What is Cavitation
Cavitation consists of rapid vaporization and condensation within a
liquid. When local pressure falls to vapor pressure (approximately 0.25
psi / 0.018 bar absolute for cold water), vapor bubbles are formed and
when these bubbles travel to an area of higher pressure, the bubbles
collapse with phenomenal force and great localized stress. It is the
violent collapse of these vapor bubbles near valve components or
downstream piping surfaces, which cause cavitation damage and
subsequent performance degradation. Typically, the reason for low
pressure is that the pressure drop across a control valve has created very
high velocity in the seat area and corresponding low pressure because
potential (pressure) energy is reduced to compensate for the increase in
kinetic energy. This principle, known as Bernoulli’s Principle was named
after the mathematician Daniel Bernoulli and was first published in 1798
in his book, Hydrodynamica. The principle can be applied to various
types of fluid flow and simply states that when there is an increase in
the velocity of fluids then it must be accompanied by a decrease in the
fluid’s pressure, the total energy associated with the flow must remain
constant. And as summarized above, in scenarios where the pressure
drops to vapour pressure, cavitation will occur.
In control valves, the pressure drop typically occurs at or near the seat
area or just downstream. The shock waves and pressure fluctuations
resulting from these high velocity bubble collapses can also cause noise,
vibrations, accelerated corrosion, as well as limited valve flow. Typically
the cavitation is formed in the valve throttling area, the pressure
fluctuations radiate into the downstream pipe as noise. As the cavitation
increases the magnitude of these pressure fluctuations also increase.
System vibrations, pipe wall vibration, and component damage will
increase accordingly. The associated results can negatively impact the
reliability of control valve accessories and other system components.
1 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
2 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
Impacts of Cavitation
1. Strong vibrations – The shock waves generated by collapsing
vapor bubbles produce pressure fluctuations and cause vibration. As
cavitation increases, the magnitude of the vibrations increases by
several orders. Even systems with large valves that are properly
secured will exhibit pipe and valve movement during severe levels of
cavitation. Such vibrations can loosen bolts, cause fatigue of
connections, loosen or break restraining devices and ultimately lead
to structural damage or failure.
2. Loud noise – In its least violent form, cavitation produces only a
light crackling sound, about the same intensity as popcorn popping.
However, at more advanced stages cavitation noise becomes
objectionable and safety concerns may increase. For example,
cavitation in certain types of valves sounds like gravel rumbling
through the pipeline. In extreme cases in a large valve the noise can
even resemble the sound of dynamite exploding. The noise intensity
can exceed 100 dB, a level that constitutes a risk of hearing
damage.
3. Choked flow caused by vapor formation – Less flow capacity for
flow due to presence of vapour.
4. Erosion of valve components.
5. Destruction of the control valve.
6. Erosion and destruction of downstream piping in close proximity
to the valve.
7. Plant or distribution system shut down due to catastrophic
failure.
Predicting Cavitation
Many manufacturers of pilot-operated valves have the ability to assist in
predicting cavitation and defining what conditions should be of concern.
Often this information can be found in technical product catalogues. The
cold water cavitation coefficient3 is an approximation that many
manufacturers use for reference. In the case of globe style valves,
damage can occur when the cold water coefficient is less than the
0.7.This roughly translates to a 3 to 1 ratio indicator which is a rule of
thumb that Singer Valve uses to flag applications that require careful
consideration for implementing a variety of techniques to overcome or
contain cavitation.
3 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
4 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
5 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
file://localhost/Users/shorefamily/Library/Caches/TemporaryItems
/msoclip/0/clip_image014.png
file://localhost/Users/shorefamily/Library/Caches/TemporaryItems
/msoclip/0/clip_image016.png
file://localhost/Users/shorefamily/Library/Caches/TemporaryItems
/msoclip/0/clip_image018.png
6 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
In illustration 6 note the large separation between the wall of the valve
and the anti-cavitation cage. The bodies of the engineered orifice design
are specifically designed to fit a larger cage allowing higher Cv values
(increased flow) while the body is also specifically designed to allow
reasonable space between the anti-cavitation trim and the body
wall.This separation allows for even, uniform entry around the cage area
ensuring the vapour bubbles collapse symmetrically towards the center
of the anti-cavitation cage.
7 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
If there is not sufficient space between the cage and the wall of the
valve, flow into the cage area may be restricted offsetting the central
collapse of the vapor bubbles and forcing the vapor bubbles to the
extremity of the upper cage potentially encouraging the escape of these
vapor bubbles downstream.
First stage:
Flow into the cage. Severe cavitation may be present but the vapour
bubbles collapse inside the cage, away from metal.
Second stage:
Flow from cage to downstream. Pressure drop is controlled to assure no
cavitation.
The Nymboida River supplies the Shannon Creek Dam with its water and
has an inlet weir at the river takeoff that is approximately 128 m above
the pipe work in the valve pit. The dam delivery head is 33 m making the
normal head loss across the valve 95 m.This can increase to a maximum
of 105 m when the Nymboida River is at its maximum level as a result of
heavy rainfall.
8 of 10 11/27/2015 9:52 PM
Dealing with Cavitation in Control Valves - IWA Water Wiki - Open Acc... http://www.iwawaterwiki.org/xwiki/bin/view/Articles/DealingwithCavita...
After the second valve seal failure on the main valve that resulted in
severe leakage when closed, it was determined that with the significant
head loss across these valves and the variable flow range required, the
installed DN750 butterfly valve was oversized, and was an inappropriate
valve type for this application, resulting in severe cavitation damage to
the valve seats, leaf and seal.
The specific flow ranges, inlet pressure ranges and outlet pressure
requirements enabled the valve manufacturer to engineer a dual cage
orifice solution to their specific application.
The DN750 main inlet valve and DN250 bypass valve were replaced with a
single DN600 electronic dual solenoid control valve, with custom
engineered - Anti Cavitation Trim.
The valve was tested over a variable flow range capacity that was within
allowable licensed flows on the day. It was able to control flow and deal
with the head loss pressure easily with minimum noise and no vibration
from 0 to 400 l/sec on the day of commissioning. The operators are now
able to locally and remotely control the inlet flow of water into the dam
with no further concerns for valve failure or leakage from cavitation.
Author Bio's
Brad Clarke is the VP of Sales and Marketing for Singer Valve, a global
designer and manufacturer of automatic control valves. He has spent
the last 35 years working in the water industry and has written and
presented several papers around the world on key issues that improve
the operation, conservation and management of water systems.