as part of an
FEATURES/BENEFITS/CAUTIONS FOR architecturally determined smoke
PASSIVE PLENUMS barrier, and to separate the perimeter
The following guidelines can be used in from the core when a hybrid solution
developing a pressurized plenum design for is used.
HVAC use with passive and active diffusers. • For good acoustic privacy between
• Common plenum depths are 12-18 offices, the floor panels should
inches from top of slab to top of weigh at least 10 psf. Placing a
floor panel, with most panels being < physical barrier in the plenum along
2 inches thick. Practical minimum the common wall line provides
plenum depth is 8 inches and additional attenuation.
plenums deeper than 24 inches offer • Floor panel temperature will be
no HVAC advantages. midway between room set point and
• Airflow leakage must be designed plenum temperature, creating both a
out with superior construction radiant cooling effect, and
sealing of all joints, including convective heat transfer into the
overlapping joints when laying down plenum, lowering the required room
carpet squares. The type of required airflow.

24
Design Guide to Underfloor Air Distribution

• Floor slab mass can allow for content during humid summer conditions,
unoccupied thermal storage to be off-coil temperatures must be lower than the
used later for occupied period load supply air temperatures used with UFAD
leveling benefit. diffusers. To warm these temperatures back
up, return air is routed back into the supply
air stream, either at the zone air terminal or
at the supply fan housing, bypassing the
cooling coil. For the zone terminal design to
work, warm air is usually ducted back from
a ceiling return plenum. Placing ceiling
return registers along the exterior walls
brings an added benefit of pulling in any
thermal plumes that develop under high
solar loading conditions, reducing zone
cooling load in the summer and increasing
the first stage heating effectiveness in the
Figure 15 – Carpet used to winter. If active diffusers are used,
prevent plenum leakage additional floor registers are provided to
allow room air to reenter the plenum,
maintaining supply diffuser CAV feature
Return Air Design
when reduced loads lower the supply airflow
entering the plenum. Remember, if room air
MAINTAINING DISPLACEMENT is returned back into the zone without
BENEFITS flowing through the main cooling coil,
The key design elements for the return side cooling load credits indicated in the loads
of the air distribution system are to help section discussed above need to be lowered
create the partial displacement ventilation or eliminated all together.
effect and more directly remove local high
cooling loading conditions. Placing return
registers on the ceiling or high sidewall, Ductwork Design
coupled with the stratification layer created
by the short throw supply diffusers in the
One of the main benefits of UFAD is
floor, creates the desired overall upward
deleting ductwork associated with air
vertical flow of the air within the room.
distribution downstream of the zone
When a space has high cooling loads like a
terminals and using an airflow plenum
copier or a cluster of data terminals, place
underneath a raised access flooring system
the return directly above the area to
for low-pressure distribution to the room
effectively capture a large portion of the
diffusers. All the ductwork from the air-
heat. How much will depend on the height
handling unit to the zone terminals is laid
of the ceiling and nature of the supply
out and sized using the same methods used
airflow in the immediate area.
on traditional mixing ventilation systems.
This applies to both supply and return ducts,
RECIRCULATING RETURN AIR
as well as the outdoor air ductwork. There
Variations in return airflow occur when
is little which is special about UFAD
space humidity control is critical or a CAV
systems for duct mains and branches.
plenum design is used, either pressurized or
neutral. To control the supply air moisture

