CLASS A OR CLASS B POSTS REQUIRE STRETCHER BARS AND BANDS NOTE: BARB SELVAGE 1" ABOVE TOP OF LINE

NOTE: BARB SELVAGE 1" ABOVE TOP OF LINE POSTS ON FENCES 6’ HIGH AND
CLASS C POSTS HAVE THE FENCE FABRIC WOVEN INTO THE POST OVER. KNUCKLED SELVAGE FOR FENCES LESS THAN 6’
(SEE MANUFACTURER’S INSTRUCTION)

492’ MAX 492’ MAX

8’ MAX 8’ MAX 8’ MAX 8’ MAX 8’ MAX 8’ MAX 8’ MAX

END POST INTERMEDIATE POST INTERMEDIATE POST INTERMEDIATE POST CORNER I


NTERMEDIATE POST
LINE POST LINE POST (PULL POST) (PULL POST) POST (PULL POST)
(PULL POST)
TENSION WIRE WITH CAP WITH CAP

" d TRUSS ROD " d TRUSS ROD


STRETCHER BAR

BANDS TENSION WIRE

6"
FINISHED GRADE

2" MAX.
TURNBUCKLE TURNBUCKLE TURNBUCKLE TURNBUCKLE
TURNBUCKLE
KNUCKLED SELVAGE
(SEE NOTE 6)
(SEE NOTE 6)
CONCRETE BASE

TERMINAL SECTION LINE SECTION PULL SECTION CORNER INSTALLATION

KNUCKLED SELVAGE BARB SELVAGE


NOTES:

1. POSTS, INCLUDING ENCASEMENT, SHALL BE SET INSIDE THE R.O.W. LINE SO


THAT FENCING PLACED UPON THE R.O.W. SIDE OF POSTS WILL BE AS NEARLY
TENSION WIRE ON THE R.O.W. LINE AS IS POSSIBLE. WHEN DIRECTED BY THE ENGINEER, THE
FABRIC SHALL BE PLACED ON THE OPPOSITE SIDE IN ORDER FOR FABRIC TO
COLLAR: WELDABLE STEEL OR CAST STEEL BE PULLED TIGHT AGAINST THE POST.
GALVANIZED IN ACCORDANCE WITH SECTION
719-01 TYPE I OR CAST IRON OR MALLEABLE IRON 2. POST IN ROCK. WHERE SUBSTANTIAL ROCK IS ENCOUNTERED. A HOLE 1"
6 GA. ALUMINUM TIE NOTE: DRIVE ANCHOR ANGLES LARGER IN DIAMETER THAN THE POST. AND OF 12" MIN. DEPTH FOR LINE
END, CORNER, AND TOP AND BRACE ROLLFORMED NORMAL TO FENCE FABRIC
WIRE TWIST AROUND POST POSTS, AND 1’-6" MINIMUM DEPTH FOR CORNER, END, AND INTERMEDIATE
INTERMEDIATE POST POST POST
POSTS SHALL BE MADE. AFTER INSERTING THE POSTS, THE HOLES SHALL BE
" GALVANIZED BOLT
BACK FILLED WITH A HAND MIXED 1:2 MORTAR CONSISTING OF ONE PART
SUGGESTED METHOD OF TYING CLASS "C" ROLLFORMED SECTIONS
PORTLAND CEMENT TO TWO PARTS FINE AGGREGATE MIXED TO A PLASTIC
TENSION WIRE TO LINE POST (SEE POST AND RAIL SCHEDULE FOR DIMENSIONS) CONSISTENCY SHOWING NO SIGNS OF FREE WATER. THE HAND MIXING AND
CONSOLIDATION OF THE MORTAR SHALL BE PERFORMED IN A MANNER
COLLAR APPROVED BY A ENGINEER.

FINISHED GRADE 3. CORNER POSTS SHALL BE USED AT BREAKS IN VERTICAL GRADE, AND CHANGES

4"
IN HORIZONTAL ALIGNMENT OF 15n AND OVER. PULL POSTS SHALL BE USED
1" X 1" X " X 2’-6" c BOLTS EVERY 492’ ON RUNS OF CHAIN LINK FENCE OR AS DIRECTED BY THE ENGINEER.
GALVANIZED STEEL ANGLE
POST AND RAIL SECTION ANCHOR
4. DETAIL DRAWING FOR CHAIN LINK FENCE THAT THE CONTRACTOR PLANS
ANGLE
TO ERECT SHALL BE SUBMITTED TO THE ENGINEER. NO FENCE SHALL BE
4 n
5
STEEL ALUMINUM n 45 ERECTED PRIOR TO THE APPROVAL OF THE VARIES DETAILS.

