* STAAD.Pro V8i SELECTseries5 *
* Version 20.07.10.64 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= NOV 23, 2019 *
* Time= 11:43:46 *
* *
* USER ID: *
****************************************************
1. STAAD SPACE
INPUT FILE: BAPATLA-MORTUARY.STD
2. START JOB INFORMATION
3. ENGINEER DATE 18-NOV-19
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KN
7. JOINT COORDINATES
8. 1 0 0 0; 2 4.73 0 0; 3 9.64 0 0; 4 14.54 0 0; 5 17.77 0 0; 6 0 0 7.77
9. 7 4.73 0 7.77; 8 9.64 0 7.77; 9 14.54 0 7.77; 10 17.77 0 7.77; 11 0 2 0
10. 12 4.73 2 0; 13 9.64 2 0; 14 14.54 2 0; 15 17.77 2 0; 16 0 2 7.77
11. 17 4.73 2 7.77; 18 9.64 2 7.77; 19 14.54 2 7.77; 20 17.77 2 7.77; 21 0 6 0
12. 22 4.73 6 0; 23 9.64 6 0; 24 14.54 6 0; 25 17.77 6 0; 26 0 6 7.77
13. 27 4.73 6 7.77; 28 9.64 6 7.77; 29 14.54 6 7.77; 30 17.77 6 7.77
14. 31 14.54 2 3.545; 32 17.77 2 3.545; 33 14.54 6 9.27; 34 17.77 6 9.27
15. MEMBER INCIDENCES
16. 1 1 11; 2 2 12; 3 3 13; 4 4 14; 5 5 15; 6 6 16; 7 7 17; 8 8 18; 9 9 19
17. 10 10 20; 101 11 21; 102 12 22; 103 13 23; 104 14 24; 105 15 25; 106 16 26
18. 107 17 27; 108 18 28; 109 19 29; 110 20 30; 1001 11 12; 1002 12 13; 1003 13 14
19. 1004 14 15; 1005 31 32; 1006 16 17; 1007 17 18; 1008 18 19; 1009 19 20
20. 1010 16 11; 1011 17 12; 1012 18 13; 1013 19 31; 1014 31 14; 1015 20 32
21. 1016 32 15; 2001 21 22; 2002 22 23; 2003 23 24; 2004 24 25; 2005 26 27
22. 2006 27 28; 2007 28 29; 2008 29 30; 2009 33 34; 2010 26 21; 2011 27 22
23. 2012 28 23; 2013 33 29; 2014 29 24; 2015 34 30; 2016 30 25
24. DEFINE MATERIAL START
25. ISOTROPIC CONCRETE
26. E 2.5E+007
27. POISSON 0.17
28. DENSITY 25
29. ALPHA 1E-005
30. DAMP 0.05
*** NOTE: If any floor diaphragm is present in the model Wind Load definition
should be defined after Floor Diaphragm definition. Otherwise wind
load generation may be unsuccessful during analysis.
P R O B L E M S T A T I S T I C S
-----------------------------------
*********************************************************
* *
* TIME PERIOD FOR X 1893 LOADING = 0.09000 SEC *
* SA/G PER 1893= 2.350, LOAD FACTOR= 1.000 *
* VB PER 1893= 0.0800 X 3100.37= 248.03 KN *
* *
*********************************************************
74. CHANGE
75. **EARTHQUAKE LOAD IN Z DIRECTION
76. LOAD 8 LOADTYPE NONE TITLE SL(+Z)
77. 1893 LOAD Z 1
78. PERFORM ANALYSIS
*********************************************************
* *
* TIME PERIOD FOR Z 1893 LOADING = 0.13000 SEC *
* SA/G PER 1893= 2.500, LOAD FACTOR= 1.000 *
* VB PER 1893= 0.0600 X 3100.37= 186.02 KN *
* *
*********************************************************
79. CHANGE
80. **EARTHQUAKE LOAD IN - X DIRECTION
*********************************************************
* *
* TIME PERIOD FOR X 1893 LOADING = 0.09000 SEC *
* SA/G PER 1893= 2.350, LOAD FACTOR=-1.000 *
* VB PER 1893= 0.0800 X 3100.37= -248.03 KN *
* *
*********************************************************
84. CHANGE
85. **EARTHQUAKE LOAD IN - Z DIRECTION
86. LOAD 10 LOADTYPE NONE TITLE SL(-Z)
87. 1893 LOAD Z -1.
