You are on page 1of 15

HYDRONIC TERMINALS

Recuperatori di Calore HRD2


HEAT RECOVERY

EC MOTOR

2
Heat Recovery – General Information

 Circulating always on the same


environment the air is charged with
anhydride carbon and pollutants.
It must be changed and renewed.

 Fresh oxygenated air must be taken from outside and


introduced on inside environment, but this operation normally
has a high cost.

 If part of the energy of the exhausted air, can be transferred to


the fresh air, the cost of the air renewal process can be reduced.
The heat recovery unit HRD2 can manage this through the
utilization of a counterflow high efficiency heat exchanger.

3
Heat Recovery - Application

900450 – 3800
÷ 6000 m3/h  Commercial Sector
m3/h
 Schools

 Industrial environments

 Offices

 Restaurants

 Gym

η > 75%  …………………

4
Heat Recovery - Nomenclature

HRD2 050 OR
VERSIONS
OR Horizontal inst. Right air delivery
OL Horizontal inst. Left air delivery

VR Vertical inst. Right air delivery


VL Vertical inst. Left air delivery

SIZE – 6 Sizes
HRD2 (EC Motor)
050, 090, 140,
210, 300, 400

NAME/RANGE
HRD2: EC Motor

5
Heat Recovery - CONFIGURATIONS

VERSIONS
OR Horizontal inst. Right air delivery
OL Horizontal inst. Left air delivery

VR Vertical inst. Right air delivery


VL Vertical inst. Left air delivery

6
Heat Recovery – Construction Details

7
Heat Recovery – Electrical Box

Built-in electrical box with electronic


Control of all functions as:
 Manual control of EC fans,
 Auto control of EC fans (by pressure,
temp. or air quality sensor)
 Heating/Cooling water valve
 Electrical heater (pre and re heater)
 Free cooling control
 Post ventilation
 Weekly programming
 Alarm management
 Winter/Summer Remote
 Fire alarm digital input
 BMS connection

8
Heat Recovery Remote Control

 Remote control for setting and visualization


of the functioning parameters

 Control box installed on the front panel

 Temperature probe connection


(situated on 4 sides of the units)

9
Heat Recovery – Erp Compliant

ErP2016

ErP2018
η>75%

SIZE 050 090 140 210 300 410

Air Flow [m3/h] 426 776 1230 1843 2720 3685


Recovering Capacity (kW) 3,35 5,87 9,36 14,07 20,60 27,84
SFP* Limit (W/m3/s) 1337 1283 1201 1162 1113 1078
Efficiency on dry conditions (%) 81,4 80,1 77,9 77,4 76,8 76,8
* SFP: Specific Fan Power
Dry Conditions at nominal air flow :
External air 5° and internal air 25°

10
HRD2 Key Features

1. High Efficiency > 75% heat exchanger

2. Centrifugal Fan with EC Motor

3. M5 Class filter on return air and F7 Class filter on extract air

4. 6 Sizes for Vertical and Horizontal Installation

5. Huge range of accessories

6. Electrical box to manage all unit functions

7. BMS Connection

8. Self-supporting body with 25 mm thick p.

9. By Pass for free cooling and free h.

11
Heat Recovery By - Pass System

12
Heat Recovery – Water Coil Section

 External section of water coil, that can be used


to integrate the total recovery energy in order to
reach the desired temperature conditions on the
inside environment.

 The Coil section is connected to the


basic unit on supply air/return air side

 3 row water coil suitable both for heating and


cooling mode

 Aluminum dray tray

Cooling Capacity*: 2,46 kW ÷ 20,68 kW * Air inlet condition: 28°C, UR 60%, in/out water temp. 7°/12°C
Heating Capacity**: 3,30 kW ÷ 27,50 kW ** Air inlet condition: 13°C, in/out water temp. 45°/40°C

13
Heat Recovery – CO2 Sensor

 CO2 Sensor of ducted type, to be placed on


the return duct.

 It allows a continuous modulation of air flow


based on air quality desired level.
(set point 700 ppm)

14

You might also like