25
Design Guide to Underfloor Air Distribution

VERTICAL DROPS contractor and need to be sized like normal


A vertical drop into an access floor plenum ductwork (limit mains to 1,200 – 1,500 fpm
could result in excessive thermal decay if due to limitations on placement of vertical
the distance from the air source to the drop entries into the plenum, remember that
farthest point in the underfloor plenum is too future rearrangement of furniture/partition
great. Due to the thermal decay of the zoning above the floor will likely require
supply air temperature within the plenum, similar ductwork adjustment under the floor,
travel distance needs to be limited to 50-60 negating some of the cost savings. Also, air
feet from the plenum entry to the furthest highways almost always cause service utility
diffuser. This will require multiple entry re-routings around them when laying out
points on all but the smallest system. If power and communications.
shallower plenums are used and frequent
obstructions are possibilities, more than the SMOKE PARTITIONS AND FIRE
usual number of plenum entry points should WALLS
be included in the duct design. Whenever plenum areas become too large,
they inevitably cross over partitions or walls
AIR HIGHWAYS that need to meet life safety code
Another popular plenum distribution requirements extend down through the
technique is to use air highways within the plenum to the floor slab. HVAC zoning
plenum to distribute zone supply air to needs to pay attention to these lines and try
multiple points within the plenum. These not to cross over them. If air needs to be
are typically provided by the installing transferred over, do so with a hard duct

Figure 16– Floor Plan Chase Locations


26
Design Guide to Underfloor Air Distribution

sleeve with the appropriate smoke and/or HEATING INTERIORS WITH CENTRAL
fire damper installed per code. EQUIPMENT
Smaller single-story buildings are often able
Heating System Design to switchover during the peak heating times
to full heating from the central HVAC
CENTRAL SYSTEM OR HYBRID equipment. When this happens, normal
How we choose to heat the perimeter zones control strategies for the zone terminals will
depends primarily on the magnitude of the control mixing of the warmer SAT with
load and whether or not simultaneous recirculated plenum air and adjust terminal
heating and cooling is required. The need fan speed to control plenum pressure so that
for continuous cooling in too many interior the “cooling” diffusers will now operate
zones makes it hard to switch over the properly as heating diffusers.
central equipment to heating. If the
wintertime temperatures drop below 40ºF
and the building perimeter has more than 1/4 Control Systems
glass area, increased SAT’s will be required
to counteract the high heating loads and UFAD systems rely on proper design and
downdrafts along the outside walls. In operation of the controls like any other
either of these cases it is recommended that system. Listed below are concepts and
a separate heating system be designed for concerns that, if incorporated into the
the perimeter zones, creating a hybrid design, will result in maintaining the
system with UFAD heating being reserved stratification layer and its many benefits:
for the interior. • Most UFAD systems use pressurized
plenums and CAV passive diffusers,
PERIMETER FAN-COILS WITH LINEAR requiring some type of pressurization
BAR GRILLES control on either the zone mixing
High heating loads along the outside walls box or central equipment.
often require higher SAT’s than interior • Zone control with CAV diffusers
spaces need for morning warm-up or requires adjustment of the supply air
offsetting roof loads, so selecting zone fan- temperature at the air terminal. This
coils and locating them in the perimeter is best accomplished using Parallel
plenums is an ideal solution. Using either Fan Powered Mixing Boxes
hot water or electric heating coils allows (PFPMB) connected to the zone
local boosting of the zone SAT above those ceiling plenum return air that mixes
obtained by recirculating ceiling plenum air with the primary air.
that is traditionally stage one heating for • Resetting Supply Air Temperature
light load conditions. Use of a linear bar up under light loads allows
grille style diffuser is recommended to additional hours of outdoor air
spread the air out along the perimeter wall economizer cooling, especially in
and offset the downdrafts that develop. drier climates.
During summer cooling this style of grill is • Nighttime pre-cooling, done
also beneficial in treating the higher cooling correctly to avoid potential
loads that are typical along the perimeter of condensation on the plenum
most buildings. surfaces, can offset or delay thermal
decay of the zone SAT.