-0"
USE SECTION 5. STEEL PIPE AND STEEL SHAPES INDICATED ON THIS SHEET SHALL NOT BE

3’
NPS ROLLFORMED O.D. WEIGHT NPS ROLLFORMED O.D. WEIGHT
LIGHTER IN WEIGHT THAN 95% OF THAT SPECIFIED. THEY MAY EXCEED
DESIGNATOR AND H POSTS LBS/FT DESIGNATOR AND H POSTS LBS/FT
THE REQUIRED WEIGHT.
LINE POST
CLASS A SCHEDULE 40 PIPE 2 2" 3.65 2 2" 1.26 6. THE CONTRACTOR SHALL HAVE THE OPTION OF SETTING THE LINE POSTS
END, CORNER AND
IN 10"d BY 3’ DEEP CONCRETE BASES WITH THE POST EMBEDDED 2’-6"
INTERMEDIATE POSTS CLASS B STEEL TUBING 2 2" 3.12
OR USING METHODS OF DRIVING AND ANCHORING SPECIFIED BY THE
FOR FENCES 6’ AND UNDER
CLASS C ROLLFORMED 3" X 3" 5.10 MANUFACTURER. HOWEVER, LINE POSTS WITH TRUSS RODS ATTACHED
AND ALL END, CORNER AND INTERMEDIATE POSTS SHALL BE SET IN
CLASS A SCHEDULE 40 PIPE 2 2 5.79 2 2" 2.00
END, CORNER AND 3’-3" CONCRETE BASES. THESE CONCRETE BASES SHALL BE A MINIMUM
INTERMEDIATE POSTS CLASS B STEEL TUBING 2 2 4.64 OF 10"d BY 3’-0" DEEP WITH THE POST EMBEDDED 2’-6" FOR FENCES
FOR FENCES OVER 6’ 6’ HIGH OR LESS AND 12"d BY 3’-6" DEEP WITH THE POST EMBEDDED
CLASS C ROLLFORMED 3" X 3" 5.10 DRIVE ANCHOR 3’ FOR FENCES OVER 6’ HIGH. FOR GATE POSTS SEE THE CURRENT STANDARD
CLASS A SCHEDULE 40 PIPE 1 1" 2.72 1 1" 0.94 SHEET TITLED "GATES AND CHAINLINK FENCE ADJACENT TO GATE".

CLASS B STEEL TUBING 1 1" 2.28


7. TOP TENSION WIRE SHALL BE FASTENED TO EACH POST IN A MANNER
LINE POSTS FOR FENCES CLASS C ROLLFORMED 1" X 1" 1.85 APPROVED BY THE ENGINEER.
6’ AND UNDER
H POSTS 2" X 1" 3.43 1" X 1" 0.90

H POSTS 2" X 2" 1.22

CLASS A SCHEDULE 40 PIPE 2 2" 3.65 2 2" 1.26

CLASS B STEEL TUBING 2 2" 3.12 ACCESSORY STEEL ALUMINUM


LINE POSTS FOR FENCES STATE OF NEW YORK
GREATER THAN 6’ AND CLASS C ROLLFORMED 1" X 1" 2.40 " d ALUMINUM WIRE AT
EQUAL TO OR LESS THAN 8’ FABRIC TIES FOR 6 GA. ALUMINUM WIRE
14" C.C. MAX OR " X "
DEPARTMENT OF TRANSPORTATION
H POSTS 2" X 1" 3.43 1" X 1" 0.90 LINE POSTS AT 14" O.C. MAX.
CLIPS AT 14" C.C. MAX.
2" X 2" 1.22
dgn

FABRIC TIES FOR 11 GA. ALUMINUM WIRE " d ALUMINUM WIRE U.S. CUSTOMARY STANDARD SHEET
CLASS A SCHEDULE 40 PIPE 2 2" 3.65 2 2" 1.26 12" O.C. MAX. AT 12" C.C. MAX.
01

TENSION WIRE
FILE NAM E = 607-05_010809e1.
DATE/TIM E = 14-NOV-2013 09:

LINE POSTS FOR FENCES


CLASS B STEEL TUBING 2 2" 3.12 TOP & BOTTOM
GREATER THAN 8’ AND 7 GA. GALVANIZED
" d ALUMINUM WIRE
EQUAL TO OR LESS THAN 10’ CLASS C ROLLFORMED 2" X 1" 2.78 TENSION WIRE STEEL

H POSTS 2" X 1" 3.43 2" X 2" 1.22 CHAINLINK FENCE


WITH TOP TENSION WIRE
USER = rlohse

CLASS A SCHEDULE 40 PIPE 2 2" 5.79 2 2" 2.00


LINE POSTS FOR FENCES CLASS B STEEL TUBING 2 2" 4.64
OVER 10’
H POSTS 2" X 1" 3.43 2" X 2" 1.22
APPROVED: NOVEMBER 4, 2013 ISSUED UNDER EB 08-036
ERRATA 1 EFF. 01/09/2014
* DO NOT USE 3" X 3" ROLLFORMED POST ON FENCES OVER 8’
ISSUED WITH EB 13-042 /S/ RICHARD W. LEE, P.E.