ELECTRICAL SYSTEM DESIGN

GENERAL LOADS FOR MCB


LIGHTHING LOADS:
LIGHTHING LOADS=3600VA =88.630+(1.5)(12)=106.630
150sqm * 24VA/m =3600VA
CONVENIENCE LOADS=4500VA USE 150AT 1000AF 2POLE
TOTAL= 3600VA
FIRST 3000VA @100% D.F=3000VA USE: 2- 50mm2 HW 1-30mm2 GW THHN
COVENIENCE LOADS
THE REST @35% D.F=1785VA
SMALL APPLIANCE:
TOTAL LOADS=4785VA
1500 * 2 =3000VA

LAUNDRY CIRCUIT:
FOR OTHER LOADS:
1500 * 1=1500VA
@100% D.F
TOTAL=4500VA
=15600VA

OTHER LOADS
TOTAL VA LOADS:
E-RANGE: 8000*0.8=6400VA
=15600+4785=20385VA
ACU@1.5Hp: 2*2300=4600VA

REF@1Hp: 1*1840=1840VA
TOTAL CURRENT
W-PUMP@2Hp=1*2760=2760VA
=20385/230=88.630A
TOTAL=15600VA