27
Design Guide to Underfloor Air Distribution

• Thermostat mounting heights are • A wall mounted space temperature


often being set lower because of sensor located in the zone will sense
ADA (Americans with Disabilities load requirements.
Act), from 54 to 48 inches above the • As the zone’s cooling load decreases,
access floor. This is actually a the fan speed increases, which
benefit because if mounted too high increases the amount of recirculated
the thermostat would be sensing the air drawn in from the ceiling plenum.
higher temperatures near the • Simultaneously, the amount of
stratification layer, requiring primary air is reduced to maintain a
adjusting the set point upwards to constant plenum pressure.
compensate. • The terminal fan will operate
• Systems, which use Parallel Fan whenever the primary air source is
Powered Mixing Boxes to control operating.
the zone primary airflow for System Start-up
ventilation requirements, can use • Points 1 to 2 from figure17 indicate
Demand Controlled Ventilation, that maximum cooling airflow is
DCV, to reduce primary airflow in established by the user-defined
lower occupancy periods resulting in maximum cooling plenum pressure
additional energy savings. set point until the zone comes under
• Control requirements of ASHRAE control at point 2. The fan operates
Standard 90.1 should be adhered to. at minimum speed.
Including setback requirements and • From point 2, slowing the primary
optimum start requirements. airflow until the minimum cooling
plenum pressure set point is reached
TYPICAL CONTROL SEQUENCES (Up at point 3 reduces the plenum
To Two 45X Mixing Boxes Serving A pressure.
Common Underfloor Plenum):
Plenum mixing boxes with variable speed
Typical Cooling Operation
fans can provide pressure and temperature • Point 3 indicates that the zone
control for plenums serving interior zones, temperature is above the control
and exterior zones using a separate (heating) set point; the plenum
perimeter heating system. This control pressure is maintained at the user-
sequence has the capability to over defined minimum cooling plenum
pressurize the plenum at start-up or during pressure setpoint.
high load requirements. Typical operating • At point 4 from figure17, the zone
sequence is shown in figure 17. temperature decreases; increasing the
• The sequence shows basic VAV fan speed to introduce more
control of the primary air. recirculated air, while
simultaneously reducing the primary
• The fan provides plenum
airflow, increases the plenum
temperature control by varying the
temperature. The plenum pressure
amount of recirculated air introduced
remains constant at the user-defined
into the plenum, while the primary
minimum cooling plenum pressure
air damper simultaneously maintains
set point.
the plenum pressure by controlling
the amount of primary air introduced • As indicated by points 4 to 5, should
into the plenum. the zone temperature continue to fall
the primary air damper will close,

28
Design Guide to Underfloor Air Distribution

but not below the user defined control may be configured to provide
minimum ventilation set point at constant volume heating for a
point 5 (may be set to zero), while constant supply of heated air to the
the fan provides recirculated air to zone.
maintain the plenum pressure set
point. Morning Warm-up
• Upon receiving a morning warm-up
Heating Operation signal generated by the air source
• Upon receiving a signal for heating controller, the primary air damper
and heated air is being provided from will modulate to maintain the
the air source, the system heating- maximum heating plenum pressure
mode is automatically in effect. set point if the zone temperature is
• If the zone temperature is above the below the occupied heating set point.
occupied heating setpoint, the This allows a maximum quantity of
primary air damper modulates to warm primary air to be delivered to
maintain the minimum heating the zone. As the zone’s temperature
plenum pressure set point. The fan rises, the plenum pressure is reduced
operates at minimum speed. to the minimum heating plenum
• Should the zone temperature fall, the pressure. The terminal fan operates
plenum pressure will increase up to at minimum speed.
the user-defined maximum heating
plenum pressure set point. The

UFAD Control Operating Sequences

Plenum Pressure
(Maximum Cooling)
2 1
Maximum Fan Airflow Primary Airflow
5
Warmer 4

Plenum Pressure
(Minimum Cooling)
Cool Plenum Temperature

Minimum Ventilation 4
5 Min. Fan Airflow

Occupied Heating Setpoint Occupied Cooling


Set point
(Heating & Morning Warm-up)

LEGEND
NTFC – Nighttime Free Cooling
--------- Air Source Supplying Heated Air
Air Source Supplying Cool Air

Figure 17 – Carrier UFAD Control Sequence Equipment Cooling

29
Design Guide to Underfloor Air Distribution

TYPICAL CONTROL SEQUENCES zone comes under control at point 4.