88. PERFORM ANALYSIS
*********************************************************
* *
* TIME PERIOD FOR Z 1893 LOADING = 0.13000 SEC *
* SA/G PER 1893= 2.500, LOAD FACTOR=-1.000 *
* VB PER 1893= 0.0600 X 3100.37= -186.02 KN *
* *
*********************************************************
89. CHANGE
90. *******************************************************************************
91. LOAD 1 LOADTYPE DEAD TITLE DEAD LOAD
92. SELFWEIGHT Y -1
93. MEMBER LOAD
94. *********** 230MM BRICK WALL LOAD OF HEIGHT 4M ***********
95. 1001 TO 1011 1013 TO 1016 UNI GY -17.665
96. *********** 230MM BRICK WALL LOAD OF HEIGHT 1M ***********
97. 2001 TO 2016 UNI GY -4.42
98. FLOOR LOAD
99. *********** TERRACE LOAD OF 150MM THICK SLAB************
X = 0.938384356E+01
Y = 0.391815918E+01
Z = 0.400060157E+01
X = 0.000000000E+00
Y = 0.399999998E+01
Z = 0.388500003E+01
X = 0.177700004E+02
Y = 0.399999998E+01
Z = 0.388500005E+01
X = 0.888500021E+01
Y = 0.399999998E+01
Z = 0.000000000E+00
X = 0.888500021E+01
Y = 0.399999998E+01
Z = 0.777000005E+01
201. *******************************
202. LOAD LIST 201 TO 217
203. *******************************
204. START CONCRETE DESIGN
205. CODE INDIAN
206. ************* BEAM DESIGN PROPERTIES *********
207. CLEAR 0.025 MEMB 1001 TO 1016 2001 TO 2016
208. FC 25000 MEMB 1001 TO 1016 2001 TO 2016
209. FYMAIN 500000 MEMB 1001 TO 1016 2001 TO 2016
210. FYSEC 500000 MEMB 1001 TO 1016 2001 TO 2016
211. MAXMAIN 20 MEMB 1001 TO 1016 2001 TO 2016
212. MAXSEC 12 MEMB 1001 TO 1016 2001 TO 2016
213. MINMAIN 12 MEMB 1001 TO 1016 2001 TO 2016
214. MINSEC 8 MEMB 1001 TO 1016 2001 TO 2016
215. ************* COLUMN DESIGN PROPERTIES *********
216. CLEAR 0.04 MEMB 1001 TO 1016 2001 TO 2012 2014 2016
217. FC 25000 MEMB 1 TO 10 101 TO 110
218. FYMAIN 500000 MEMB 1 TO 10 101 TO 110
219. FYSEC 500000 MEMB 1 TO 10 101 TO 110
220. MAXMAIN 25 MEMB 1 TO 10 101 TO 110
221. MAXSEC 12 MEMB 1 TO 10 101 TO 110
222. MINMAIN 12 MEMB 1 TO 10 101 TO 110
223. MINSEC 8 MEMB 1 TO 10 101 TO 110
============================================================================
B E A M N O. 1001 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1003 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1004 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1005 D E S I G N R E S U L T S
============================================================================
============================================================================
B E A M N O. 1006 D E S I G N R E S U L T S
============================================================================
============================================================================
B E A M N O. 1007 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1009 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1010 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1011 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1012 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1013 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1014 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 1015 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2001 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2002 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2003 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2004 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2005 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2006 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2007 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2008 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2009 D E S I G N R E S U L T S
============================================================================
============================================================================
B E A M N O. 2010 D E S I G N R E S U L T S
============================================================================
============================================================================
B E A M N O. 2011 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2013 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2014 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
============================================================================
B E A M N O. 2015 D E S I G N R E S U L T S
============================================================================
B E A M N O. 2016 D E S I G N R E S U L T S
SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------
============================================================================
C O L U M N N O. 1 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 2 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 3 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 4 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 5 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 6 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 7 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 8 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 9 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 10 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 101 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 102 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 103 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 104 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 105 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 106 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 107 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 108 D E S I G N R E S U L T S
============================================================================
============================================================================
C O L U M N N O. 109 D E S I G N R E S U L T S
============================================================================
C O L U M N N O. 110 D E S I G N R E S U L T S
230. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2014 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************