(Three or more 45X Mixing Boxes Serving a The fan operates at minimum speed.
Common Underfloor Plenum):
For applications requiring multiple mixing Typical Cooling Operation
boxes serving a common plenum, it is • Point 3 indicates that the zone
necessary to maintain a balance between temperature is above the control
each of the mixing units. To accomplish (heating) set point; the terminals
this, plenum mixing boxes with variable primary airflow is maximized to
speed fans can provide constant cfm and provide cold air to the plenum and
temperature control for these large common cool the space. The fan is at a
plenums. A Typical operating sequence is minimum airflow and the total
shown in figure 18. volume of air is maintained at the
• The sequences show basic VAV required constant airflow set point.
control of the primary air. • At point 4 from figure 18, as the
• The control provides volume airflow zone temperature decreases; the
from each terminal into a common discharge
access floor plenum, thus air temperature from the terminal
maintaining the plenum pressure into the plenum is increased by
constant during both cooling and increasing the fan speed to introduce
heating. The fan provides plenum more recirculated air, while
temperature control by varying the simultaneously reducing the primary
amount of recirculated air introduced airflow to maintain the total airflow
into the plenum, while the primary into the access underfloor plenum.
air damper simultaneously maintains • As indicated by points 4 to 5, should
the constant volume airflow set point the zone temperature continue to fall
by controlling the amount of primary the primary air damper will close,
air introduced into the plenum. but not below the user defined
• A wall mounted space temperature minimum ventilation set point at
sensor located in the zone will sense point 5 (may be set to zero), while
load requirements. the fan provides recirculated air to
• As the zone’s cooling load decreases, maintain constant airflow into the
the fan speed increases, which underfloor access plenum.
increases the amount of recirculated
air drawn in from the ceiling plenum. Heating/Morning Warm-up
• Simultaneously, the amount of
primary air is reduced to maintain • Upon receiving a heating signal
constant airflow into the plenum. generated by the air source
• The terminal fan operates whenever controller, (or a primary temperature
the primary air source is operating. sensor is installed to detect that the
air source is heating), the heating
mode is automatically in effect and
System Start-up the primary air damper is modulated
• Points 1 to 4 from figure 18 indicates to maintain constant airflow into the
that maximum cooling airflow is plenum. The fan operates at
provided by primary air until the minimum speed.

30
Design Guide to Underfloor Air Distribution

UFAD Control Operating Sequences

Warmer 4 3 2 1
Maximum Primary Airflow
5
Maximum Fan Airflow

Resulting Plenum Total Supply Airflow to Plenum


Pressure
Cooler Plenum Temperature

Minimum Primary Airflow 4


Minimum Fan Airflow Fan
Ventilation 5

Occupied Control
Setpoint

(Configured Heating)

Figure 18 – Carrier UFAD Control Sequence – Equipment Cooling

31
Design Guide to Underfloor Air Distribution

Installation Costs • Controls costs should be similar to


traditional systems when basic
Many owners and developers have found zoning is unchanged.
that raised floor systems with UFAD • Raised floor systems have the
significantly reduce costs associated with potential to reduce slab-to-slab
space reconfiguration. With the national heights by as much as 6 to 12 inches
churn rate now approaching 50%, it is not per floor. This is particularly
unexpected to find that many new office beneficial in mid-rise and high-rise
buildings use raised flooring. Buildings markets with zoning code height
using UFAD systems have certain cost limitations.
components that make them more expensive • Testing and balancing savings can be
than traditional systems and compensating realized from CAV pressurized
ones that lower the overall price premium plenum designs, which are
that currently exist for this application. essentially self-balancing.
Recent job costs show that raised floor can
represent a cost increase of from $3 to $5 Energy usage
per square foot. A few of these cost
components are worth mentioning: UFAD systems have the potential to save
energy in comparison to traditional designs.
• The raised floor system is the The bulk of these savings come from
component with the single largest reduced fan energy associated with lower
cost increase, which should be cost static pressures and overall CFM reductions
justified based on the benefits to the created by the stratification layer partial
entire service delivery system displacement ventilation effect. Documented
(HVAC, power, voice and data) and energy costs savings remain difficult to
not against the UFAD alone. predict because to date there is no energy
• Local building and fire inspectors simulation software that accurately models
may require sprinkler protection if UFAD system performance.
plenum depth exceeds 18 inches and
often require smoke detectors within
the plenum. O&M Considerations
• Generally, HVAC costs for central
cooling and heating equipment and Office building UFAD systems are quite
ductwork mains are no different for new, making it difficult to get actual owning
UFAD systems. and maintenance cost data to compare them
• Diffuser costs are dependent on the against traditional HVAC systems.
type(s) chosen for the majority of air Operations and maintenance costs are
delivered. primarily replacement costs for equipment,
• If a relatively open underfloor and labor expenses associated with
plenum can be used, significant maintaining the HVAC system and
ductwork savings can be realized responding to occupant complaints. While
compared to the typical overhead air many engineers believe that UFAD may
distribution system. prove to be more costly to service, research
suggests that the frequency of occupant

32
complaints will be reduced when they are Tests have shown an ideal airflow of
given some individual control of their local 0.6 cfm/sqft for good mixing while
environment. maintaining the stratification height
at 6 feet and keeping the room
RECOMMENDATIONS temperature gradient below 5º F.
6. Carefully run loads for both Qoccupied
and Qunoccupied, and determine if load
1. Do not eliminate the suspended
credits can be taken; equipment size
ceiling. Shallow up the ceiling
reduction will benefit the job costs.
plenum and use it as a return air
7. Select diffusers so that T50 throws
plenum, gaining additional airflow
are around 4-5 feet so as not to
benefits from assigning greater
disturb the stratification zone. Use
amounts of cooling load directly to
CAV passive swirls in the interior
the return air.
and uniformly loaded large perimeter
2. Keep plenum depths below 18 inches
spaces.
to avoid potential requirement for
8. Hybrid designs, using conventional
underfloor sprinklers.
VAV in high load/variable load
3. Do not use too many zoning barriers
situations, maximizes the benefits of
in the plenum or you will restrict the
the lower AHU supply air
ease of future rezoning and running
temperatures and keeps summertime
of service utilities to various points
humidity concerns under control.
of use.
9. Placing returns over heat producing
4. Using multiple vertical drops avoids
equipment and/or at the outside wall
air highways, while meeting the 50-
when high solar loads exist will
60 foot guideline for maximum
maximize benefit of the partial
travel to the farthest diffuser.
displacement ventilation effect.
5. Do not include excess safety factors;
10. DDC controls should be considered
airflows need to closely match load
as a basis of design for realizing true
requirements within the occupied
UFAD benefits.
zone so as not to over air the system.

33
Design Guide to Underfloor Air Distribution

References
Bauman, Fred S., 2003. “Underfloor Air Distribution (UFAD) Design Guide. American Society
of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Building Owners and Managers Association (BOMA) International and ULI, the Urban Land
Institute. 1999. “What do office tenants want”.

IFMA. 1997. Benchmark III International Facility Management Association, Houston Tex.

ASHRAE. 1990. ANSI/ASHRAE Standard 113-1990, Method of testing for room air
distribution. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.

ASHRAE. 1992 ANSI/ASHRAE Standard 55-1992, Thermal environmental conditions for


human occupancy. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.

ASHRAE. 2001b. ANSI/ASHRAE Standard 62-2001, Ventilation for acceptable indoor air
quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc.

ASHRAE. 2001c. ANSI/ASHRAE Standard 90.1-2001, Energy standard for buildings except
low-rise residential buildings. Atlanta: American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc.

34

You might also like